Eclipse Self-Check UV Scanner

Similar documents
Eclipse 90 UV Scanner Model A Version 1

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

Fireye FLAME SCANNERS

MBCE-110/230UV Flame Sensor Module

FIREYE C9707A ALL FUEL SCANNER

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC

VeriFlame CE Burner Monitoring System

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

MBCE-110/230FR Flame Sensor Module

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

MBCE-110/230FR Flame Sensor Module

Instruction Manual 826 7/22/2009. Eclipse Bi-Flame Dual Burner Monitoring System Model 6500 Version 1

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

DESCRIPTION AND INSTALLATION

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

DESCRIPTION AND INSTALLATION

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

North American Flame Detector Adapters 8832 through 8839 and Series R

7800 SERIES Relay Modules

ECLIPSE INFORMATION GUIDE

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

UV Flame Supervision System

LAE10 LFE10. Use. Series 02

Steam Fundamentals. (in heating & processing applications)

DESCRIPTION AND INSTALLATION

DOMESTIC HOT WATER Follow operational sequence

DIRECTIVE NO: D-B

R7120M 7800 SERIES Relay Modules

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832

FIREYE FLAME SCANNERS

LFL Series Burner Flame Safeguard Control

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents

FIREYE FLAME SCANNERS

55UV5 SCANNER MODEL 1010

Indirect gas-fired air heater

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

S55XB and S55XBE Series Viewing Heads

FIREYE FLAME SCANNERS

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

COMPACT FLAME CONTROLLER CFC 2000

Q - Series Boiler. Troubleshooting Manual

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

Design Guide 111 9/25/2008. Eclipse Winnox Burners WX Series Version 1

COMPACT FLAME CONTROLLER CFC 1000

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Interrupted Ignition Series Oil Primary Control

Flame Safeguard Fault Code Diagnostics

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Operator: Save these instructions for future use!

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents

PACKAGED METALLIC BURNERS

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

OPERATING AND MAINTENANCE MANUAL

Technical

ECLIPSE INFORMATION GUIDE

Flame Safeguards LFE10. Building Technologies HVAC Products

FIREYE FLAME SAFEGUARD CONTROLS DESCRIPTION

D-GF 150. Burner Control for Gas and Oil Burners Flame Sensor D-GF 150 D-LE 103

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

INDUSTRIAL FLAME SCANNERS

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

EUROFLAT SERIES TYPES C... S... M...

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER)

SOLID STATE Burner Management Controls SERIES D40-41

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Cleaver-Brooks CB780/CB784 Operation and Maintenance Manual

Technical

FLAME SAFEGUARD & COMBUSTION CONTROLS. Preface

S55XB and S55XBE Series Viewing Heads

Flame Safeguards LFE10. Building Technologies HVAC Products

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

CSD-1 COMMERCIAL BOILER CONTROLS

C7915A Infrared Flame Detector

U2 Combination Viewing Head and Signal Processors

MULTIPLEX SELF RECUPERATIVE gas burner

Figure 10 or Figure 6

FIREYE FLAME SCANNERS

HYDROCARBONENGINEERING June June 2015

TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B)

RM7838A 7800 SERIES Relay Modules

Forced draught gas burner

C Note! LGI16... Burner Controls. Building Technologies

Power Flame Incorporated

Design Guide No /01. RatioMatic Burners. RM Series Version 3.10

FLAME SAFEGUARD FOR BURNER MANAGEMENT SYSTEMS

INDITHERM. Low temperature gas burners

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

Transcription:

856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly every ten seconds, at which time the scanner s internal circuit checks for a flame signal. If a signal is present, indicating a failed sensor, the output signal to the flame safeguard is stopped and the system shuts down. The scanner features a high quality fused silica quartz lens, machined alloy housing with seals and a long life push-pull electromagnetically driven photo shutter. This scanner operates with the series 5600 and VF56 series Veri-Flames, the series 6000 Multi-Flame, Series 6500 Bi- Flame controllers, and series 7000 Peek-A-Flame. Factory Mutual (FM) recommends these scanners be used when any fired equipment is operated continuously (more than 24 hours without shutdown). Mechanical Specifications Parameter Specification Overall Length 7-3/4" (197mm) Diameter 3-1/4" (83mm) Housing Material Aluminum Finish Clear anodized Sight Tube Entrance 1" NPT Purge Air Entrance 1/4" NPT Purge Air Flow 5 cfm, 10 psi maximum (140 lpm, 0.7mbar)

