INSTALLATION MANUAL: IDC-6 INITIATING DEVICE CIRCUIT EXPANDER

Similar documents
Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Fire Alarm Control Panels

PFC-4064 Conventional Fire Alarm Panel

PSN-1000 & PSN 1000(E) Installation Manual

Installation Instructions Model CDC-4

These instructions detail procedures to follow in order to avoid damage to equipment.

December Scorpio. Fire Control Panel. Installation, Operation & Maintenance Manual. P/N UL Listing File No. S2422.

PSD-7157 P55FE1 Photoelectric Advanced Smoke Detector (Open Area, Air Velocities fpm) - our standard!!

FA-101U Fire Alarm Control Panel

Multiplex Eight Input Remote Modules

PFC-3002T Fire Alarm Control Panel

F220-B6PS/M. Installation Guide. Addressable Detector Bases

FireNET Plus Wiring Instructions

Multiple Input and Output Modules

MMF Six Zone Interface Module

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AFC-1000 Fire Alarm Installation Manual

ORENA BRAND CONVENTIONAL (ORENA Brand) CE

IDP-Zone-6 Six Zone Interface Module

INTELLIKNIGHT 5895XL. Installation and Operations Manual. Intelligent Power Module for the 5820XL Systems. Part Number Rev E

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

CZ-6A Six Zone Interface Module

InstallatIon GuIde XR500 series CanadIan ContRol Panel

Conventional Fire Alarm System Product Range Guide

FIRE DETECTION CONTROL PANEL OPERATING & MAINTENANCE MANUAL

Signature Series Auto-Sync Output Module (CC1S)

P/N Product Manual. Conventional Fire Alarm/Suppression System

Input/Output Modules Data Sheet

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

Silent Knight Software Suite Intelliknight Training

SC-6 Six Supervised Control Module

DS7465i. Installation Instructions. Input/Output Module

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

good things in small packages

MR-2602 Two Zone Fire Alarm Control Panel

AU MX Digital Loop Card Installation Instructions

XR10/XR20 Command Processor Panels Installation Guide

Addressable NAC Output Module D327A

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

Installation Instructions Model HZM

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

SECTION FIRE ALARM SYSTEMS

Addressable Fire Alarm Control Panel

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

30.45 Electric Release PDRP-2001

DS7400Xi Addressable Control/ Communicator

Conventional Fire Alarm Systems

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

I NSTALLATION M ANUAL

Booster Power Supply Manual

Intelligent Analog/Addressable Fire Alarm/Voice Integration Systems. IntelliKnight TM Series

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

Commercial and Light Industrial Fire Alarm Control Panel

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Barrier. ED /07/09 Release to production R.P. A ECO N DATE DESCRIPTION OF CHANGE CHG By ISSUE TITLE TC842B1007 AE PRODUCT SPECIFICATION

PAD100-6DB & PAD100-4DB PAD100-PD

Installation, Operating and Maintenance Manual

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

ZNS MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL PANEL. Installation & Operation Manual

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

intelligent solutions

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

Fire Alarm and Life Safety System Inspection Certificate

Addressable Detectors & Bases

FEC400 Series. Installation Manual

Fire Alarm System Fundamentals

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Installation Instructions Model DLC

Notification Appliance Circuit Module

Control Panels D9412GV4/D7412GV4/D7212GV4. Approved Applications Compliance Guide

4100U City and Relay Cards Installation Instructions

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Multi-Application Peripherals and Accessories

AND ARCHITECT SPECIFICATIONS

FIRE ALARM SYSTEM FRCME AMS R2M SOM CZM DIMM. Serial. Annunciator. Printer ATG-EA ALK-V. Duct Detector SLC (DCP) Notification Alarm Equipment

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Fire Alarm Testing and Inspection Report

QS1 Intelligent single loop life safety control panel

DCP-FRCME - FAST RESPONSE CONTACT MODULE

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

Signature Series Component

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Genesis Series Cable THE POWER OF CHOICE. Cables for Silent Knight

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

4007ES Fire Control Panels

Fire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features

An introduction to... Sigma

7706-ULF Integrated Fire Monitoring System. Installation, Operation & Programming Manual

Transcription:

NOTICE TO THE INSTALLER This manual provides an overview and the installation instructions for the IDC-6 module. All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions. The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation. 1. DESCRIPTION The Initiating Device Circuit Expander (IDC-6) provides an additional 6 inputs per module. The panel supports up to thirty-one (31) IDC-6 modules. The circuits are power-limited and supervised. All inputs are suitable to monitor 2-wire smoke detectors. Smoke detectors shall be installed in compliance with NFPA 72. Inputs can also be used for automatic, manual, waterflow or supervisory service. The IDC-6 communicates via the PLink communication bus. The IDC-6 can be mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting. 2. SETTING THE ADDRESS Each P-Link device has a five (5) position dip switch which is used to program the device address ranging from one (1) to thirty-one (31). The table below may be used to set dip switches when addressing any P-Link module: Figure 1. DIP SWITCH SETTINGS TABLE (ADDRESSES 1 31) 1 2 4 8 16 1 2 4 8 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 9 25 10 26 11 27 12 28 13 29 14 30 15 31 16 1 2 4 8 16 1 2 4 8 16 Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off." The examples shown below illustrate a P-Link's dip switch settings: the 1st example shows a P-Link module not addressed where all dip switch settings are in the default "Off" position, the 2nd illustrates an addressed P-Link module via the dip switch settings. Figure 2. EXAMPLES OF P-LINK MODULE SHOWING DEFAULT DIP SWITCH SETTING (UNADDRESSED) & ADDRESSED 1 2 4 8 16 ON OFF All dip switches are shown in the "Off" position. 1 2 4 8 16 Example shows this P-Link module ON address = 10. Dip switches #2 & 8 are in the "On" position. OFF PAGE 1 OF 5

