PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

Similar documents
PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.

SIGMADEK, LTD. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FUNDERMAX GMBH FIRE TEST REPORT

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Report of Surface Burning Characteristics Test on Acoustical Panel

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Criteri di Preselezione in Accordo ad UL 94 e Conformità del Prodotto Finito. Matteo Paleari Senior Project Engineer

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

Acoustical Surfaces, Inc.

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

SOUTHWEST RESEARCH INSTITUTE

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

UL 94 Flammability Ratings: Introduction

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

We Identify and S.T.O.P. Your Noise Problems

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

ENGINEERING EVALUATION

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Flammability Test Results

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

ENVIRONMENTAL TEST REPORT

PRODUCT SPECIFICATION. 0.5mm Fine Stacking. Hermaphroditic Type BTB Connector

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017

Jan05 Rev A EC

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Jun08 Rev A

TEST REPORT IEC Safety of laser products - Part 1: Equipment classification and requirements

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

Jul07 Rev C

Two Circuit Heavy Duty Burner Connector

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

INTERNATIONAL STANDARD

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Contact person Date Reference Page Richard Johansson P (2) Fire Research

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

BOARD OF COUNTY COMMISSIONERS

Public Comment No. 2-NFPA [ Section No ]

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

Full-scale test of fire detection in a facade using heat detection cable and flame detector

Engineering Report Vibration Test for Intertek Testing Services Prepared by Approved by 9725 Girard Avenue South Minneapolis, MN 55431

Standards Update Notice (SUN) Issued: January 9, 2017

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Glass fibre rovings - Non-metallic materials

Fire Performance of Translucent Systems

Test Report: ICL/H18/9039 Rev 1

NATIONAL TECHNICAL SYSTEMS

Standards Update Notice (SUN) Issued: February 2, 2017

Public Comment No. 1-NFPA [ Section No ]

BCTC CARPET TECHNICAL CENTRE

GUARDIAN FIRE TESTING LABORATORIES, INC.

FIRE ALARM SYSTEM INSPECTION

SHOP PRIMERS FOR CORROSION PROTECTION OF STEEL PLATES AND SECTIONS

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Test Report. Appliance EMF Testing

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

156 Egret Street, Covington, LA * * MOLD/IAQ SCREENING REPORT

SmartSensor 105 & Advance NEMA External Ice

Infrastructure Technology

Report on Public Input June 2014 NFPA 101

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

Transcription:

PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC PRODUCT: Modular Block Product Report No.: G1320.01-106-31 Report Date: 08/04/16 Test Record Retention Date: 07/29/20 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC 55 East 59th Street Suite 1700 New York, New York 10022 Report No.: G1320.01-106-31 Test Start Date: 07/27/16 Test Completion Date: 07/29/16 Report Date: 08/04/16 Test Record Retention Date: 08/04/20 Product: Modular Block Product Project Summary: Architectural Testing, Inc., an Intertek company ("Intertek-ATI"), was contracted by EverBlock Systems, LLC to evaluate the flammability properties of their modular block product. The product description, test procedure, and test results are reported herein. UL94 - Horizontal Burn Test Summary of Test Results Meets HB rating Test Method: The test specimens were evaluated in accordance with the following method. UL94, Standard for Flammability of Plastic Materials for Parts in Devices and Appliances, Section 7 Horizontal Burning Test, Sixth Edition, March 28, 2013 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

Page 2 of 4 Product Description: The modular block product was submitted to Intertek-ATI by EverBlock Systems, LLC on July 26, 2016 and consisted of eight nominally 6" x 7" x 3" full profile specimens. The material was tested as-received with the exception of machining the smaller test specimens from the pieces. Refer to the product description photos in Appendix A. Test Procedure and Test Results: The testing procedure and results obtained from testing are reported as follows. All conditioning of test specimens and test conditions were at standard laboratory conditions (23 ±2 C, 50 ±5% RH) unless otherwise reported. Refer to the test related photos in Appendix A. UL 94 - Horizontal Burning Test The Horizontal Burning classification was determined utilizing a laboratory burner (ICN: Y002875) that was confirmed in accordance with ASTM D5207. The specimen was supported horizontally at one end and the free end exposed to a gas flame for 30 seconds. After removal of the flame, the specimen was observed for time and extent of burning. The test was conducted on specimens conditioned for a minimum of 48 hours at standard laboratory conditions. Specimen No. Initial Burn With Flame Burn After Flame Removed Time, t (sec) Burn Beyond 25 mm Mark Damaged Length, L (mm) Linear Burning Rate, V (mm/min) 1 Yes Yes 161 75 28.0 2 Yes Yes 177 75 25.4 3 Yes Yes 158 75 28.5 Average 27.3 Classification: HB Average Size of Specimens (L x W x T): 5" (127 mm) x 0.5" (13 mm) x 0.125" (3 mm)

Page 3 of 4 Intertek-ATI will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Intertek-ATI for the entire test record retention period. Results obtained are tested values and were secured using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: J. Rich Hammons Dawn M. Chaney Technician II Technician Team Lead Components / Materials Testing Components / Materials Testing JRH:dmc/kf Attachments (pages) This report is complete only when all attachments listed are included. Appendix A - Photographs (2)

Page 4 of 4 Revision Log Rev. # Date Page(s) Revision(s) 0 08/04/16 N/A Original report issue This report produced from controlled document template ATI 00231, revised 01/14/16.

APPENDIX A Photographs

Photo No. 1 Test Specimens As-Received Photo No. 2 Prepped Test Specimens

Photo No. 3 Test Setup (Typical) Photo No. 4 Testing in Progress