H29A Series Compressor Applications. Application Bulletin 139

Similar documents
A Series Inertia Compressor Applications. Application Bulletin 115

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

AIR TO AIR HEAT PUMP SYSTEM DESIGN

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

AE R17 November 2016

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Commercial High-Efficiency Condensing Units

Application Engineering

Heat Pump Defrost Board Replacement Kit

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

ThermoSaver TM Hot Gas Defrost System

User s Information and Installation Instructions

WCH5**4. Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

R4H4. Product Specifications

Service Step by Step Trouble-Shooting Check-List

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

APPLICATION DATA SHEET

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

SERVICE MANUAL Residential Small Package Products Air Conditioners and Heat Pumps Using R 410A Refrigerant

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

Warm Case Troubleshooting Guide 9/18/2014

R4H4. Product Specifications

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

AE R21 September 2017

TEMPERATURE & PRESSURE CONTROLS

Commercial High-Efficiency Condensing Units

User s Information and Installation Instructions

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

ThermoSaver TM Hot Gas Defrost System

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PACKAGE AIR CONDITIONER

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

Refrigerant Transfer and Compressor Damage

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Application Engineering

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

AE R8 March 2015

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

User s Information and Installation Instructions

INSTRUCTIONS! DO NOT DISCARD!

N4H4. Product Specifications

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0 CAUTION

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

SPLIT-SYSTEM HEAT PUMP UNIT. Model PH12 SS-PH12-11 FEATURES

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

AIR COOLED PACKAGED CHILLER

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice.

Due to a possibility of personal injury or property damage, always contact an authorized technician for service or repair of this refrigerator.

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

Glass Door Merchandiser. Model RM-49

Installation, Operation, and Maintenance Information

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

JBL2088HES JBL2088HES0, JBR2088HES JBR2088HES0, JFC2089HEP JFC2089HEP0, JFC2089HES JFC2089HES0, JFC2089HPF JFC2089HPF0, JFC2089HPY JFC2089HPY0

Otherwise, you can continue reading the file on the following pages.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

HVAC/R Refrigerant Cycle Basics

INSTALLATION AND OPERATING INSTRUCTIONS

Glass Door Merchandiser. Model RM-45-SD

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

Operator: Save these instructions for future use!

R100 Oil-Less Refrigerant Recovery Unit

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors

A 14 SEER Heat Pump with R---410A Refrigerant Series

CAUTION. All safety information must be followed as provided in Service Manual RS ! WARNING

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

Compressor Capacity Control: A New Direction

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

REFRIGERANT RECOVERY Log Book

NM952 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor...

Contour TM Screw Compressors

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S

Transcription:

H29A Series Compressor Applications Application Bulletin 139

Application Bulletin Subject: H29A Series Compressor Applications Number: 139 Release EN: J28319 Date: 4/26/02 Revision EN: Z27301 Date: 10/2/15 This Application Bulletin is for air-to-air air conditioning and heat pump applications only. For other applications or deviations from this Bulletin, please call Bristol s Applications Engineering Department at (276) 466-4121 The Bristol H29A compressors are among the most advanced reciprocating compressors in the industry today. Mechanical design and gas management make the H29A compressors very efficient and quiet. The following guidelines were developed for the H29A compressors through actual system testing as well as laboratory testing. 1.0 Crankcase Heat A crankcase heater is not required on systems when the total system charge is below the compressor charge limitation. Total charge includes the allowance for the tube size and length plus the tolerance of the charging equipment. Immersion type 30 and 40 watt PTCR crankcase heaters are available. To increase the longevity of the compressor bearings a crankcase heater is recommended to prevent liquid refrigerant from migrating into the compressor. Liquid refrigerant can dilute the oil causing excessive bearing wear. Refer to Application Bulletin 135, Crankcase Heaters. Compressors 50,000 BTU and higher should use 40-watt crankcase heaters. 2.0 Accumulators Heat pump systems require an accumulator and all other systems should be tested to see if accumulators will be required to limit liquid refrigerant returning to the compressor (for suggested testing, see Application Bulletin 101, section 4 on Suction Line Accumulators). Systems with a total charge below the compressor charge limitation normally will not require an accumulator. A double-sided see-through sight glass installed in the suction line of the compressor during all tests will assist the system designer in making this decision. Large volumes of liquid refrigerant repeatedly flooding back to the compressor during the off-cycle, defrost cycle or excessive floodback during steady operation can dilute the oil to the point that the bearings are inadequately lubricated, causing excessive bearing wear. 3.0 Motor Protection Inherent internal line break motor protection is provided. 4.0 Starting Characteristics The H29A single-phase compressor employs the highest efficiency motor available today. Because of this ultimate efficiency, the compressor will always need some method of start assist. A PTCR start assist device may be used on systems where the pressure equalizes in the off-cycle. If non-bleed expansion valves are used or other reasons exist that will not allow pressure equalization prior to compressor start-up, then a Page 2

