Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

REQUIREMENTS FOR HOOD PLANS

Kitchen Ventilation Hood Permit Application

2015 ICC Commercial Cooking Systems

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

2012 ICC Commercial Kitchen Hoods

MSYS 4490 AC Systems

MECHANICAL EXHAUST VENTILATION SYSTEMS FOR RETAIL FOOD FACILITIES. Design, Calculations, and Operational Guidelines

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

Low Wall Back Shelf Exhaust Canopy

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009

Commercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations

Mobile Vendors Bulletin

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

CHAPTER 5: EXHAUST SYSTEMS

MECHANICAL EXHAUST VENTILATION SYSTEMS Design, Calculations, and Operational Guidelines

Inspection Checklist Mechanical Final

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009

Notable Changes in the Mechanical Codes

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK

Dear Concessionaire,

Inspection Checklist Mechanical Rough in

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems

Chapter One Commercial Kitchen Fires

IMC Significant Changes Summary Tier I

2012 INTERNATIONAL FUEL GAS CODE VENTS

COMMERCIAL KITCHEN FIRE SAFETY

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007

2012 International Mechanical Code Significant Changes. About the Significant Changes

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS

UNIFORM MECHANICAL CODE

2015 MECHANICAL CODE REQUIREMENTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

FOOD SERVICE EQUIPMENT REBATES

SECTION COMMERCIAL-KITCHEN HOODS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

FRESNO COUNTY HUMAN SERVICES SYSTEM ENVIRONMENTAL HEALTH SYSTEM P.O. Box Fresno, CA Telephone (209)

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

MODEL: JRSVH SERIES JEAN S RESTAURANT SUPPLY 426 SOUTH STAPLES CORPUS CHRISTI, TEXAS PH: (361)

Effective ventilation is necessary for the comfort

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHIMNEYS AND VENTS CHAPTER 8

SPECIFIC APPLIANCES CHAPTER 6

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

CHAPTER 8 CHIMNEYS AND VENTS

EXHAUST FAN SCHEDULE

SECTION DUCTWORK

NFPA 96, 2017 REVIEW SUMMARY

FOOD PREPARATION WITHIN EXHIBITS

CHAPTER 8 CHIMNEYS AND VENTS

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

Mechanical Appliance and Equipment Inspection Checklist

HVAC Equipment Access Equipment Location

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY

JADE RANGE LOG BROILER MODELS: JLB SERIES

SPECIFIC APPLIANCES CHAPTER 6

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

For the Florida Building Commission And the Fire Code Advisory Council

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

APPUZO RANGE HOOD INSTALLATION

SPECIFIC APPLIANCES CHAPTER 6

TMB Baking TSV Gas Oven TAG Series. Contractor s Utility Requirements

Inspection Checklist Residential Mechanical Rough In July 2016

Food Service Plan Review Information

UMC 2012 ( ): Item # 38

Gas Safety. Syllabus. For. Gas Appliance Service. Certificate of Qualification Examination. (Formerly Class C)

Applicable codes and standards provide

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

DUCT SYSTEMS CHAPTER 6

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code 2011

FT900BD FLIGHT-TYPE DISHWASHER

To expedite the plan review and inspection processes, please refer to the information below.

Building Department Informational Handout

New Food Service Plan Review Checklist

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

CHAPTER 6 SPECIFIC APPLIANCES

SANDUSKY FIRE DEPARTMENT Fire Prevention Bureau. Dear Prospective Food Vendor:

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

Code verification sign-off

SECTION AIR HANDLING UNIT

SECTION AIR DUCT ACCESSORIES

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

FT900SDBD DUAL RINSE FLIGHT-TYPE DISHWASHER

SCALE 1 INCH = 20 FEET C1.0

Model UDAP. Power Vented, Low Static Axial Fan Commercial/Industrial Unit Heaters DESCRIPTION STANDARD FEATURES OPTIONAL FEATURES - FACTORY INSTALLED

Ships and marine technology Fireextinguishing. of galley cooking equipment

Transcription:

STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting Supplemental Application HOOD AND DUCT DATE STAMP LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY Intake by: This application cannot be submitted alone. In addition to this form, a complete package includes: Applicant Staff Use SUBMITTAL CHECKLIST Use Only Master Application. Quantity and Supplemental Checklist (see attached). A separate application is required for the hood fire suppression system. (Form No. SA009 & SA009f) A plumbing permit may be required for new grease trap installations. (Form No. SA006) Applicable processing fees. Refer to current fee schedules. Depending on the adopted fee structure, additional fees may occur if base hours/fees at intake are exhausted. Name of Project: Owner: Contractor: License #: Company Name: Expire Date: Phone #: Cell Phone # Fax #: E-mail Address: Contact Person: Phone #: Engineer Name: License #: Expire Date: E-mail Address: Phone #: Cell Phone # Fax #: Contact:

Page 2 of 5 PROJECTS ASSOCIATED WITH THIS APPLICATION: Non-residential Hood and Duct Application Supplemental Requirement Checklists Applicant Use QUANTITY CHECKLIST Staff Use Only A completed application submitted for each hood and duct. Three sets of 11 x 17 drawings max. Three sets of equipment cut sheets. This section provides the information needed for the applicant, the plans examiner, and the building inspector to verify code compliance. The information provided becomes part of the issued permit. Complete a separate sheet for each hood. This does not cover all of the exceptions in the International Mechanical Code. Use of exceptions is the responsibility of the applicant. The applicant shall identify the code section and note where used on the plans. Supplemental Information Is it an existing restaurant, food processing area or food service area: Yes No If no, provide construction or change of use permit number: Location of exterior ductwork and mechanical equipment: 1. Is ductwork or mechanical equipment located outside of building other than roof top? Yes No 2. Provide plan and elevation views showing ductwork, duct enclosure, hood, cooking surface air supply, exhaust system, and equipment support including structural detail. Supports for hoods over 400lbs must be designed by a licensed engineer. Trusses will need to be evaluated by an engineer to determine if they are adequate to support the imposed loads in accordance with ASCE 07-05. Type of hood: (IMC 507.2) 1. For grease and smoke removal: Type I Yes No (Example: Deep fryer, char-broilers, grill, pizza ovens and all solid-fuel appliances) 2. For steam, vapor, heat or odor removal : Type II Yes No (Example: steamer, pastry dishwashers): Type II hood shall have permanently identification label. 3. Is hood for solid-fuel cooking equipment? Yes No If yes, a separate exhaust system is required. TYPE I HOOD TYPE II HOOD Type of Material Gage Gage Duct and Stainless Steel 18 Ga. Stainless Steel 26 Ga. Up to 12 Diameter Plenum Galvanized Steel 16 Ga. Galvanized Steel 22 Ga. Up to 30 Diameter Hood Stainless Steel 20 Ga. Stainless Steel 22 Ga. Galvanized Steel 18 Ga. Galvanized Steel 24 Ga. Flashing Stainless Steel 22 Ga. Not Required Galvanized Steel 22 Ga. Quantity of air exhausted through the hood (507.12, 507.14) 1. Canopy hoods are hoods that extend a minimum 6 beyond cooking surface Type of hood proposed: Canopy Non-canopy Distance between lip of hood and cooking surface: Canopy - 4 ft. maximum allowed Non-canopy 3 ft. maximum allowed 2. Complete part i for listed hood or part ii for unlisted hood: i) Listed hood. Make and model No.: Listed CFM

Page 3 of 5 ii) Unlisted hood: Quantity of air = Lineal ft. of hood front X CFM from table below: = 10 ft. X 550 CFM/ft. = 5500 CFM Identify the cooking appliance and circle the CFM applied. Where any combination of cooking appliances is utilized under a single hood, the highest exhaust rate required by this table shall be used for the entire hood. Hood Exhaust CFM Table - Minimum net airflow for different types of unlisted hoods. (507.13) Type of Hood Extra Heavy Duty Heavy Duty Medium Duty Light Duty Wall mounted 550 400 300 200 canopy Single island canopy 700 600 500 400 Double island canopy 550 400 300 250 Back-shelf / pass-over Not allowed 400 300 250 Eyebrow Not allowed Not allowed 250 250 Definitions: Extra Heavy Duty cooking appliances: appliances utilizing solid fuel such as wood, charcoal, briquettes, and mesquite to provide all or part of the heat source for cooking. Heavy Duty cooking appliances: electric under-fired broilers, electric chain (conveyor) broilers, gas under-fired broilers, gas chain (conveyor) broilers, gas open-burner ranges (with or without oven), Electric and gas wok ranges, and electric and gas over-fired (upright) broilers and salamanders. Medium Duty Cooking appliances: electric discrete element ranges (with or without oven), electric and gas hot top ranges, electric and gas griddles, electric and gas double-sided griddles, electric and gas fryers, (including open deep fat fryers, donut fryers, kettle fryers, and pressure fryers), electric and gas pasta cookers, electric and gas conveyor pizza ovens, electric and gas tilting skillets (braising pans) and electric and gas rotisseries. Light Duty Cooking appliances: gas and electric ovens (including standard, bake, roasting, revolving re-therm convection, combination convection / steamer, conveyor, deck or deck style pizza, and pastry), electric and gas steamjacketed kettles, electric and gas compartment steamers (both pressure and atmospheric) and electric and gas cheesemelters. Exhaust Duct System Welding Certifications must be on site. Light test required Applicant shall provide the specified air velocity in exhaust duct. (Duct size 24 in X 36in.) / 144 = (dcfm) 6 ft2 Type of Hood Air Velocity (FPM)/CFM / Duct Area (ft2)= Proposed Air Velocity Type I hood = (1500 req. to 2500 recommended) 1500 / 6 (dcfm)ft2 = 250 FPM Type II hood = (500 to 2500 recommended) 500 / 6 (dcfm)ft2 = 83.3 FPM Static pressure loss: Duct in. + grease filters / extractor in. + other in. = Total in. of H20 Fan and Motor shall be of sufficient capacity to provide the required air movement. Fan motor shall not be installed within ducts or under hood. The activation of the exhaust fan shall occur through an interlock with the cooking appliances. Fan make and model HP Static pressure in. at CFM. Exhaust outlet location (506.3.12) Min. required Exhaust outlet shall terminate above roof minimum: Type I - 40 in Type II 30 in

