Installation and maintenance instructions

Similar documents
and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

Operating instructions Oil condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

Operating instructions

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

Installation and maintenance instructions

VIESMANN. Operating instructions VITODENS 100-W. for the system user

Installation and maintenance manual

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

Installation and maintenance instructions

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Operating instructions

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS 111-W. for the system user

WHE 2.24 / WHE 2.24 FF

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

WOLF GAS CONDENSING BOILERS COMFORTLINE

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

INSTALLATION AND MANINTENANCE INSTRUCTIONS

/2010 US/CA

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

HOT WASHER MODEL NO: KING150

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VETO CLEANER 500 FLUE GAS CLEANER

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

Operating Instructions

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

Installation, operating and servicing instructions

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

Gas Instantaneous Water Heater

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

POWER SHOWERS Models 4500M 5002M 4500T 5002T

Installation, operation and care. Pellmax UB. Burner not included Replaces:

INSTRUCTION MANUAL (English version) Water still

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

Operating instructions

Operating instructions

Installation and maintenance instructions

DTG Eco / V130

15KW ELECTRIC FAN HEATER

Technical documentation. ComfortLine gas condensing boilers CGB-2(K) CGW-2 CGS-2 CSZ-2 NEW

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

USERS MANUAL FOR GAS BOILERS

Operating instructions

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

Installation, Operating and Servicing Instructions

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Installation and operating instructions. DK energy storage and DK energy buffer

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Alpha CombiMax 350 and 600

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Installation, Operating and Servicing Instructions

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

Installation and maintenance instructions

atmocraft VK 654/9-1654/9 DE/AT/GB/CZ/SK/HU/PL/HR/SI/SCG

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

GB162 Concentric Horizontal Vent Kit

Fan coil unit KL. Wall unit Ceiling unit

Light oil burners. One stage operation

TERMO Combi Cylinder TECHNICAL INFORMATION

User s Information Manual

CI/SfB X. RHeco Series CONDENSING GAS FIRED UNIT HEATERS

AGS 2 SOLAR PUMP STATION FOR SOLAR DOMESTIC HOT WATER SYSTEMS UK/IE

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Installation and service instructions for contractors Logano plus SB625. Burner shroud not available in UK and Ireland

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

User s Information Manual

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

VIESMANN VITOLADENS 300-T Oil Unit condensing boiler 35.4 to 53.7 kw

BM Programming Module. For the heating engineer Installation instructions

Installation and maintenance instructions for contractors

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

AQUARIUS 45 MARINE SERVICE MANUAL

User s Information Manual

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

HX Field Replacement Kit

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Transcription:

Technology serving Mankind Installation and maintenance instructions ComfortLine FunctionLine Steel boilers up to 63 kw Wolf GmbH Postfach 1380 84048 Mainburg Tel. +49 8751/74-0 Fax +49 8751/741600 Internet: www.wolf-heiztechnik.de Part.-No. 30 60 917 Subject to modifications 12/03 TV GB

Index Index... Page Reference symbols / Safety instructions...3 Standards / Regulations... 4-5 ComfortLine steel boilers...6 FunctionLine steel boilers...7 Installation... 8-9 Boiler installation on a plinth... 10 Boiler installation on a horizontal DHW cylinder... 11 Boiler assembly... 12-15 ComfortLine decorative panel installation... 16-17 FunctionLine decorative panel installation... 18 Flue pipe installation... 19 Central heating boiler connections... 20 DHW cylinder to boiler pipework... 21 Filling the heating system... 22-23 Draining the heating system... 24 Pressure jet oil burner installation / electrical supply... 25 Initial start-up... 26 Commissioning report... 27 Maintenance... 28-29 Maintenance log... 30-31 Specification... 32-33 Dimensions... 34-35 Troubleshooting... 36 2

