NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 184 - QUEENS, 163-15 21 ROAD, New York, 11357 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-05 11:46 AM 2018-04-11 3:18 PM Asset Data Type of Service Does Interactive Whiteboard (IWB) Exist? Water Penetration in Electrical Room? Have any Systems/Major Building Components been upgraded? DEDICATED INTERCOMS IN FIRE RESCUE AREAS Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building? Answer Below Ground Years: Years: 2016 Years: 2015 Years: 2012 Years: 2011 Years: 2008 Years: 2006 Years: 1997 Fire Alarm System (Electronic Sub-Panel, CO Detectors) Under construction Auditorium (Except House ) Service Switch, Switchboard, Exit Lights (Battery Pack), Intrusion Alarm System (Partial Remote Annunciator), Interior, Grounding System Public Address System (Master Clock) Exit/Emergency Lights Gymnasium (Scoreboard), Library (Raceway With Receptacles) Public Address System (Tuner) Emergency Light/Exit Light Panel, Security Lights Molded Case Circuit Breaker Panel Board Years: 1990, 1999, 2015 No Priority Priority Priority Exist Category Last Year? Description Component Affected Location Description Person(s) Notified Person(s) Title Status PhotoImage No Water Leaks onto Electrical Equipment N/A Electrical Junction Box Basement Crawl Space Eddie Shurman Fireman Sent to DSF Water Penetration in Electrical Room N/A Electrical Equipment Electrical Room Eddie Shurman Fireman Sent to DSF Inspection Electrical AUDITORIUM House Does a Chandelier exist? No PB/A&W Page 1 of 12
Building Assessment Survey 2017-2018 AUDITORIUM House Fixture - HID Fixture - Incandescent Fixture - LED Local Sound System Installation Year 2016 Custodial Staff Projection System Is the projector on a cart or installed on the ceiling? Ceiling Theater System Dimming System Theater CAFETERIA PB/A&W Page 2 of 12
Building Assessment Survey 2017-2018 CAFETERIA Fixture - HID Fixture - Incandescent Fixture - LED Local Sound System Installation Year 1990 BEYOND USEFUL LIFE Location/Instance CAFETERIA - 1st Floor Quantity 1 Urgency of Action PRIORITY 1 Photo1 Projection System Theater System CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Does a Chandelier exist? Fixture - HID Fixture - Incandescent No PB/A&W Page 3 of 12
Building Assessment Survey 2017-2018 CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Fixture - LED COMPUTER LAB Power Panel Fixture - HID Fixture - Incandescent Fixture - LED Raceway With Receptacles GYMNASIUM Fixture - HID Fixture - Incandescent Fixture - LED Local Sound System PB/A&W Page 4 of 12
Building Assessment Survey 2017-2018 GYMNASIUM Local Sound System Installation Year 1990 BEYOND USEFUL LIFE Location/Instance CAFETERIA - 1st Floor Quantity 1 Urgency of Action PRIORITY 1 Photo1 Projection System Scoreboard Theater System KITCHEN Fixture - HID Fixture - Incandescent Fixture - LED LIBRARY 2 - Between Good and Fair PB/A&W Page 5 of 12
LIBRARY Fixture - HID Fixture - Incandescent Fixture - LED Raceway With Receptacles Projection System LOCKER ROOM MULTIPURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM SWIMMING POOL TOILET ROOM - STAFF Fixture - HID Fixture - Incandescent Fixture - LED TOILET ROOM - STUDENT NYC Department of Education Building Assessment Survey 2017-2018 2 - Between Good and Fair PB/A&W Page 6 of 12
Building Assessment Survey 2017-2018 TOILET ROOM - STUDENT Fixture - HID Fixture - Incandescent Fixture - LED AUXILIARY SIGNAL/BELL SYSTEM Replacement Quantity 57,000 Replacement Uom S.F. EMERGENCY DC STANDBY BATTERY POWER EMERGENCY GENERATOR SET EMERGENCY LIGHT/EXIT LIGHT PANEL EMERGENCY LIGHTING Battery Pack BATTERY NOT OPERATIONAL Location/Instance Cafeteria, Auditorium Quantity 3 BATTERY Urgency of Action PRIORITY 5 Photo1 Non Battery Pack EXIT LIGHT Battery Pack Non Battery Pack EXIT/EMERGENCY LIGHT 2 - Between Good and Fair CITY FIRE ALARM SYSTEM 5 - Poor NOT OPERATIONAL Location/Instance By General Office Quantity 1 PB/A&W Page 7 of 12