Electrical Specifications Parameter Specification Supply Voltage 120V +10/-15%, 50/60 Hz Supply Current 0.04A Output Pulse frequency modulated transistor Required Accessory Cable with connector, 10 feet (3m), model, Part 49602-91-7 Wiring Extension Instrumentation cable with two pairs of individually shielded #18 AWG conductors, 300V minimum, BELDEN #9368 or equivalent. Temperature Range 0 F to 140 F (-20 to +60 C) case temperature Shipping Weight 4.5 lbs (2 kg) Optical Angle of view @ 2.5 depending on sight pipe size and length Spectral Sensitivity: 185 to 260 nanometers; scanner is solar blind Option Non-Magnifying lens part 18165 Sensor Installation Incorrect sensor installation may cause the sensor to generate a false flame signal. This can cause unburned fuel to collect in the combustion chamber, resulting in explosions, injuries, and property damage. Be certain that the flame sensor detects only the pilot and/or main flame of the intended burner by testing the control system under varying operating conditions and firing rates. Follow the test procedures given in this manual and the equipment provider s instructions after installation and at regularly scheduled maintenance intervals. Sensor Wiring Route sensor wiring a sufficient distance from ignition and other high voltage wiring to avoid electrical interference. To reduce interference, ground both shields. If sensor wiring is to extend beyond the supplied 10 ft (305cm) lengths, use wiring extension as shown in specifications. Tables 1-4 illustrate how the sensor should be wired to appropriate controls. Near the end of each of the four cable leads is a letter tag for identifications. The scanner is only available for 120V supply. Refer to Figure 1 to use with a 230 VAC supply. NOTE: The shield wire terminals shown in the tables provide a convenient attachment point. A panel ground wire must also be run to these points. Cable lead "B" should only be connected to power (120 VAC); connecting it to any other terminal will bypass the safe-start check of the scanner. 5602-91 Connector Pin Cable Wire Table 1 - Wiring to Multi-Flame Multi-Flame J4 Terminal #1 #3 Multi-Flame J5 Terminal #2 #4 Expansion Board J3, J4, J5, J6 Terminals #5, 6, 9, 10 (also #13, 14, 17, 18) #7, 8, 11, 12 (also #15, 16, 19 20) A red Neutral Neutral Neutral Neutral Neutral Neutral Neutral B white 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC C black UV 3 9 3 9 3 9 D green Gnd Return 2 8 2 8 2 8 - shields Ground 4 10 4 10 4 10 2 Eclipse Self-Check UV, V1, Instruction Manual 856, 10/18/2010

5602-91 Connector Pin Cable Wire Table 2 - Wiring to Bi-Flame Bi-Flame J4 Terminal J5 Terminal #1 #2 A red Neutral Neutral Neutral B white 120 VAC 120 VAC 120 VAC C black UV 3 1 D green Gnd Return 2 2 - shields Ground 4 4 5602-91 Connector Pin Table 3 - Wiring to Veri-Flame Cable Wire Veri-Flame Terminal A red Neutral 2 B white 120 VAC 1 C black UV S1 D green Gnd Return S2 - shields Ground Gnd 5602-91 Connector Pin Table 4 - Wiring to Peek-A-Flame Cable Wire Peek-A-Flame Terminal A red Neutral 1 B white 120 VAC 3 C black UV 7 D green Gnd Return 8 - shields Ground 2 Sensor Installation In most cases, the location for this scanner will be predetermined by the burner manufacturer. However, proper application of this scanner requires knowledge of the burner, the combustion chamber, and the process. Opposing burners, flame swirl patterns, and substance in the line-of-sight may require special mounting techniques. The UV tube is fragile. Handle carefully and avoid dropping or sharp blows. Consult the burner manufacturer s instructions for mounting location. The scanner should view the intersection of the pilot and main flames. It typically should be aimed at the first third of the flame closest to the burner nozzle, see Figure 2. Certain unburned hydrocarbons, oil mist, recirculated flue gas or other contaminants may mask and absorb the ultraviolet radiation. Position the scanner within 30 inches (762 mm) of the flame. For temperatures higher than specified, provide clean cooling air to the 1/4" NPT purge tap on the housing. Maximum furnace pressure is 60 psig. To assist in sighting the scanner, a swivel mount (#10042584) may be used. Keep the scanner lens and line-of-sight free of contamination. Be aware that scanners looking up are susceptible to dirt and dust settling. Soot, steam, and unburned hydrocarbons may reduce or even mask the radiation from the flame. A purging assembly as described above may alleviate these problems. Some burners have an open construction allowing the scanner to view into a furnace. Avoid sighting background sources of UV light. If necessary, mask the offending background source by use of an orifice. Eclipse Self-Check UV, V1, Instruction Manual 856, 10/18/2010 3