Reference symbols / Safety instructions The following symbols are used in conjunction with these important instructions concerning personal safety and technical reliability. Note "Safety instructions" are instructions with which you must comply exactly, to prevent injury and material losses. Danger through "live" electrical components. Please note: Switch OFF the ON/ OFF switch before removing the casing. Never touch electrical components or contacts when the switch is in the ON position. This creates a risk of electrocution, which may cause injury or death. The main supply terminals are "live" even when the ON/OFF switch is in the OFF position. This indicates technical instructions which you must observe to prevent material losses and boiler malfunctions. In addition to the installation instructions, operating instructions and adhesive labels are included or fitted to the boiler. These must also be observed. General Authorised personnel should read these instructions before any installation, commissioning or maintenance work. Adhere to the instructions given in this document. Non-observance of these installation instructions voids any guarantee offered by WOLF. Safety instructions Only use qualified and trained personnel for the installation, commissioning and maintenance of the boiler. In accordance with DIN EN 50110-1, work on electrical components (e.g. control units) may only be carried out by qualified electricians. The regulations of VDE/ÖVE and those of your local electricity supplier as well as all other local regulations are applicable to electrical installation work. Only operate the boiler within its output range which is stated in the specification supplied by WOLF. Appropriate use of the boiler refers to the exclusive use for hot water heating systems in accordance with DIN 4751. Never remove, bypass or otherwise disable any safety and monitoring equipment. The boiler may only be operated in perfect technical condition. Any faults and damage which may impact on safety which might limit the safe use of the equipment must be remedied immediately by a qualified contractor. Only replace faulty components or equipment with original WOLF spare parts. 3

Standards / Regulations Standards and regulations Observe all current Building Regulations and other local requirements. Only recognised heating contractors may install WOLF boilers. This heating contractor will also be responsible for the proper installation and the commissioning of the heating system. The boilers described in these installation instructions are low temperature boilers according to HeizAnlV and 92/42/EEC (Efficiency of Hot Water Boilers). Locate the enclosed operating instructions in a clearly visible position in the boiler room. Boilers may only be installed and operated in boiler rooms which are suitable according to the Landes-FeuVo [or local regulations]. The following regulations, rules and guidelines must be observed during installation: Boiler room guidelines or Building Regulations relating to the construction and installation of central boiler rooms and fuel storage facilities. Energy Savings Act (EnEG) and related directives (Heating Systems Order). DIN standards DIN 1988 Technical rules for DHW installations DIN 4701 Rules for calculating the heat demand of buildings DIN 4751 Part 3 - Safety Equipment for heating systems with flow temperatures up to 95 C DIN 18160 Domestic chimneys VDE requirements: VDE 0100 General information regarding the installation of HV systems with rated voltages up to 1000V VDE 0105 VDE 0722 VDE 0470/ EN 60529 Operation of HV systems, general considerations Electrical equipment of non-electrically heated heat generators Protection through housings EN 60335-1 Safety of electrical equipment for domestic use and similar purposes Note: Please read these instructions carefully before the installation and keep them in a safe place. 4

Standards / Regulations Steel boilers according to DIN EN 303 as well as in accordance with EC Directive 90/396/EEC (gas consuming equipment), 73/23/EEC (Low Voltage Directive), 89/336/EEC (EMC Directive), 92/42/EEC (Efficiency of Hot Water Boilers) and 93/68/EEC (Identification Directive) for heating systems with heating circuit pumps and flow temperatures up to 110 C and 3 bar permissible operating pressure in accordance with DIN 4751 and DHW cylinder pressure (max. 10 bar) in accordance with DIN 4753. For the operation with pressure jet gas burners, the following gas device categories apply: Country abbreviation Country Gas device category DE Germany II 2ELL3B/P AT Austria II 2H3B/P LU Luxembourg I 2E or I 3+ The NO x limits required by the 1st BImSchV para. 7(2) are maintained. 5

ComfortLine steel boilers Oil and gas-fired steel boiler, type CNK (boiler plinth, accessory) Oil and gas-fired steel boiler, type CNK-CB incl. DHW cylinder Oil and gas-fired steel boiler, type CNU incl. pressure jet oil burner (boiler plinth, accessory) 6 Oil-fired steel Unit boiler, type CNU-CB incl. DHW cylinder and pressure jet oil burner

