TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

Similar documents
aquilar - leak detection solutions

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

aquilar - leak detection solutions

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TT3000 and TT5000 Series

Sensor Interface Module Installation/Operation Instructions

Installation, Operation and Maintenance Manual

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Water Leak Detector. Installation and Troubleshooting. Overview

Modular Sensing Cable Installation Instructions

TT3000 and TT5000 Series

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

TT3000 and TT5000 Series

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

Installation Instructions for W2H Series Signals

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

CEILING FAN OWNER'S MANUAL

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

TraceTek Sensing Cable for Aboveground Leak Detection Installation Instructions

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

Installation Instructions

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

NGC-UIT2-ORD-R Remote User Interface Terminal for Raychem NGC Systems Installation Instructions

Notices. 2 Restek Corporation. Safety Notices

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be

Wiring Instructions (01-09)

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

MANUAL RESET ALARM RELEASE

DESCRIPTION. 42 mm. 125 mm

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

Electronic Crimping Tools REF Operation Guide

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

Industrial Strength Leak Detection

SERVICE MANUAL MULTI DECK 60 HOT MERCHANDISER MULTI DECK 100 HOT MERCHANDISER MULTI DECK 120 HOT MERCHANDISER CLASSIC DECK HOT MERCHANDISER

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Public Safety DAS Annunciator Panel

INSTALLATION AND OPERATIONS MANUAL

ACQUITY UPLC HT Column Heater Instructions

Electronic Ignition Water Heater

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

Chargebuster Ion Gun Installation, Operation and Maintenance

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

4 Channel Contact Closure SFP DIN Fiber Link System

FreezGard. Self-regulating crankcase heater. Product Overview

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

SAFETY INFORMATION AND WARNINGS

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

Manual. Above-counter dispenser for hot drinks OTHG /12

Panel Fan Series Operators Manual (Galvanized and Polymer)

Viking Installation Guide

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Service Manual. Model Number: DFR2651L. UL Part Number

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

MANUAL RESET ALARM RELEASE

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland

Remote Chexit Module (RCM) System. General Information

Pioneer-R16 Gas Monitor Operator s Manual

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

TraceTek TT1000 Modular Sensing Cable

IMPORTANT SAFETY INFORMATION

Duct and Rough Service Carbon Monoxide Sensor

INSTALLATION & OPERATION MANUAL

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers

Dishwasher Installation Instructions DW 24XT/DW 24XV

TraceTek Leak Detection

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Transcription:

TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks. The module provides visual indication when a leak or cable break has occurred and has relay contacts to connect the TTC-1 to external devices for remote monitoring and control. ELECTRICAL CODES Installation must be done in accordance with national and local codes and regulations that apply. The TTC-1 must be installed in ordinary areas only. 2 in (52 mm) 4.4 in (112 mm) Figure 1: TTC-1 Module 4.2 in (106 mm) IMPORTANT NOTES The TTC-1 module is designed for use with TraceTek sensing cables and probes only. A TTC-1 based system will detect and alarm on all fluid leaks detected by the TraceTek cable as per the appropriate cable data sheet. Transient spills and contamination may also activate the system. Users should consider this operational function when determining the suitability of the TraceTek system for specific applications. The system has not been designed for repetitive cycling. Always connect the Leak Detection relay to an annunciation device (for example the nvent RAYCHEM TraceTek TTE-XAL External Loud Alarm) so that an operator is notified and can verify proper operation if automatic equipment is connected. Maintenance personnel should examine the sensing cable for cleanliness and verify proper operation of the TTC-1 module at least every six (6) months. MODULE LOCATION Enclosure rating: IP 20 / NEMA 1 Operating temperature range: 0ºC to 50ºC (32ºF to 122ºF) SPECIFICATIONS Maximum sensing cable length: 250 ft (76 m) Leader cable length is not included in the length limitation. Input power: 12 to 24 Volts AC 0.25 A 15 to 24 Volts DC 0.15 A When using a transformer, use UL listed Class II transformer rated at 24 V, 20 VA Recommended fuse rating: 3 A Relay ratings: 3 A: 30 Volts DC or 24 Volts AC INSTALLATION MATERIALS AND TOOLS REQUIRED Wall fastener (2 ea for surface mounting only) PARTS AND MATERIALS 1 ea TTC-1 Sensing Module 1 ea TTC-1 Wall Label 4 ea Strain Reliefs OPTIONAL ACCESSORIES TTC-DRC DIN Rail Clip Part # 062825-000 TTE-XAL External Loud Alarm Part # 418569-000 TT-MAP-TOOL Part # E43135-000 APPROVALS TYPE NM General Signaling Equipment 76LJ

