Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Similar documents
Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

η second law = Second law efficiency

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

ADVANCES in NATURAL and APPLIED SCIENCES

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Chapter 10. Refrigeration and Heat Pump Systems

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Comparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

*Corresponding author;

Theoretical study on a modified subcooling vaporcompression refrigeration cycle using hydrocarbon mixture R290/R600a

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Thermodynamics I. Refrigeration and Heat Pump Cycles

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

A RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E)

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Control Method Of Circulating Refrigerant Amount For Heat Pump System

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

CHAPTER 1 INTRODUCTION

(Refer Slide Time: 00:00:40 min)

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Environment Protection Engineering

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

Performance investigation of Air-conditioning system using ejector as expansion device

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

A Comparison Between Refrigerants Used In Air Conditioning

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Oyelami S., Bolaji B. O.

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Reheating Refrigeration System

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Volume 1, Issue 2 (2013) ISSN International Journal of Advance Research and Innovation

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Performance analysis of a vapour compression-absorption cascaded refrigeration system with undersized evaporator and condenser

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Performance of an Improved Household Refrigerator/Freezer

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Study of R161 Refrigerant for Residential Airconditioning

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System ABSTRACT

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

Performance Evaluation Of A Vapour Compression Refrigeration System For Simultaneous Cooling And Heating By Using R22 And Alternative Refrigerants

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

A COMPARATIVE STUDY OF REFRIGERANTS R12, R134A, R407 & R717 FOR VAPOUR COMPRESSION REFRIGERATION SYSTEM

A study of Transient Performance of A Cascade Heat Pump System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Transcription:

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution of CFC s and HCFC s due to their adverse impact on atmospheric ozone layer which protects earth from U.V rays. The CFCs have been entirely ruled out since 1995 and a longterm basis HCFCs must be replaced by 2020. All this events motivated HFC refrigerants which are harmless to ozone layer. In this paper thermodynamic analysis of cascade refrigeration system has been done using three different refrigerant pairs R13-R12, R290-R23, and R404A-R23. Effect of various operating parameters i.e. evaporator temperature, condenser temperature, temperature difference in cascade condenser and low temperature cycle condenser temperature on performance parameters viz. COP, exergetic efficiency and refrigerant mass flow ratio have been studied. Thermodynamic analysis shows that out of three refrigerant pairs R12-R13, R290-R23 and R404A-R23 the COP of R290-R23 refrigerant pair is highest. Keywords Thermodynamic analysis, cascade refrigeration system, COP, exergetic efficiency. A I. INTRODUCTION cascade refrigeration system consists of two independently operated single-stage refrigeration systems. A lower system that maintains a lower evaporating temperature and produces a refrigeration effect and a higher system that operates at a higher evaporating temperature. For some industrial applications that require moderately low temperatures with a considerably large temperature and pressure difference then the single stage vapor-compression refrigeration cycles become impractical. One of the solutions for such cases is to perform the refrigeration in two or more stages which operate in series. These refrigeration cycles are called cascade refrigeration cycles. Therefore, cascade systems are employed to obtain high-temperature differentials between the heat source and heat sink and are applied for temperatures ranging from 70 C to -100 C. Application of a three-stage vapor compression system for evaporating temperature below 70 C is limited, because of difficulties with refrigerants reaching their freezing temperatures. The Montreal protocol and Kyoto underlined the need of substitution of CFC s and HCFC s regarding their bad impact on atmospheric ozone layer which protects earth from U.V rays [1]. A lot of research work is going on to analyze the performance of cascade refrigeration system using alternate refrigerants. J. Alberto Dopazo et al. [2] carried Theoretical analysis of a CO 2 NH 3 cascade refrigeration system for A. D. Parekh and P.R Tailor are with the Sardhar Vallabhbhai National Institute of Technology, Surat, India 395007 (e-mail: adp@med.svnit.ac.in, prt@med.svnit.ac.in). cooling applications at low temperatures; they concluded that COP increases 70% when the T E varies from -55 C to -30 C. The COP diminishes 45% when the T C increases from 25 C to 50 C. The system COP diminishes 9% when T CC varies from 3 C to 6 C. The exergetic efficiency decreases 45% and 9% with the increases indicated above in T C and T CC. H.M. Getu and P.K. Bansal [3] carried Thermodynamic analysis of an R744 R717 cascade Refrigeration system, they showed that an increase in condensing temperature resulted in a decrease in COP and an increase in refrigerant mass flow ratios. An increase in evaporating temperature increased COP of the system and decreased mass flow ratios. An increase in temperature difference in cascade condenser reduced both COP and mass flow ratios. D. Pyasi and R. C. Gupta [4] carried work on Performance analysis of R404A-R508b Cascade Refrigeration cycle for low temperature, they concluded that System overall performance (COP) and Exergetic efficiency gets increased by 0.88 to 1.19 and 0.60 to 0.626 as the evaporator temperature is varied from (-90 0 C to- 70 0 C) while other parameters are kept constant, The system COP decreases by 1.06 to 0.61 and exergetic efficiency deteriorates by 0.65 to 0.43 when condenser temperature of high stage is varied from 30 C to 50 C keeping other parameter constant, System COP deteriorates by 0.95 to 0.84 and Exergy by 0.60 to 0.53 when temperature difference of cascade condenser is varied from 2 C to 10 C. Mass flow ratio is decreased from (1.84 to 1.34) when low stage condenser temperature is varied from -45 C to -20 C keeping various other parameter constant. In present study the thermodynamic analysis of cascade refrigeration system has been done with three refrigerant pairs R12-R13, R290-R23 and R404A-R23. The effect of various operating parameters is studied on performance parameters. Thermodynamic analysis is carried out by developing computational model in Engineering Equation solver (EES). II. CASCADE REFRIGERATION SYSTEM Fig. 1 shows cascade refrigeration system with its components. It consists of two stages lower temperature (pressure) cycle and higher temperature (pressure) cycle which is connected by cascade condenser. The main components of cascade system are: Low temperature compressor, High temperature compressor, Condenser, Evaporator, Cascade Condenser and Throttling devices for Low temperature cycle and High temperature cycle. During process 1-2 the low temperature cycle refrigerant is compressed isentropically. It is then passes through cascade condenser where it gives heat to refrigerant of higher 1351