FunctionLine steel boilers Oil and gas-fired steel boilers, type FNK (boiler plinth, accessory) Oil and gas-fired steel boiler, type FNK-FB/FE incl. DHW cylinder Oil-fired steel Unit boiler, type FNU incl. pressure jet oil burner (boiler plinth, accessory) Oil-fired steel Unit boiler, type FNU-FB/FE incl. DHW cylinder and pressure jet oil burner 7

Installation General tips regarding location Install the boiler with or without the DHW cylinder on a level surface which is substantial enough to carry its weight. Position the boiler and DHW cylinder (if installed) horizontally or slightly rising towards the back to ensure adequate venting of any trapped air (level with adjustable feet). Note Only install the boiler and DHW cylinder (if installed) in a room safe from the risk of frost. Drain the boiler, the DHW cylinder and the entire heating system if there is a risk of frost, when the system has been shutdown, to prevent pipes from bursting. The ventilation air supply must be ensured and comply with local regulations or those relating to gas installations. We recommend that you supply the boiler with fresh air directly from the outside. An insufficient fresh air supply can lead to fuel gas escaping, which represents a risk to life (poisoning/suffocation). Clearances towards walls and combustible materials must comply with local fire regulations, and should be at least 200mm, otherwise there is a high risk of fire. Note Boilers should not be installed in areas subject to aggressive vapours, very dusty or highly humid conditions (workshops, washrooms, hobby rooms etc.). This prevents the optimum burner function from being achieved. The combustion air supplied to the pressure jet oil burner must be free from halogenated hydrocarbons (e.g. as contained in sprays, solvents, cleaning fluids, paints and adhesives). Under the most unfavourable conditions, these may lead to pitting of the boiler and even the flue gas system. Never store or use combustible material or liquids near the boiler. 8

Installation Recommended minimum wall clearance Maintain a minimum clearance between the boiler sides and walls of 400 mm to enable the boiler door with fitted burner to be opened. Ensure that sufficient space is available for cleaning and maintenance. 900 400 1000 Recommended minimum wall clearance Transportation into the boiler room To ease the transportation into the boiler room, lifting slings with lifting hooks are offered as accessories. Note Only lift the boiler using all four lifting slings. Lifting eyes for lifting slings Boiler installation on adjustable feet At the factory the boiler is equipped with four adjustable feet. Level the boiler with adjustable feet (accessory) horizontally or with a slight incline to the rear. Adjustable bolt Adjustable bolt/ feet Feet (accessory) 9

Boiler installation on a plinth 10 13 8 9 3 13 2 1 6 5 5 11 11 4 7 14 15 12 1 Boiler 9 Control unit housing 2 Thermal insulation, boiler 10 Casing cover 3 Thermal insulation, boiler back 11 Spring shackles 4 Thermal insulation, boiler front 12 Front casing 5 Side casing 13 Type plate 6 Control unit bracket 14 Wolf logo 7 Boiler door 15 Plinth (accessory) 8 Back wall casing 10

Boiler installation on a horizontal DHW cylinder 10 13 8 9 3 13 2 6 1 5 5 11 11 4 7 14 15 12 1 Boiler 9 Control unit housing 2 Thermal insulation, boiler 10 Casing cover 3 Thermal insulation, boiler back 11 Spring shackles 4 Thermal insulation, boiler front 12 Front casing 5 Side casing 13 Type plate 6 Control unit bracket 14 Wolf logo 7 Boiler door 15 Horizontal DHW cylinder 8 Back wall casing 11

Boiler assembly 1 Boiler Install the plinth or the DHW cylinder in accordance with the enclosed installation instructions. Position the boiler with adjustable bolts fully inserted using the lifting slings on the fully assembled plinth or DHW cylinder. To secure the boiler to the plinth or DHW cylinder, tapped holes are provided at the front sides of the boiler. Additional fixings are not required. Screws for securing the boiler Screws for securing the boiler to the plinth Screws for securing the boiler Check the horizontal level of the boiler together with the plinth and DHW cylinder and adjust, with a slight incline to the rear, if necessary. Fixing screws on the DHW cylinder 2 Position the thermal boiler insulation around the boiler (overlapping) and secure with spring clips. 3 Position the thermal insulation for the boiler back over the rear connections and on the back wall of the boiler. 4 12 Position the thermal insulation for the boiler front loosely on the boiler