Installing the TTC-1 Preparation for Mounting Open the knockouts as required on the base unit. The holes are sized for the PG-9 threaded strain relief provided in the kit. For Wall Mounting Use the two holes in the back plate to mount the TTC-1 base unit to the wall using suitable wall fasteners. The mounting holes are 4mm diameter, separated by 85mm (center to center). The mounting screw holes are recessed into a molded well that is 7 mm in diameter. It is recommended to use a J15 metric screw with a head diameter small enough to fit into the molded well. Figure 2: Wall mounting For proper orientation, the terminal strip must be on the left, as shown in Figure 2. Mounting holes 85mm (center to center) Cable entry knockouts For DIN 1 Rail Mounting Attach the optional rail mounting clip (TTC-DRC) to the base unit and clip base unit on rail. Remove the top housing from the TTC-1. Place one of the hex nuts in the molded hex cavity in the center of the DIN rail plate. Align the DIN rail plate with the bottom of the TTC-1 base and insert one of the screws through the TTC-1 Figure 3: DIN rail mounting TTC-DRC insulating collar and the hole in the center of the base. Turn the screw to secure the base. Insert the second hex nut into the remaining molded hex cavity at the end of the hex plate and use the second screw to secure the plate. Loosen the two captive screws at least 10 full turns. You may hear a click when screw is fully released. Use a gentle rocking motion to pull the module top away from the base. Note: If the screws are not fully released the base can be damaged during this step. The screws are captive and will be retained with the module when separated from the base. ID: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Figure 4: Module dis-assembly WARNING: To avoid electrical shock all wiring must be done with the power off. WARNING: To avoid electrical shock all wiring must be done with the power off. 7 8 9 10 11 12 13 14 15 16 17 18 19 4 5 6 TROUBLE RELAY LEAK DETECTION RELAY POWER INPUT Strip all wire insulation back 3/8 inch. Push leader cable, power supply and relay contact wires through the strain reliefs as needed, see Figure 5. Wires should be connected to the terminal strip following the label on the rear cover plate of the TTC-1, see Figure 6. 1 2 3 SENSOR LEADER Figure 5: Terminal block wiring Figure 6: Typical terminal block label 2 nvent.com

Power Supply Connection Note: For proper operation of the TTC-1, use a power supply whose output is electrically isolated from the incoming AC line power and ground. One (and only one) TTC-1 can be connected to the output of one of the following suitable power supplies: a) a transformer (except an autotransformer) b) an isolated AC-to-DC switching or linear supply (use a UL Listed Class II power supply) c) an isolated DC-to-DC switching power supply (use a UL Listed Class II power supply) d) a 15 to 24 V battery Do not connect either leg of the power supply output to neutral or ground. To ensure that multiple TTC-1 modules are isolated from ground and from each other, each TTC-1 module requires a separate isolated power supply. There is no polarity requirement when using a DC power supply. Maximum wire size: 14 AWG. WARNING: To avoid electrical shock all wiring must be done with the power off. Relay Connections Trouble Relay: One relay with single pole, double throw contact. The relay is normally energized. Loss of power at the TTC-1 module causes the relay to switch to the ALARM condition (COM-NC open). Leak Detection Relay: One relay with double pole, double throw contacts. Leak detection relay latch can be disabled by removing jumper wire between terminal 18 to 19. See further discussion in the Field Adjustments and Maintenance section on page 5. Note: If relays are connected to automatic equipment, verify proper operation. Module Field Adjustments: Time Delay can be increased from immediate to approximately 2 minutes using adjustment screw on rear panel. Sensitivity can be increased or decreased from factory setting with adjustment screw on rear panel. See further discussions in the Field Adjustments and Maintenance section on page 5. Final Reassembly When all wiring connections are complete and the field adjustments have been made, carefully insert the edge of the circuit board into the terminal strip edge card connector. Using a gentle rocking motion, push the circuit board module into the base unit until it seats. Use the two captive screws on the module to secure the circuit module to the base, see Figure 7. Attach the wall label in a conspicuous place near the TTC-1. Figure 7: Module reassembly Final Check List 1. Complete a system inspection in the presence of the owner. 2. Ensure a plan showing the location of the sensor is available. 3. Check that the following information is clearly visible adjacent to the alarm module: In case of alarm instructions Location of the system map in case it is not installed adjacent to the alarm module Name and contact number of the person responsible for operating the system Supplier s contact name and address 4. Give these Installation, Operating and Maintenance Instructions to the owner. 5. Make the owner aware that it is strongly recommended to perform a systems check at regular intervals, at least every six (6) months. nvent.com 3