Page 4 of 5 Exhaust outlets shall be located 10 feet minimum from adjacent buildings, adjoining grade, property line, doors and windows and 10 feet from or 3 feet above any mechanical air intakes. Wall and roof terminations shall not be in areas where opening protection is required. Any termination shall not be within 3 feet of other building openings. Makeup air (508.1) Makeup air not less than 90% of the exhaust. (dcfm) 6 ft 2 X.9 = 8.1 CFM. Makeup air system shall be electrically interlocked with the exhaust system, such that the makeup air system will operate when the exhaust system is in operation. Makeup air shall be provided by a mechanical or gravity means of sufficient capacity. Windows and door openings shall not be used for the purpose of providing makeup air. If more than 2500 CFM supplied to the space other than the hood, provide heater capable of heating makeup air supplied to the space to 65 degrees F. Heater model # Input BTU Output BTU Heater CFM AFUE FAN Make and Model Recommended air velocity, 500 FPM HP Static pressure in. at CFM Duct area req. = CFM / 500 FPM: CFM / 500 FPM = ft2 Duct Dimension in X in = ft2 Duct dimension required = Air velocity = CFM / Area: CFM / ft2 = FPM Eff. Damper opening X = ft2 Slope of duct and cleanout access (506.3.7, 506.3.8) and Clearance (506.3.6) Horizontal duct up to 75 long Min. Slope 1/4 in/ft. More that 75 long Min. Slope 1 in/ft. Tight-fitting cleanout doors shall be provided at every change in ductwork direction. GWB on Metal stud - minimum 3 clearance required GWB on wood stud - minimum 18 clearance required Duct enclosure (506.3.10.3, 506.3.) Ducts penetrating a ceiling, wall, or floor shall be enclosed, from point of penetration to the outside air, in a duct enclosure having a fire rating not less than the floor or wall that is penetrated - not to exceed two hour rating. A duct may only penetrate exterior walls at locations where unprotected openings are permitted the International Building Code. Rating of roof, wall or ceiling assembly: Duct Enclosure clearances from duct to shaft: GWB w/ wood stud wall 18 in. GWB w/ steel stud wall 6 in. ASTM 814 or UL 1479 Factory built or Field Per manufacturers installation instructions. applied enclosures Duct enclosures shall be sealed around the duct at the point of penetration and vented to the exterior through a weatherprotected opening. Duct enclosures shall serve only one kitchen exhaust duct. Tight-fitting hinged access door shall be provided at each clean-out. Access enclosure doors shall have a fire resistance rating equal to the enclosure. An approved sign shall be placed on access door. ACCESS PANEL. DO NOT OBSTRUCT. These shall be identified on the plans. Additional code requirements may apply. Additional Information UL 710 and UL 710B hoods installed in accordance with the listing are exempt from material seam grease filter and capacity requirements of the IMC. UL 710B Type II hoods must use 100 square feet per appliance to determine ventilation rates. Grease filters shall be installed at min 45 degree angle and equipped with a drip tray and gutter beneath lower edge of filters.

Page 5 of 5 Distance between lowest edge of grease filters and cooking surface: Grill, fryer, exposed flame shall be not less than 2 ft. Exposed charcoal, charbroil shall be not less than 3 1/2 ft. Type 1 hood shall have clearances from combustible construction of 18. No clearance is required where ½ minimum cementatious board is covered with a smooth, cleanable, nonabsorbent, surface and noncombustible material that is attached to a noncombustible structure. This protection must extend 18 in all directions from the hood. Vibration insulation connector may be used provided it consists of non-combustible packing in a metal sleeve joint. (506.3.2.4) All joints and seems shall be made with continuous liquid-tight weld or braze made on the external surface of the duct system. (506.3.2) Exhaust fans used for discharging grease exhaust shall be positioned so that the discharge will not impinge on the roof. The fan shall be provided with an adequate drain opening at the lowest point to permit drainage of grease to a suitable collection device. (506.5.2) Grease ducts shall be inspected prior to both, use or concealment by duct wrap or shafts. The permit holder is required to provide the equipment for the test. A light test with a 100 watt power rating shall be performed on the entire duct system including connectors to the fan and hood. Duct supports and bracing shall be provided to carry gravity and seismic loads. Supporting materials shall not penetrate the duct walls. Fire Suppression System Fire Suppression System shall be per fire code. Portable fire extinguisher shall also Be provided per Fire Code. Provide automatic shut off for make-up air, exhaust system, and appliances when suppression system is activated. Dependant on suppression agent and manufacturer s requirements. Testing Performance test certificate of the hood system shall be provided to owner before final approval. Test shall verify proper operation, the rate of exhaust, make-up air, and capture and containment performance of the exhaust at normal operating conditions.