Boiler assembly 5 Insert the side casing into the boiler front pushing the spring shackles 11 behind the boiler bracket Spring shackle Bracket Side casing installation and fit the lower folded edge into both notches (view X). Lower folded edge of the side casing View X Boiler notch Side casing installation 6 Locate the control unit bracket centrally and push parallel forward, until both recesses in the side casing click into the control unit bracket tabs. Control unit bracket Hooks Side casing Secure the control unit bracket and side casing with the self-tapping screws supplied (6 no.). Control unit bracket installation Self-tapping screws Side casing fixing screws 13

Boiler assembly 7 Fit the boiler door with the four M10x45 screws and washers supplied. Insert the door hinge pins into the door bracket on the l.h. or r.h. side, subject to door opening. Door hinge pin M10x45 screws Boiler door installation 8 Hook the back wall casing with tabs into the notches in the side casing, and secure with the self-tapping screws (4 no.) supplied. Back wall notches Rear wall installation Self-tapping screws 9 Push the control unit housing with locking tabs into the apertures in the control unit bracket and pull forward to its end stop. Secure the control unit housing with the two self-tapping screws supplied to the control unit at the l.h. and r.h. rear, working from top to bottom. Route the boiler sensor to the rear and push into the sensor well in any arrangement, then secure with the circlip. Locking tabs Control unit bracket Secure tightly Control unit housing installation 14

Boiler assembly 9 Guide the burner cable through the aperture in the control unit bracket (l.h. or r.h. subject to boiler door opening). Clip a cover cap into the control unit bracket to protect the burner cable. Secure the cable clip with the burner cable at the l.h. or r.h. side (bottom) of the boiler. Cover cap Cable clip Burner cable holder 10 Position the casing cover onto both side casings and push towards the control unit bracket. 12 Push the front casing with open control unit lid with the profile screws against the spring shackles 11, until they click into place. Front casing installation 13 Affix the type plate in a clearly visible position. Wolf logo 14 Clip the Wolf logo into the front casing (only for FunctionLine). Type plate Type plate / Wolf logo 15

ComfortLine decorative panel installation In addition, all ComfortLine boilers require the following work to be undertaken. Decorative panel Position the decorative panel with the document wallet on the holes and push against the front casing, until the clips click into place. Decorative panel installation Decorative frame (CNK 17-60 single boiler) Click the plastic clips (4 no., black) into the front casing. Position the decorative frame onto the clips and push down to their end stop. Decorative panel installation, single boiler 16

ComfortLine decorative panel installation Decorative frame (CNU 17-32 Unit boiler) With the dome at the top, push the silencer hood into the decorative frame, then secure the silencer hood with four self-tapping screws from the inside to the decorative frame. Silencer hood Self-tapping screws Decorative frame Joining the decorative frame and the silencer hood Click both top plastic clips (black) from the outside into the front casing. Click both lower plastic clips (black) from the inside into the front casing. Hook the decorative frame with the silencer hood into the top clips and secure in the lower plastic clips. Decorative panel installation, Unit boiler Large silencer hood (CNU 40-63 Unit boiler) Click the plastic clips (4 no., orange) into the front casing. Position the large silencer hood onto the clips and push down to their end stop. Large silencer hood installation 17

FunctionLine decorative panel installation For models FNU-TH/17/20/25, the following additional work should be undertaken. Decorative panel Click the plastic clips front casing. (4 no., grey) into the Decorative panel Decorative panel installation 18

Flue pipe installation The flue pipe cross-section must match that of the boiler flue outlet. Reducing the flue pipe size is only permitted, if the satisfactory function has been verified (by calculation) in accordance with DIN 4705. Keep the flue pipe as short as possible and inclined towards the chimney stack. Thoroughly seal in the flue pipe. Use flue pipe elbows with clean-out covers to facilitate the cleaning of the flue pipe. Flue pipe outlet Clean-out covers in flue pipe elbows Clean-out covers 19