temperature cycle (process 2-3). It is expands in throttling device (process 3-4) and further passes to evaporator (process 4-1) to produce necessary refrigerating effect. In higher stage refrigerant is compressed in high temperature cycle compressor (process 5-6), then it passed through condenser where it rejects heat (process 6-7). It expands isentropically in throttling device (process 7-8) further passes to cascade condenser where heat transfer between two refrigerants takes place. (1) Power consumed by HT cycle compressor is calculated by equation ( ): (2) Power consumed by LT compressor is calculated by the equation ( ): Fig. 1 Cascade refrigeration system Fig. 2 Temperature-Entropy diagram of cascade refrigeration system III. THERMODYNAMIC MODELING The thermodynamic analysis of the two-stage cascade refrigeration system was performed based on the following general assumptions: Negligible pressure and heat losses or gains in the pipe networks or system components. The dead state is T 0 =25 C and P 0 =1 atm Negligible changes in kinetic and potential energy. Isenthalpic expansion of refrigerants in expansion valves. The capacity of the evaporator is calculated by the equation ( ): (3) Exchange of heat by refrigerants in cascade condenser is calculated by the equation ( ): (4) Refrigerant mass flow ratio is calculated by the equation ( / ): Heat rejected by condenser calculated by the equation ( ): (5) (6) Coefficient of performance of system is calculated by equation [5] (7) Exergetic efficiency of system is calculated by the equation [6] (8) Reversible work input of system is calculated by the equation [7] = 1 (9) These all above equations are used for thermodynamic modeling of cascade refrigeration system. IV. RESULTS AND DISCUSSIONS Computational model has been developed in EES to find effect of various design and operating parameters on the on the performance parameters which are coefficient of performance (COP), exergetic efficiency (η exe ) and refrigerant mass flow ratio (m H /m L ). The different operating parameters which are varied during thermodynamic analysis and their effect on the performance parameter are listed in this section. The parameters which are varied explained here. 1. Evaporator temperature (T E ) varied from -80 C to -60 C 2. Condenser temperature (T C ) varied from 25 C to 45 C 1352