Operating Instructions System Operation The TTC-1 module and attached sensor cable continuously monitors for liquid contact and wire breakage. LEDs on the cover of the enclosure indicate the status of the system, see Figure 8. Relay contacts react to leak detection as well as trouble conditions: Normal Mode Indications: CABLE BREAK LED RESET LED ON (green) NORMAL (de-energized) NORMAL (energized) Figure 8: TTC-1 front panel Leak Detection Indication: ON (red) CABLE BREAK LED RESET LED ON (red) (See Note 1) ON (green) User Action: 1. Press RESET to return Leak Detection relay to NORMAL position CAUTION: Any equipment that has been automatically shut down by the Leak Detection relay may be re-activated when RESET is pushed. Cable Break Indication: CABLE BREAK LED RESET LED Power Failure Indication: CABLE BREAK LED RESET LED ALARM (energized) NORMAL (energized) ON (yellow) ON (green) NORMAL (de-energized) ALARM (de-energized) NORMAL (de-energized) ALARM (de-energized) 2. Locate the spill area, investigate the cause of the spill and take the necessary repair actions. 3. Clean up the spill area and clean and dry the cable if necessary. will turn off when cable is dried. User Action: 1. Investigate the sensor cable and leader cable for physical damage. Check connectors for damage. Make repairs or replace components as necessary. 2. CABLE BREAK LED automatically turns off when full sensor cable continuity is restored. 3. TROUBLE relay automatically returns to the NORMAL position when cable continuity is restored. User Action: 1. Investigate power wiring and connections, circuit breakers, etc. to determine cause of power loss. Make repairs as necessary to restore power to the TTC-1. 2. turns on automatically when power is restored. 3. TROUBLE relay returns to NORMAL position when power is restored. Note 1: The RESET LED is turned on when a leak is first detected. Pushing the RESET button will cause the Leak Detection relay to return to the NORMAL condition and the red LED to turn off. RESET will work regardless of whether the cable is wet or dry. 4 nvent.com

Field Adjustments and Maintenance Time Delay Adjustment The leak alarm relay can be adjusted for time delay range up to 2 minutes. The purpose of the time delay is to prevent the alarm relay from activating on short term transient conditions caused by air conditioner start-up. The factory default setting is zero delay. The adjustment screw is accessed through the rear cover plate when the TTC-1 top cover is removed from the base unit. (See Figure 9). Rotate the time delay adjustment screw in the clockwise direction to increase time delay. Sensitivity Adjustment The sensitivity adjustment refers to the size of the liquid leak which will trigger a response from the TTC-1 module. For water detection applications the factory default setting will cause the TTC-1 to respond to a puddle of tap water approximately 8 cm (3 inches) in diameter. The sensitivity adjustment screw is accessed through the rear cover plate when the TTC-1 top cover is removed from the base unit. See Figure 9. Note initial setting before changing. Sensitivity can be increased by rotating the adjustment screw in the clockwise direction and decreased by rotating the screw in the counter clockwise direction. The sensitivity control has very little effect on TT5000 or TT5001 sensors since these cables act like ON/ switches. Leak Detection Relay Latch Function The TTC-1 default setting causes the Leak Detection relay to latch in the ALARM condition when a leak is first detected. Resetting the relay to the NORMAL condition is a manual operation that occurs when the user pushes the RESET push-button. In some installations it may be desirable to have the Leak Detection relay track the sensor cable conditions. (i.e. RELAY in ALARM mode if the cable is wet and RELAY automatically reset when the cable dries). This alternative configuration causes the Leak Detection relay to track the cable condition and no user interaction is required to reset the leak relay. To enable automatic relay tracking (and defeat the latch function), remove the small jumper wire between terminal 18 and 19. See Figure 9. Periodic Maintenance and Test Recommended Interval: Perform a functional check per the following procedures at 6 month intervals. Repair or replace all damaged wiring and sensor cables. There are no field repair procedures for the TTC-1 module. If the module fails to perform the functional tests, it must be replaced. Test Procedure: 1. Normal Operation: Look for Green 2. Leak Simulation: For systems using nvent RAYCHEM TraceTek TT1000 or TT3000 sensor cable, use a TraceTek Mapping Tool or a small container of water to simulate a leak. After the time delay has expired (maximum 2.5 minutes) look for the following indications: Red on Red RESET LED Green on Leak Detection Relay in ALARM condition (Note: This may cause equipment shut down if devices are connected to the ALARM relay contacts) (C1-NC1 open, C2-NC2 open) After above conditions are observed: Press RESET Red RESET LED turns off LEAK RELAY returns to NORMAL condition. Remove simulated leak: Red goes out For TT5000 and TT5001 systems, simulate a leak condition by tightly bending and holding the sensor cable. 3. Cable Break Simulation: For any sensor system, disconnect any sensor connector in the system. Look for the following indications: Yellow CABLE BREAK LED on in ALARM condition (COM-NC open) Restoring the connection should cause the TTC-1 to return to the normal indications. Adjustment screw locations Figure 9: Location of adjustment controls nvent.com 5