Central heating boiler connections Connect the heating flow and return to the respective boiler fittings. For connections, see below. Install a check valve downstream of the boiler circuit pump(s) to prevent incorrect circulation. Install a safety assembly comprising a safety valve with a response pressure of 3 bar and an automatic air-vent valve.the pipework between the boiler and the safety valve must not be able to be shut off. Severely excessive boiler pressure due to excessive boiler temperature, can burst the boiler body or the boiler pipework, which would lead to a sudden excape of hot water (risk of scalding). Connect any underfloor heating system via a three or four-way mixer. Note Provide system separation by means of a heat exchanger, when using pipes which are not impermeable to oxygen. This boiler is only suitable for heating systems with pumped heating circuits. If no heating circuit pump has been installed, sufficient circulation through the radiators cannot be ensured, putting the room heating in question. Recommendation: Convert open systems into sealed systems. Return temperature raising facility Note Heating systems with large water volume (above 20 litres per kw output) require a return temperature of 30 C, as otherwise the longer heat-up time of such systems would create condensate and run an increased risk of boiler body corrosion. Sensor well Connection for venting and safety flow Boiler flow Boiler flow Boiler return Boiler return Filling / Draining Central heating boiler connections 20

DHW cylinder to boiler pipework Install the pipework between the boiler and the DHW cylinder in accordance with the illustration below. Note The DHW cylinder loading pump must supply from the top to bottom. Close any boiler flow and return connections which are not required with caps and gaskets supplied. Elbows Ferrule with union nut Cylinder loading pump incl. gaskets Gravity brake Boiler flow 2x Boiler return 2 x DHW outlet Hoses with gaskets DHW circulation Sensor well for DHW cylinder sensor Cold water inlet DHW cylinder to boiler pipework 21

Filling the heating system Fill the system and vent it properly to safeguard the perfect boiler function. Note Before connecting the boiler to the heating system, flush the entire system to remove residues such as welding pearls, hemp, putty, etc. from the pipework. Connection for venting and safety flow Note The boiler and central heating system may only be filled, if a typetested safety valve (opening pressure max. 3 bar) has been installed. Filling the heating system Filling Connect a water hose to the filling/drain valve (on-site). Hose connection Boiler fill and drain valve Open the cap of the quick-action air-vent valve of the safety assembly (accessory) by one revolution, but do not remove the cap. Locking cap Automatic air-vent valve With the boiler in a cold condition, fill the heating system slowly via the fill and drain valve, until 1 bar pressure is indicated. Inhibitors are not permissible. Automatic air-vent valve 22

Filling the heating system Observe the pressure gauge of the safety equipment assembly when filling the system with water. Pressure gauge Safety assembly pressure gauge For boilers with DHW cylinder, vent the heating coil at a system pressure of approximately 0.50 bar or less by starting the DHW cylinder loading pump (operating time approximately 2 minutes). Check the entire system for water leaks. Check the safety valve function. Ventilate the boiler (e.g. via an automatic air-vent valve). Fill the system to 1 bar pressure. In operation, the pressure gauge must indicate between 1 and 2.5 bar. Top up with water when the system pressure falls severely. In constant mode, the boiler automatically vents via the air-vent valve. 23

Draining the heating system Switch OFF the heating system (see operating instructions) and let it cool down to a maximum of 40 C, to prevent the risk of scalding. Connection for venting and safety flow Open the drain tap on the boiler. Open the radiator bleed valves. Drain the heating water off. Drain Draining the heating system Hose connection Boiler fill and drain valve 24

Pressure jet oil burner installation The Unit pressure jet oil burner installation instructions are included in the burner packaging. Pressure jet oil burner installation / Electrical supply Only use bolts when securing the burner to the boiler flange, whose thread penetrates the boiler flange by a maximum of 15 mm. Only use pressure jet gas burners compliant with EC Directive 90/396/EEC. Boiler flange Burner flange holes Burner plug wiring diagram Electrical supply Cable grommets Note Do not route sensor leads with 230 V mains cables. Connect the heating circuit pump(s) and the DHW cylinder loading pump(s) on-site via contactor, if: The burner and pump draw more than 2 A each. The total control unit power consumption is exceeded. Electrical supply Observe the control unit installation and operating instructions. 25