3. Temperature difference in cascade condenser ( T CC ) varied from 2 C to 6 C 4. L.T cycle condenser temperature (T casl ) varied from -5 C to -35 C Standard operating parameters of cascade refrigeration system are taken as below 1. Evaporator temperature (T E ) = -80 C 2. Condenser temperature (T C ) = 25 C 3. Temperature difference in cascade condenser ( T CC ) = -3 C 4. Low temperature cycle condenser temperature (T casl ) = -5 C A. Effect of Evaporator Temperature (T E ): The effect on COP, exergetic efficiency and refrigerant mass flow ratio, when evaporator temperature varied from -80 C to -60 C in the interval of 5 C keeping other parameters constant is shown in Figs. 3 (a), (b), and (c) respectively. For a given condensing temperature, the pressure ratio increases as the evaporator temperature decreases. Fig. 3 (a) shows that as evaporator temperature increases the COP increases. COP varies from 1.147 to 1.764, 1.176 to 1.779, and 1.158 to 1.743 for R12-R13, R290-R23, and R404A-R23 respectively. Among all three pair R12-R13 shows maximum change in COP followed by R290-R23 and R404A-R23. Figs. 3 (b) and (c) show that as evaporator temperature increases, the exergetic efficiency improves while mass flow rate decreases. Exergetic efficiency varies from 0.6175 to 0.6976, 0.6335 to 0.7033 and 0.6233 to 0.689 for R12-R13, R290-R23 and R404A-R23 respectively. For R12-R13 the variation of exergetic efficiency is highest followed by R290- R23 and R404A-R23. Fig. 3 (a) Effect of evaporator temperature on COP Fig. 3 (b) Effect of evaporator temperature on exergetic efficiency Fig. 3 (c) Effect of evaporator temperature on refrigerant mass flow ratio B. Effect of Condenser Temperature (T C ): The condenser temperature is varied from 25 C to 45 C in the interval of 5 C and other parameters are kept constant. The effect on COP, exergetic efficiency and refrigerant mass flow ratio is shown in Figs. 4 (a), (b), and (c) respectively. Fig. 4 (a) shows that when condensing temperature varied from 25 C to 45 C the COP of system is decreasing and It decreases from 1.147 to 0.9453, 1.176 to 0.9536 and 1.158 to 0.9038 for R12-R13, R290-R23 and R404A-R23 respectively. Out of three refrigerant pairs R404A-R23 shows maximum change followed by R290-R23 and R12-R13. Fig. 4 (b) shows that as condensing temperature increases the exergetic efficiency is decreases. The exergetic efficiency decreases from 0.6175 to 0.509, 0.6335 to 0.5135 and 0.6233 to 0.4867 respectively R12-R13, R290-R23 and R404A-R23 respectively. R404A-R23 shows maximum variation for condensing temperature change followed by R290-R23 and R12-R13. Fig. 4 (c) shows that as condensing temperature increases the refrigerant mass flow ratio increases. The increases are from 0.9769 to 1.157, 0.7217 to 0.883 and 1.719 to 2.28 for R12-R13, R290-R23 and R404A-R23 respectively. The R404A-R23 show maximum variation followed by R12-R13 and R290-R23 respectively. 1353

Fig. 4 (a) Effect of condenser temperature on COP Fig. 4 (b) Effect of condenser temperature on exergetic efficiency difference in cascade condenser on COP, exergetic efficiency and refrigerant mass flow ratio is shown in Figs. 5 (a), (b) and (c) respectively. The effect of temperature difference in cascade condenser on COP is shown in Fig. 5 (a), when the temperature difference in cascade condenser increases the COP of system decreases. The COP varies from 1.158 to 1.112, 1.189 to 1.14 and 1.171 to 1.119 for R12-R13, R290-R23 and R404A-R23 respectively. Out of three refrigerant pairs R404A-R23 responds maximum for change in temperature difference in cascade condenser. The effect of temperature difference in cascade condenser on exergetic efficiency is shown in Fig. 5 (b), when the temperature difference in cascade condenser is increases the exergetic efficiency is decreases. The exergetic efficiency varies from 0.6237 to 0.599, 0.6401 to 0.6137 and 0.6303 to 0.6025 for R12-R13, R290-R23 and R404A-R23 respectively. The R404A-R233 shows maximum variation for change in temperature difference in cascade condenser. Fig. 5 (a) Effect of temperature difference in cascade condenser on COP Fig. 4 (c) Effect of condenser temperature on refrigerant mass flow rate C. Effect of Temperature Difference in Cascade Condenser ( T CC ): The temperature difference in cascade heat exchanger is varied from 2 C to 6 C in the interval of 1 C and other parameters are kept constant. The effect of temperature Fig. 5 (b) Effect of temperature difference in cascade condenser on exergetic efficiency 1354