Wiring with a Transformer for 230V Supply 2 1 S1 S2 240V T1 120V A B C D T1 Third party transformer required. Must be at least 25 VA. Figure 1. 4. Measure the flame signal strength as described above. 5. Slowly reduce the pilot fuel until the signal drops out. Increase the pilot fuel slightly and restart the system. Observe the flame signal and adjust the pilot fuel as required to prevent flame failure. This is the minimum pilot. 6. Take the control out of the pilot test mode and begin the start-up sequence again. On the Veri-Flame push the Test/Reset button again so that it pops out to the Run position. On the Bi-Flame and Multi-Flame press the Reset button. Main Burner One-Third of Flame Length 7. When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the main burner. If the main burner does not light within five seconds, immediately shut off the burner fuel supply, stop the control and purge the system. Attempt to light the burner again before proceeding with adjustments in the next step. Sight Line Test Procedures Figure 2. UV Sighting Perform the following tests for every new installation and at periodic maintenance intervals. Depending on the burner equipment (such as pilot versus direct spark), some of the tests may not be possible. Measuring Flame Signal Strength Insert the positive probe of a 0-15 VDC voltmeter (100k ohm minimum input impedance) into the test point on the control cover. Connect the negative probe to the GND or terminal for the "D" (green) wire. Readings greater than 4 VDC are adequate. Minimum Pilot Test Run this test on pilot ignited burners to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame. 1. Manually shut off the fuel supply to the burner, but not to the pilot. 2. Put the control in the pilot test mode. On the Veri-Flame push the Test/Reset button in the Test position (button in). On the Bi-Flame and Multi-Flame press the Reset and Enter buttons together then release the Reset and after a few seconds release the Enter. 3. Start the system normally. The control will hold the operating sequence at the pilot flame step. 8. For burners with an adjustable scanner sighting assembly, adjust the sighting assembly further away from the nozzle of the pilot flame thus requiring a larger minimum pilot for adequate signal strength. For burners with fixed sighting, increase the pilot flame. Repeat steps 1 through 8 until the main burner lights off smoothly and reliably. Ignition Interference Test Test the effect of the ignition system (transformer, spark plug, wiring and grounding) on the flame signal and control. Ignition interference can decrease or increase the flame signal strength or can cause erratic operation of the control. The scanner placement on some burners allows direct sighting of the spark, creating a strong but false flame signal. The Eclipse flame control sequence does not interrupt the spark upon flame detection until after the trial for ignition period. Therefore spark detection is not a problem; however ignition interference should still be reduced or eliminated where possible. 1. Manually shut off the fuel supply to the burner. 2. Start the system normally. Observe the flame signal during ignition to see if it responds during the spark. Readings above 2 VDC indicate spark interference or spark sighting. 3. On pilot ignited burners, manually shut off the fuel supply to the main burner. For direct spark burners, lock the burner firing-rate at the start position. 4. Put the control in the pilot test mode (see step 2 of Minimum Pilot Test above). 4 Eclipse Self-Check UV, V1, Instruction Manual 856, 10/18/2010

5. Start the system normally. Observe the flame signal during spark and after the trial for ignition. Spark interference causes the signal during the spark to differ more than 2 VDC from the signal after the spark. 6. If spark interference is observed, try to minimize its affect: a. Ensure proper grounding for the ignition circuit. b. Isolate the scanner from ground and/or remove the shield connection from ground. c. Check for proper spark gap. d. Clean, repair, or replace faulty wiring and connectors. e. Separate or shield the scanner wiring from the ignition wiring. f. Reverse the wires feeding the primary to the ignition transformer. g. Move the location of the ignition transformer. Pilot Flame Failure Test 1. Put the control in the pilot test mode (see step 2 of Minimum Pilot Test above). 2. Start the system normally. 3. After the pilot has lit, manually turn off the fuel supply. The controller should lock out of flame failure. If not, then the controller is detecting a false flame signal. Find the problem and correct it before resuming normal operation. Main Flame Failure Test 1. Put the control in the "Run" position (see step 6 of Minimum Pilot Test above). 2. Start the system normally. 3. After the sequence lights the main flame, manually shut off the fuel supply. If the control does not shut down in less than 4 seconds after visually observing that the flame extinguished, it may be detecting a false flame signal. Find the problem and correct it before resuming normal operation. Process Conditions Test 1. Start the system normally. 2. Observe the flame signal as the system operates at various firing rates under process (at temperature) conditions. 3. Perform the Main Flame Failure Test under these conditions and verify that the control shuts down in less than 4 seconds after visually observing that the flame extinguished. Limit & Interlock Tests Periodically check all interlock and limit switches by manually tripping them during burner operation to make sure they cause a system to lock out. Never operate a system that is improperly adjusted or has faulty interlocks or limit switches. Always replace faulty equipment with new equipment before resuming operation. Operating a system with defective safety equipment can cause explosions, injuries, and property damage. Maintenance WARNING High voltage, turn off power before disconnecting or installing sensors or controls. All burner systems must be maintained to ensure their safe operation. The operator of this equipment must be trained in safe operating procedures. The owner and operator must set a regularly scheduled maintenance interval based on recommendations from the equipment manufacturers, environmental conditions, and their own operational history. System Checks Periodically test the sensors as described in the Test Procedure section. Sensor Lens Clean the glass lens regularly with a soft, damp cloth. The presence of foreign material will measurably reduce the flame signal strength. Rotation To ensure operability of stored items and to reduce the possibility of extended down-time, periodically swap spare sensors and control units with active ones. Eclipse Self-Check UV, V1, Instruction Manual 856, 10/18/2010 5

Dimensions in inches (mm) Ø3.2 (81.3) 7.5 (190.5) 6.8 (172.7) 1.8 (45.7) Ø2.0 (50.8) 1.7 (43.2) 1-3/8" - 18 EXT 1/4" - 18 NPT 1" NPT INTERNAL 856 Instruction Manual, 10/18/2010