Initial start-up Only qualified personnel may carry out the commissioning and operation of the boiler and the instruction of the user. Check the boiler and system for leaks. Close the water outlet - risk of overheating and scalding. Check that all flue gas accessories have been correctly installed. Open the shut-off valves on flow and return. Switch ON the system ON/OFF switch on the control unit. Note: When the heating system is started, the display of the weather-compensated control unit indicates all superfluous (not connected) sensors as fault messages. For removing these fault messages see the control unit operating instructions. If the system water pressure falls below 1.0 bar, top up with water until a pressure of 1.0 to max. 2.5 bar has been achieved. An error code will flash in the display, if the boiler/burner fails to start properly. For details about error codes see the quickstart operating instructions. Instruct the customer in the operation of the boiler. Complete the commissioning log and hand over the instructions. Position the operating instructions in the boiler room where they are clearly visible. Saving energy Instruct the customer about energy-savings options. Use this opportunity for reducing the heating temperature night operation using control accessories. Adjust the temperature so you are comfortable; every degree of room temperature reduction will achieve energy savings of up to 5%. Reduce the room temperature in unoccupied rooms as far as possible; please observe frost protection. Ensure that all thermostatic radiator valves are fully opened in rooms where room thermostats are installed. The room thermostat must not be obstructed by furniture or curtains. Function checks During commissioning, check all control, regulating and safety equipment for their correct function and settings. 26

Commissioning report Commissioning steps 1.) Water connections checked for leaks? Test values and confirmation 2.) Vented boiler and system? 3.) System pressure 1-2.5 bar? 4.) Function test carried out? 5.) Flue gas test: Gross flue gas temperature Ventilation air temperature Net flue gas temperature t A [ C] t L [ C] (t A - t L ) [ C] Carbon dioxide content (CO 2 ) or oxygen content (O 2 ) % Carbon monoxide content (CO), free of air ppm 6.) Casing fitted? 7.) System user trained, technical documents handed over? 8.) Confirm commissioning 27

Maintenance Note: To ensure the reliable and safe function of a heating system, users are required to have it checked and cleaned on an annual basis by an approved heating contractor (check local regulations). Switch OFF the boiler when cleaning the boiler room. We would recommend a maintenance contract. Switch OFF the heating system (see operating instructions) and let it cool down. Remove the front casing from the boiler. Front casing Front casing removal Pull the burner plug. Release the boiler door screws. Boiler door screws 28 Boiler door removal

Maintenance Open the boiler door. Turbulator Pull out the turbulators (only for CNK-40/ FNK-40 and CNK-63/FNK-63). Turbulators Pull out the hot combustion chamber. Hot combustion chamber Remove soot/sulphur deposits with the cleaning brush supplied. Cleaning using the cleaning brush Assemble in reverse order. 29

Maintenance log Please tick the maintenance steps carried out and enter the test values into this log. Maintenance steps Date Date 1. Cleaned the boiler? 2. Leak test carried out during operation? 3. Function test carried out? 4. Flue gas test: Gross flue gas temperature t A [ C] t A [ C] Ventilation air temperature t L [ C] t L [ C] Net flue gas temperature (t A - t L ) [ C] (t A - t L ) [ C] Carbon dioxide content (CO 2 ) or % % Oxygen content (O 2 ) % % Carbon monoxide content (CO), free of air ppm ppm 5. Confirm maintenance (company stamp, signature) 30

Maintenance log Date Date Date Date t A [ C] t A [ C] t A [ C] t A [ C] t L [ C] t L [ C] t L [ C] t L [ C] (t A - t L ) [ C] (t A - t L ) [ C] (t A - t L ) [ C] (t A - t L ) [ C] % % % % % % % % ppm ppm ppm ppm 31