start capacitor and potential relay are required. The PTCR device is not required when a start capacitor and relay are used. High torque start components are available for the H29A models. To determine the components needed for each application, start tests must be run at worst case conditions (lowest voltage, highest ambient and highest pressure differential) the unit is designed to operate. PTCR s and start components for each model are listed in Table 2. 5.0 Excessive Continuous Liquid Floodback Tests The following tests are for all systems including those designed with an accumulator. These tests are used to determine if the system needs design changes. Bristol testing has indicated that adding an accumulator as the only solution to excessive flooding, in most cases, is inadequate. Two excessive liquid floodback tests are required on heat pumps. One for the heating mode and one for cooling. Air conditioners will require the cooling test. The test set up is the same for heat pumps and air conditioners. Before starting the test, thermocouples should be attached to the suction and discharge tubes approximately 10 to 12 inches from the compressor. A thermocouple should also be attached to the sump of the compressor (as close to bottom center as possible, all TCs must be insulated). The system charge for this test should be 20% greater than design specifications using a 25 foot line set. The 20% overcharge simulates commonly found overcharge in the field. The evaporator should be elevated 5 feet above the condensing unit. Should you have any questions, please call Bristol s Applications Engineering Department. 5.1 Heating Mode Excessive Continuous Liquid Floodback Test The defrost control must be disconnected to prevent unit from defrosting. Outdoor ambient must be 17 F DB, 15 F WB and indoor ambient 70 F DB, 60 F WB maximum. Outdoor unit fan motor must be disconnected. Run unit until pressures and temperatures are stabilized. See examples 5.1.1 and 5.1.2. 5.1.1 Discharge superheat should not be less than 50 F. Examples: For R22 at 168 psig discharge, the saturated condensing temperature is 90 F Example No. 1: Assume actual discharge temperature of 140 F Discharge superheat = 140 F- 90 F = 50 F Therefore no system design change is required Example No. 2: Assume actual discharge temperature of 130 F Discharge superheat = 130 F - 90 F = 40 F Therefore system design change is required Note: Discharge superheat may run as low as 10 F (5.6 K) during start-up operation, as long as the temperature increases steadily and exceeds the minimum value before the compressor cycles off. The sump over saturated suction temperature should also be above the minimum value before cycling off. Extended operation is normally required to heat up the oil sump adequately, especially with low discharge superheat. If 5.1.1 temperature is less than 50 F, system design must be changed. Page 3