Troubleshooting Guide Problem: Leak Alarm, but no leak found. Possible Cause: Cable is dirty (TT1000, TT3000) Action: Clean cable using water. Dry the cable and check TTC-1 front panel. Heavily contaminated cable may require replacement. Sensitivity can be adjusted to a lower level, but if dirt is accumulating, cleaning and/or replacement will eventually be required regardless of sensitivity setting. Problem: Leak Alarm, but no leak is found. Possible Cause: Cable is pinched (all cables) Action: Check the sensor cable for possible pinch points. nvent RAYCHEM TraceTek TT5000 and TT5001 can be tripped if tightly bent or compressed by a heavy object. TT1000 and TT3000 can be tripped by heavy pressure from a metallic object. Check the entire cable installation for pinch points and correct the condition. Problem: Leak Alarm, but no leak is found. Possible Cause: Cable is exposed to occasional water (TT1000, TT3000) Action: Increase time delay and/or reposition cable further from the intermittent source of water. It is best to keep the sensor cable at least 3 feet from the outflow of any air conditioner units. Problem: Leak Alarm, but no leak is found. Possible Cause: Cable is in contact with sharp metal edges (TT1000, TT3000) Action: Check the sensor cable for possible points of contact with sharp edges such as the edges of drip pans or the pipe threads on adjustable floor supports. Reposition the cable as necessary or insert a small piece of insulating material to prevent the cable from making contact with the metal edge. Problem: CABLE BREAK indication but cable appears to be intact. Possible Cause: Loose connections at terminal block. Action: Check all terminal block screws for tightness. To test the module by itself, use two small pieces of wire to form temporary jumpers from red to green and yellow to black at the sensor cable terminal block. This simulates a very short piece of sensor cable and the yellow CABLE BREAK LED should go off. If the TTC-1 cannot pass the jumper wire test, it may require replacement. Problem: PLC or other host system detects a fault when the TTC-1 is operating in NORMAL mode. Possible Cause: Loose connections at terminal block or broken wires between TTC-1 and PLC. Action: Check all terminal block screws for tightness. Many installations use a normally closed contact to indicate a normal condition at the TTC-1. If the wiring between the TTC-1 and the PLC is loose or open, then the host system will read the open circuit as a fault regardless of the TTC-1 status. Note: Cable Cleaning TraceTek 1000 and TT3000 use a solid core polymer construction and can usually be easily cleaned with tap water. In extreme cases or when large amounts of cable are contaminated, these cables can be washed in an ordinary dishwasher. Try a water only (no detergent) cycle first and avoid the heated dry cycle. When placing the cable in the dishwasher be sure to tightly connect the male connector on one end to the female connector on the other in order to keep water out of the connectors. TT5000 and TT5001 cannot be cleaned without special equipment. These cables normally require replacement after exposure to fuel or solvent. North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com Europe, Middle East, Africa Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nvent.com Asia Pacific Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nvent.com Latin America Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nvent.com nvent.com 2018 nvent. All nvent marks and logos are owned or licensed by nvent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nvent reserves the right to change specifications without notice. RaychemTraceTek-IM-H53813-TTC1-EN-1805