Specification CNK / FNK / CNU-Premio / CNU-TH / FNU-TH 17 20 25 CNK-CB / FNK-FB / CNU-Premio-CB CNU-TH-CB / FNU-TH-FB 17/155 20/155 25/155 FNK-FE / FNU-TH-FE 17/155 20/155 25/155 Output range without burner kw 14-17 17-20 20-25 incl. Premio burner kw 14-17 17-20 20-25 incl. TH burner kw 14-17 17-20 20-25 Set-up burner output kw 16 19 23 DHW cylinder capacity CB & FB / FE litres 155/150 155/150 155/150 Constant DHW cylinder output CB and FB litres/h 410 490 615 FE litres/h 410 490 615 Performance factor CB and FB NL60 2.7 2.8 3.0 FE NL60 2.7 2.8 3.0 Boiler water capacity litres 51 51 58 Boiler gas content litres 36 36 41 Heating water pressure drop (at T=20K) mbar 6 6 6 Max. permissible boiler pressure bar 3 3 3 Max. permissible DHW cylinder pressure bar 10 10 10 Rel. standby losses Boiler % 1.8 1.6 1.2 Boiler+DHW cyl. % 2.5 2.2 1.8 Required boiler draught Pa 2 3 5 Flue gas temperature* C 160/180 160/180 150/170 Flue gas mass flow rate* kg/h 24/29 29/34 34/42 Boiler flow G 1½" 1½" 1½" Boiler, safety return G 1½" 1½" 1½" Filling, draining, (male thread) R 1" 1" 1" Venting, safety flow (male thread) R 1" 1" 1" Flue pipe diameter mm 129 129 129 Combustion chamber length incl. handle mm 545 545 615 Weight Boiler kg 135 135 141 Burner kg 10 10 10 CHW cylinder CB and FB kg 66 66 66 DHW cylinder FE kg 98 98 98 Electrical supply max. current (ctrl. unit and acc.) Max. current (in total, excl. pumps) Switching capacity pumps, mixer, burner Control unit fuse (max. current) Optional connection for mixer motors * Values for upper/lower boiler output, relative to a CO 2 content of 13% (fuel oil EL) and an average boiler water temperature of 60 C. The chimney stack dimensions must be calculated in accordance with DIN 4705. For flue gas temperatures below 160 C, connect the boiler to highly insulated chimney stacks (heat conductivity resistance class I acc. to DIN 18160 T1) or suitable, moisture-resistant flue gas systems, which have been type-approved. 32

25 32 32 40 50 63 25/200 32/155 32/200 40/200 50/200 63/200 25/200 32/155 32/200 40/200 - - 20-25 28-32 28-32 32-40 40-50 50-63 20-25 28-32 28-32 32-40 40-50 50-60 20-25 28-32 28-32 32-40 40-48 50-63 23 29 29 36 45 55 200 155/150 200 200 200 200 615 780 780 980 1225 1225 615 720 780 930 - - 4.5 3.2 4.8 4.9 5.0 5.0 4.2 3.2 4.4 4.5 - - 58 68 68 68 105 105 41 61 61 61 130 130 6 10 10 10 22 22 3 3 3 3 3 3 10 10 10 10 10 10 1.2 1.1 1.1 0.9 0.9 0.7 2.0 1.4 1.7 1.3 1.4 1.1 5 5 5 7 7 8 150/170 190/200 190/200 170/185 170/190 165/180 34/42 47/54 47/54 54/68 68/85 85/107 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1" 1" 1" 1" 1¼" 1¼" 1" 1" 1" 1" 1¼" 1¼" 129 149 149 149 179 179 615 665 665 665 845 845 141 169 169 169 258 258 10 10 10 15.5 15.5 15.5 83 66 83 83 83 83 121 98 121 121 - - 230 V / 50 Hz / 10A 5 VA 15 VA 230 V, 4(2) A each M 6.3 A 230V, 50Hz, optimum time 4-7 minutes 33