5.1.2 Sump temperature should be 30 F warmer than the saturated temperature equivalent of the suction pressure. Example: For R22 at 15 psig suction, the saturated evaporator temperature is -12 F Example No. 1: Assume actual sump temperature of 28 F D temperature = 28 F - (-12 F) = 40 F Therefore no system design change is required Example No. 2: Assume actual sump temperature of 15 F D temperature = 15 F - (-12 F) = 27 F Therefore system design change is required If 5.1.2 temperature is less than 30 F, system design must be changed. 5.2 Cooling Mode Excessive Continuous Liquid Floodback Test Operate the system for 1 hour; outdoor unit must be in 95 F DB, 75 F WB ambient and indoor unit at 67 F DB, 57 F WB with evaporator air flow reduced 50% to simulate dirty air filter. 5.2.1 Discharge superheat should not be less than 50 F. Example: For R22 at 260 psig discharge, the saturated condensing temperature is 120 F Example No. 1: Assume actual discharge temperature of 170 F Discharge superheat = 170 F- 120 F = 50 F Therefore no system design change is required Example No. 2: Assume actual discharge temperature of 150 F Discharge superheat = 150 F - 120 F = 30 F Therefore system design change is required If 5.2.1 temperature is less than 50 F, system design must be changed. 5.2.2 Sump temperature should be 50 F warmer than the saturated temperature equivalent of the suction pressure. Example: For R22 at 68 psig suction, the saturated evaporator temperature is 40 F Example No. 1: Assume actual sump temperature of 70 F D temperature = 70 F - 40 F = 30 F Therefore no system design change is required Example No. 2: Assume actual sump temperature of 65 F D temperature = 65 F - 40 F = 25 F Therefore system design change is required If 5.2.2 temperature is less than 30 F, system design must be changed. Page 4

6.0 Excessive Liquid Floodback Cycling Test This test is run to determine how much liquid actually gets into the compressor during system on/off cycles. To complete this test a sample compressor must be obtained with a sight tube to measure liquid level in the compressor or set the compressor on calibrated scales to measure pounds and ounces. Evaporator should be elevated 5 feet higher than the condensing unit. System charge for this test should be 20% greater than design specifications using a 25 foot line set. Operate the system in the cooling mode for 1 hour before testing at each of the ambient temperatures indicated in Table 1. Shut outdoor unit off (compressor and fan). Keep evaporator blower running. System on/off time and number of cycles is different for each of the 3 tests shown in Table 1. Observe and record the amount of liquid refrigerant (height or weight) at the start of each on cycle. If the compressor slugs or makes a metallic sound on start up, system design change is required. Test No. 1 No. 2 No. 3 Indoor Ambient ( F) 70 70 70 Outdoor Ambient ( F) 85 95 105 System On-time (Minutes) 7 14 54 System Off-time (Minutes) 13 8 6 Number of On/Off 5 5 4 Table 1 Page 5

60 Hertz H29A Electrical Components Model Run Cap µfd/ volts Required Standard PTCR Start Cap High Torque GE Relay 3ARR3*XX* H29A353CBC 40/370 305C20+ 270-324/330 3ARR22*3S* H29A383CBC 45/370 305C20+ 270-324/330 3ARR22*3S* H29A423CBC 45/370 305C19+ 270-324/330 3ARR22*3P* H29A443CBC 45/370 305C19+ 270-324/330 3ARR22*3P* H29A473CBC 55/370 305C19+ 270-324/330 3ARR22*3N* H29A503CBC 55/370 305C19+ 270-324/330 3ARR22*3N* H29A543CBC 60/370 305C9+ 270-324/330 3ARR22*3N* H29A583CBC 60/370 305C19+ 270-324/330 3ARR22*24R* H29A623CBC 60/370 305C19+ 270-324/330 3ARR22*24R* White- Rodgers 128**6-**X*X* 4*S* 4*S* 4*P* 4*P* 4*N* 4*N* 4*N* 5*R* 5*R* Table 2 Source for the PTCR 305 Series: Ceramite Corporation 1327 6th Avenue Grafton, WI 53024-0166 Phone: (414) 377-3500 Fax: (414) 377-7309 Source for the GE Relays: General Electric Appliance Control Division West Wall Street Morrison, IL 61270 Phone: (815) 772-2131 Source for the White-Rodgers Relays: White-Rodgers Division Emerson Electric Company 9797 Reavis Road St. Louis, MO 63123 Phone: (314) 577-5253 + Indicates style of mounting bracket and other options Page 6