Building Assessment Survey 2017-2018 CITY FIRE ALARM SYSTEM Urgency of Action PRIORITY 5 Photo1 FIRE ALARM SYSTEM Replacement Quantity 57,000 Replacement Uom Bell/Horn Strobe Manual Pull Station Fan Shutdown Control Duct Smoke Detector Area Smoke Detector CO Detector Heat Detector Elevator Recall Magnetic Door Holder/Contactor Fused Cutout Panel Fire Alarm Digital Communicator Main Panel Bell At Panel Fire Alarm Control Panel (Electronic) Fire Alarm Control Panel (Standard) Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment Capacity/Size Quantity 6 Capacity/Size UOM Source of Capacity/Size S.F. Under Construction Boiler Room ACME Fire Alarm Panel Circuits Installation Year 1952 Location/Instance Quantity 1 Inspector Estimate Documented BEYOND USEFUL LIFE CAFETERIA - 1st Floor Urgency of Action PRIORITY 1 PB/A&W Page 8 of 12
Building Assessment Survey 2017-2018 FIRE ALARM SYSTEM Main Panel Fire Alarm Control Panel (Standard) Photo1 Sub-Panel Bell At Panel Fire Alarm Control Panel (Electronic) Under Construction Fire Alarm Control Panel (Standard) Instance Boiler Room Instance Instance Quantity 1 Instance Instance Manufacturer ACME Equipment Sprinkler Water Flow Capacity/Size Quantity 2 Capacity/Size UOM Circuits Source of Capacity/Size Inspector Estimate Installation Year 1952 Documented BEYOND USEFUL LIFE Location/Instance CAFETERIA - 1st Floor Quantity 1 Urgency of Action PRIORITY 1 Photo1 Remote Annunciator Sprinkler Flow/Air Pressure Switch Tamper Flow Switch/Chain GROUNDING SYSTEM INTERCOM SYSTEM LAN Local Distribution Frame (I/LDF) Main Equipment Rack (MDF) PB/A&W Page 9 of 12
LAN Main Equipment Rack (MDF) LIGHTNING PROTECTION MOTOR CONTROL CENTER MOTOR STARTER/CONTACTOR PANEL BOARD Fused Disconnect Switch Type Fused Knife Switch Type Fused Toggle Switch Type Molded Case Circuit Breaker Type Location/Instance Quantity 3 PANEL BOARD DIRECTORY MISSING OR REQUIRES UPDATING Cafeteria, Boiler Room MAINTENANCE Urgency of Action PRIORITY 2 Photo1 NYC Department of Education Building Assessment Survey 2017-2018 PUBLIC ADDRESS SYSTEM Replacement Quantity 57,000 Replacement Uom SECURITY Instance Instance Instance Quantity 1 Instance Model S.F. General Office Installation Year 1970 Location/Instance Quantity 1 N/A Inspector Estimate BEYOND USEFUL LIFE CAFETERIA - 1st Floor Urgency of Action PRIORITY 1 Photo1 IPDVS/CCTV System Intrusion Alarm System Replacement Quantity 57,000 Replacement Uom Central Control Panel S.F. PB/A&W Page 10 of 12
Building Assessment Survey 2017-2018 SECURITY Intrusion Alarm System Central Control Panel Instance Custodian's Office Instance Instance Quantity 1 Instance Model N/A Installation Year 1990 Inspector Estimate BEYOND USEFUL LIFE Location/Instance CAFETERIA - 1st Floor Quantity 1 Urgency of Action PRIORITY 1 Photo1 Infrared Sensor Panic Switch Remote Annunciator 2 - Between Good and Fair Siren/Strobe Ultrasonic Sensor - Security Replacement Quantity 32 Replacement Uom TIME CLOCK NOT OPERATIONAL Location/Instance By Rooms (205, 220) Quantity 2 Urgency of Action PRIORITY 2 Purpose of Action LEVEL 3 Photo1 SERVICE SWITCH Instance Electrical Room Instance Instance Quantity 1 PB/A&W Page 11 of 12
SERVICE SWITCH Instance Instance Manufacturer Equipment Gavan-Graham Main Capacity/Size Quantity 1,600 Capacity/Size UOM Source of Capacity/Size Amps Installation Year 2015 SWITCHBOARD Number of Spares 11 Air Circuit Breaker Type Fused Disconnect Switch Type Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment Nameplate Documented Electrical Room Capacity/Size Quantity 1,600 Capacity/Size UOM Capacity/Size2 Quantity 2 Capacity/Size2 UOM Source of Capacity/Size Installation Year 2015 Fused Knife Switch Type Molded Case Circuit Breaker Type TELEPHONE SYSTEM PBX/Intercom Standard TRANSFORMER TV SYSTEM Cable System Exist? Operational? Main Equipment Rack NYC Department of Education Building Assessment Survey 2017-2018 N/A N/A Amps Total Section(S) Nameplate Documented PB/A&W Page 12 of 12