Before connecting a device to the RS-485 connection, take the following precautions to prevent potential damage to the RS-485 connection. Power to the RS-485 connection is removed. Field wiring on module is correctly installed. Field wiring has no open or short circuits. 3. TECHNICAL SPECIFICATIONS P-Link Standby Current P-Link Alarm Current IDC PWR Standby Current IDC PWR Alarm Current Input Zone Wiring Resistance Input Zone Capacitance Input Zone Short Circuit Current 20 ma 20 ma 30 ma (maximum Standby) 270 ma (maximum Alarm) 100 ohms max 1 mf max 47 ma Operating Temperature Range 32 to 120 F (0 to 49 C) Operating Humidity Range Max no. of IDC-6 Expanders 31 10%-93% (non-condensing) Dimensions (WxHxD) 4" x 6" x 1 5/8" Note: IDC PWR can be provided by any fire listed source. Power must be 16 VDC- 33 VDC, and must be power limited. 4. INSTALLATION The IDC-6 is connected to the fire control panels using a 4-wire RS-485 connection. The connection is power limited and supervised. The IDC-6 must be mounted in either a compatible fire alarm panel, the PSN-1000, or within 20 feet of the panel or power supply using the AE-2, AE-8, or the AD-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting. The wiring diagrams shown below illustrate how to wire a IDC-6 as Class B and Class A. Figure 3. CLASS B P-LINK AND IDC POWER WIRING PAGE 2 OF 5

Figure 4. CLASS A P-LINK AND IDC POWER WIRING Figure 5. EXAMPLE OF WIRING A IDC-6 MODULE CLASS A (LEFT) OR CLASS B (RIGHT) Normally Open Contact Potter Part #3005013 5.1 K EOL Normally Open Contact or Smoke Detector INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 + - + - + - + - + - + - INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 + - + - + - + - + - + - NOTES: Input 1 - Input 6 are power limited, 24 VDC inputs RS-485 wiring style supports class A and class B. RS-485 is power limited. Wiring for terminals (A, B) and (+, -) are supervised. All wiring is between #12 (max.) And #18 (min.). Wire preparation strip all wires 1/4 inch from their edges as shown here: Stripping too much insulation may cause a ground fault. 1/4 inch Stripping too little may cause a poor connection and subsequently an open circuit. These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance. Specifications subject to change without prior notification. For Technical Assistance contact Potter Electric Signal Company at 866-956-1211. Actual performance is based on proper application of the product by a qualified professional. Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purpose, the matter should be referred to a distributor in your region. PAGE 3 OF 5

Table 1: COMPATIBLE CONVENTIONAL SMOKE DETECTORS & BASES DETECTOR MODEL Identifier Base Model Identifier SYSTEM SENSOR (BRK) (MAX. NO. OF DETECTORS PER ZONE IS 20) 1400 A N/A N/A 2400 A N/A N/A 2400TH A N/A N/A 2W-B A N/A N/A 2WT-B A N/A N/A DETECTION SYSTEM (MAX. NO. OF DETECTORS PER ZONE IS 25) DS250 A MB2W/MB2WL A DS250TH A MB2W/MB2WL A ESL (MAX. NO. OF DETECTORS PER ZONE IS 25) 611U S10 601U S00 611UD S10 601U S00 611UT S10 601U S00 612U S10 601U S00 612UD S10 601U S00 613U5 S10 601U S00 611UD S10 609U10 S00 612UD S10 609U10 S00 425C S10 N/A N/A 425CT S10 N/A N/A HOCHIKI (MAX. NO. OF DETECTORS PER ZONE IS 25) SLR-24 HD-3 HSC-221R HB-71 SLR-24H HD-3 HSC-221R HB-71 SIJ-24 HD-3 HSC-221R HB-71 SOC-24V HD-3 SOC-24VN HD-3 FENWAL (MAX. NO. OF DETECTORS PER ZONE IS 25) CPD-7051 151FE1 2-WIRE FE51A PSD-7155 P55FE1 2WRLT FE52A PSD-7156 P56FE1 2WRB FE55A ALL OF THE ABOVE FENWAL DETECTORS AND BASES CAN BE USED IN ANY COMBINATION. RETROFIT BASE ADAPTOR 70-501000-003, IDENTIFIER MAFE1 (FOR SERIES 70-201000 BASES, MODELS -001,-002,-003 AND -005). DUCT HOUSING WITH DETECTOR BASE DN-51, IDENTIFIER DH22FE5 (FOR CPD-7051 AND PSD-7155 DETECTORS ONLY). PAGE 4 OF 5

DETECTOR MODEL Identifier Base Model Identifier POTTER (MAX. NO. OF DETECTORS PER ZONE IS 25) PS-24 HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI) (HOCHIKI) (HOCHIKI) PS-24H HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI) (HOCHIKI) IS-24 HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI) (HOCHIKI) CPS-24 HD-3 (HOCHIKI) SB-46 (HOCHIKI) (HOCHIKI) CPS-24N HD-3 (HOCHIKI) SB-46 (HOCHIKI) (HOCHIKI) NOTE: IF USING A MIX OF SYSTEM SENSOR AND OTHER SMOKE DETECTORS, A MAXIMUM OF 20 DETECTORS SHALL BE PERMITTED. PAGE 5 OF 5