Fig. 5 (c) Effect of temperature difference in cascade condenser on refrigerant mass flow ratio When the temperature difference in cascade condenser is increases the refrigerant mass flow ratio increases as shown in Fig. 5 (c). The changes in refrigerant mass flow ratio are from 0.9735 to 0.9872, 0.719 to 0.7299 and 1.712 to 1.741 for R12- R13, R290-R23 and R404A-R23 respectively. The R404A- R23 shows maximum variation for temperature difference in cascade condenser. D. Effect of L.T Cycle Condenser Temperature (T casl ): The low temperature cycle condenser temperature is varied from -35 C to -5 C in the interval of 5 C and the effect on performance parameters is analysed. The effect of low temperature cycle condenser temperature on COP, exergetic efficiency and refrigerant mass flow ratio is shown in Figs. 6 (a), (b), and (c) respectively. Fig. 6 (a) shows that as low temperature cycle condenser temperature is increases the COP of system decrease. The COP decreases from 1.355 to 1.147, 1.325 to 1.176 and 1.251 to 1.158 for R12-R13, R290-R23 and R404A-R23 respectively. The R12-R13 shows maximum variation in COP followed by R290-R23 and R404A-R23. Fig. 6 (b) shows that as low temperature cycle condenser temperature increases the exergetic efficiency decreases. The exergetic efficiency decreases from 0.7298 to 0.6175, 0.7136 to 0.6335 and 0.6734 to 0.6233 for R12-R13, R290-R23 and R404A-R23 respectively. The R12-R13 shows maximum variation in exergetic efficiency followed by R290-R23 and R404A-R23. Fig. 6 (c) shows as the low temperature cycle condensing temperature increases the mass flow ratio is decreases. The mass flow ratio decreases from 1.231 to 0.9769, 0.8631 to 0.7217 and 2.103 to 1.719 for R12-R12, R404A-R23 and R404A-R23 respectively. The R404A-R23 shows maximum variation followed by R12-R13 and R290-R23. Fig. 6 (a) Effect of LT cycle condenser temperature on COP Fig. 6 (b) Effect of LT cycle condenser temperature on exergetic efficiency Fig. 6 (c) Effect of LT cycle condenser temperature on refrigerant mass flow ratio V. CONCLUSION In present work thermodynamic analysis of cascade refrigeration system has been carried out by developing 1355

computational model in EES to find the effect of various operating parameters on the performance parameters. The following conclusions are drawn from present study. Thermodynamic analysis shows that out of three refrigerant pairs R12-R13, R290-R23 and R404A-R23 the COP of R290-R23 refrigerant pair is highest. When the evaporator temperature varied from to -80 C to -60 C the COP increased by 53.8% for R12-R13, 51.2% for R290-R23 and 50.51% for R404A-R23. When condenser temperature varied from 25 C to 45 C the COP decreased 17.5% for R12-R13, 18.9% for R290- R23, 21.9% for R404A-R23. When Temperature difference in cascade condenser varied from 2 C to 6 C the COP decreased 3.97% for R13-R2, 4.12% for R290-R23, 4.44% for R404A-R23. When lower temperature cycle condenser temperature varied from -5 C to -35 C the COP increased by 18.13% for R12-R13, 12.67% for R290-R23, 8.03% for R404A- R23. T E T C T CC T casc RE COP m H m L η ρ act E C exe isen HT LT rev Greek Letters Subscript NOMENCLATURE Evaporator temperature ( C) Condenser temperature ( C) Temperature difference in cascade condenser ( C) Temperature of LT cycle condenser ( C) Refrigerating effect (kw) Coefficient of Performance Refrigerant mass flow rate of HT cycle (kg/s) Refrigerant mass flow rate of LT cycle (kg/s) Efficiency Density Change Change Actual Evaporator Condenser Exergetic Isentropic High Temperature Low Temperature Reversible REFERENCES [1] Montreal protocol on substances that deplete the ozone layer. United Nations Environment programme (UNEP), 1987. [2] H.M. Getu, P.K. Bansal Thermodynamic analysis of an R744 R717 cascade refrigeration system, International Journal of Refrigeration, 31(2008), pp. 45-54. [3] J. Alberto Dopazo, José Fernández-Seara, Jaime Sieres and Francisco J. Uhía Theoretical analysis of a CO2 NH3 cascade refrigeration system for cooling applications at low temperatures, Applied Thermal Engineering, 29 (2009), pp.1577 1583. [4] Devanshu Pyasi, R.C. Gupta, Performance analysis of 404a/508b Cascade Refrigeration cycle for low Temperature, International Journal of Engineering Science and Technology, 3(2011), pp.6501-6507. [5] Tzong-Shing Lee, Cheng-Hao Liu, Tung-Wei Chen, Thermodynamic analysis of optimal condensing temperature of cascade-condenser in CO 2/NH 3 cascade refrigeration systems, International Journal of Refrigeration 29 (2006), PP.1100-1108. [6] A.D. Parekh and P. R. Tailor, Thermodynamic Analysis of R507A-R23 Cascade Refrigeration System, International Journal of Aerospace and Mechanical Engineering 6:1, 2002. [7] Souvik Bhattacharyya, S. Bose, J. Sarkar, Exergy maximization of cascade refrigeration cycles and its numerical verification for a transcritical CO 2-C 3H 8 system, International Journal of Refrigeration 30 (2007), PP.624-632. 1356