Dimensions B C A E D M G H J K L F 1 B C A E D M G H J K L F 2 CNK / FNK / CNU-Premio CNU-TH / FNU-TH 17 20 25 32 40 50 63 Boiler height A mm 670 670 670 670 670 845 845 Width B mm 660 660 660 660 660 760 760 Length C mm 756 756 826 876 876 1056 1056 Plinth height D mm 280 280 280 280 280 280 280 Overall height incl. control unit E mm 1115 1115 1115 1115 1115 1290 1290 Silencer hood depth F 1 mm 336 336 336 336 345 345 345 Burner hood depth F 2 mm 265 265 265 265 210 235 250 Draining, filling G mm 385 385 385 360 360 364 364 Central heating return H mm 449 449 449 417 417 420 420 Smoke tube connector J mm 607 607 607 607 607 657 657 Central heating flow K mm 775 775 775 807 807 904 904 Exhaustion L mm 828 828 828 853 853 949 949 Heating connections M mm 260 260 260 260 260 300 300 Observe the height of adjustable feet/bolts 20 mm ±10mm. 34

Dimensions B A D E M L K J H G P O C N B F 1 A D E M L K J H G P O C N F 2 CNK-CB / FNK-FB / CNU-Premio-CB CNU-TH-CB / FNU-TH-FB 17 20 25 32 40 50 63 FNK-FE / FNU-TH-FE 17 20 25 32 40 - - Boiler height A mm 670 670 670 670 670 845 845 Width B mm 660 660 660 660 660 760 760 Length of 155 l DHW cylinder C mm 987 987 987 987 - - - Length of 200 l DHW cylinder C mm - - 1262 1262 1262 1262 1262 DHW cylinder height D mm 625 625 625 625 625 625 625 Overall height incl. control unit E mm 1460 1460 1460 1460 1460 1635 1635 Silencer hood depth F 1 mm 336 336 336 336 345 345 345 Burner hood depth F 2 mm 265 265 265 265 210 235 250 Draining, filling G mm 730 730 730 705 705 709 709 Central heating return H mm 794 794 794 762 762 765 765 Smoke tube connector J mm 952 952 952 952 952 1002 1002 Central heating flow K mm 1120 1120 1120 1152 1152 1249 1249 Exhaustion L mm 1173 1173 1173 1198 1198 1294 1294 Heating connections M mm 605 605 605 605 605 645 645 Cold water inlet N mm 90 90 90 90 90 90 90 DHW circulation CB / FB O mm 412 412 412 412 412 412 412 DHW circulation FE O mm 312 312 312 312 312 - - DHW connection P mm 534 534 534 534 534 534 534 Observe the height of adjustable feet/bolts 20 mm ±10mm. 35

Troubleshooting Fault Cause Remedy Burner does not start No voltage present Fuse, electrical connections, or enters a fault state Check the position of the ON/OFF switch at the control unit and heating sys. emergency stop switch. Oil tank empty / Fill oil tank / Gas supply line shut off open gas supply line. Burner fault Press the reset button at burner control unit, (see burner installation instructions). Safety temperature Press the reset button at the control cut-out activated unit. Oil filter clogged Replace oil filter. Heating circuit pump does System in summer mode Check summer/winter switch position. not start Heating circuit pump Turn the pump shaft with a screwdriver. seized up Heating circuit pump faulty Replace the heating circuit pump. Cylinder loading pump DHW cylinder thermostat Check the safety thermostat does not run faulty and replace, if necessary. Cylinder loading pump Turn the pump shaft with a screwdriver. seized up Cylinder loading pump faulty Replace the DHW loading pump. Heating system operational, Maximum boiler temperature Raise maximum boiler temperature. but room temperature set too low. too low Heat-up takes too long Heating water temperature Raise the temperature too low (adjust thermostat) (check at the DHW cylinder flow, not at the boiler) Too little heating water Install larger DHW cylinder loading pump (creates wider spread, i.e. return temperature too low) Indirect coil not vented Vent indirect coil with loading pump OFF Indirect coil scaled up Descale indirect coil DHW temperature Thermostat switches Adjust thermostat too low OFF too soon Return temperature Install larger DHW cylinder loading pump too low (e.g. spread too wide)