7.0 Recommended PTCR Usage PTCR recommended by Bristol Compressors are in two classifications: standard starter and optional starter. a. Standard starters* can be used where the PTCR ambient does not exceed 115 F and/or the voltage does not drop below 197 volts (Table 3). b. Optional starter** should be used where the PTCR ambient exceeds 115 F and/or the voltage is or can be below 197 volts (Table 3). c. Cool down time between starts should be five minutes on each starter. Bristol H29A Model Number Table 3 Standard Starter* Cera-Mite P/N +Suffix indicates style of mounting and other options (see Appendices 1, 2 and 3) Optional Starter** Cera-Mite P/N H29A353CBC 305C20+ 305C19+/305C9/305C11 H29A383CBC 305C20+ 305C19+/305C9/305C11 H29A423CBC 305C19+ 305C9+/305C11 H29A443CBC 305C19+ 305C9+/305C11 H29A473CBC 305C19+ 305C9+/305C11 H29A503CBC 305C19+ 305C9+/305C11 H29A543CBC 305C9+ *** H29A583CBC 305C19+ 305C9+/305C11 H29A623CBC 305C19+ 305C9+/305C11 *** Where no optional starter is available, a system time delay greater than five minutes can be evaluated before reverting to a start capacitor and relay (see electrical data sheet). Source for the PTCR 305 Series: Ceramite Corporation 1327 6th Avenue P. O. Box 166 Grafton, WI 53024-0166 Phone: (414) 377-3500 Fax: (414) 377-7309 Page 7

8.0 PTCR Start Assist Device The PTCR, or start thermistor, can be used on Bristol s H25A/H26A/H27A Inertia compressor. This bulletin is issued to inform users about how the PTCR operates and also to provide some guides for system design and troubleshooting. 8.1 How the PTCR Operates: Figure 1 Figure 2 These devices are intended to provide additional starting torque for permanent split capacitor type motor compressors by increasing the current in the auxiliary winding during starting. The devices are to be connected across the run capacitor (in series with the auxiliary or start winding, see Figure 1). When the devices are near room temperature, the resistance is low. Upon energization, the PTCR material rapidly (approximately in 1/2 second) heats up and the resistance increases to a value that permits only milliamperes of current to flow (see Figure 2). Essentially, the devices are selflimiting in current. Note that any wires in the control box should not touch the case of the PTCR since the PTCR case temperature may reach 200 F (93.3 C). Also, wiring used when connecting to the terminals of the PTCR should be rated 105 C. 8.2 PTCR Troubleshooting 8.2.1 Step 1: Certain problems may lead to start failure in new, properly wired units. They include: a. Voltage measured at the compressor terminals during start-up is too low. b. Compressor discharge and suction pressures are not equalized. c. Improper thermostat location: If the indoor thermostat is incorrectly located, it may short cycle, meaning the thermostat may open and close the compressor contactor within a period of a few minutes. The unit should be off for approximately five minutes for the PTCR to cool sufficiently. d. Opening and closing the disconnect while servicing the unit: During installation and service, there are many reasons why a service technician may wish to restart a unit shortly after it was shut off. Again, units equipped with a PTCR must remain off for approximately five minutes. Page 8

8.2.2 Step 2: e. Control box temperature: Very high air temperatures (on a black roof for instance) and intense sunlight can increase the temperature of the control box and everything in it. These hotter temperatures may extend the time required for the PTCR to cool. If the compressor should short cycle before the PTCR is able to cool enough to start the compressor, the compressor may hum but not rotate (lock rotor). Eventually the compressor or system overload may open. If abnormal conditions occur that prevent the PTCR device from assisting the compressor in starting, the optional starter listed in Table 3 should be used in place of the standard starter. Measure the resistance: Remove the PTCR from the unit. Wait at least ten minutes for the PTCR to cool before measuring the resistance. Leave the jumper wire in place on 305C9 and 305C11 as shown in Appendix 1. The resistance of a cold PTCR measured with an ohmmeter should be as follows: 305C9 PTCR: Between 10 and 20 ohms 305C11 PTCR: Between 15 and 25 ohms 305C19 PTCR: Between 20 and 40 ohms 305C20 PTCR: Between 25 and 40 ohms Page 9

Appendix 1 Page 10

Appendix 2 Page 11

Appendix 3 Page 12

Release EN Number J28319 Release Date 4/26/02 Revisions L00912 1/31/03 X30201 4/29/14 Page 13