Reversible Chillers and Heat Pumps - LEW SERIES kw

Similar documents
LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

LEP kw. Indoor monobloc water-water unit. Total heat recovery multi-purpose units LEP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Galletti Water chillers and heat pumps catalogue

CRIMSON & CRIMSON MAX

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

kw COOLING kw HEATING

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Water chillers water/water type SIGMA Technical information manual

LZT High efficiency air to water heat pumps with E.V.I. compressors

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Blue Box Epsilon Echos +

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

TECHNICAL MANUAL FOR AIR-COOLED CONDENSING UNITS MTE

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

LZA High efficiency air to water heat pumps with HP compressor

WZH Ground source heat pumps

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

Aquaflair TRAC-TRAF-TRAH

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

ARV.

HYDRONIC RESIDENTIAL

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

Construction details: Structure and base in hot dip galvanised sheet steel with epoxy pain finish (RAL 9002)

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti.

NECS-W. Climaveneta Technical Bulletin NECS_W 0152_0612_200907_GB. Water-cooled liquid chillers and water-to-water heat pumps ,4-186 kw

ELFOEnergy Duct Inverter


WDH WDH. Ground source heat pumps OTHER VERSIONS ACCESSORIES

PRODUCT GUIDE

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

30HXC Nominal cooling capacity kw

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

WHA WHA. Ground source heat pumps OTHER VERSIONS ACCESSORIES

Air cooled industrial chillers

H4T R410A. refrigerant

WHA WHA. Ground source water to water heat pumps A ++ A ++ Versions

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

TECHNICAL MANUAL MCP. Multipurpose - total heat recovery reversible heat pumps. 7 kw - 41 kw

ARS. 1

TCHE-THHE TCEE

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

LZT High efficiency air to water heat pumps with E.V.I. compressors

Technical Catalogue. Multi-Scroll Air-Cooled Liquid Chillers. Nominal cooling capacity: kw 50 Hz

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

TCHE-THHE TCEE

NRP MULTIPURPOSE HEAT PUMPS 2 AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Conditioning your ambient, maximising your comfort.

21,8 222 kw COOLING 25,2 236 kw HEATING

WSK WSK. Water to water chillers and heat pumps VERSIONS ACCESSORIES

1

Modular Air-cooled Chillers

Air-to-water scroll chillers

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

LZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES

HT V2 HT Split

Be sustainable while protecting your business

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

44,9 202,0 kw. technicalcatalogue

SyScroll 40 to 75 Air NEW

HIWARM COMPACT kw

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

TECHNICAL MANUAL FOR CHILLERS AND HEAT PUMPS MPE

Transcription:

LEW Technical manual GB Reversible Chillers and Heat Pumps - LEW SERIES 40-480 kw

Page 2 of 56

Contents CONTENTS... 3 1 GENERAL DESCRIPTION... 5 1.1 LEW UNITS... 5 1.1.1 PRODUCT CONFIGURATIONS... 5 1.1.2 CONFIGURATION AND ACCESSORIES... 6 1.1.3 FIELD OF APPLICATION... 7 1.1.4 PRODUCT INNOVATION... 10 1.2 STRUCTURE... 10 1.3 COOLING CIRCUIT... 10 1.3.1 COMPRESSORS... 11 1.3.2 HEAT EXCHANGERS... 11 1.3.3 DE-SUPERHEATER FOR PARTIAL HEAT RECOVERY (OPTIONAL)... 12 1.3.4 UTILITY AND DISSIPATION SIDE CYCLE INVERSION VALVES (OPTIONAL)... 12 1.3.5 ELECTRONICALLY CONTROLLED ELECTRIC EXPANSION VALVE... 13 1.3.6 OTHER COOLING COMPONENTS... 14 1.4 ELECTRIC PANEL... 18 1.4.1 CONTROL MICROPROCESSOR... 18 2 MAIN UNITS TECHNICAL DATA... 19 2.1 PERFORMANCE OF LEW C, D, H, W HEAT PUMP UNITS... 25 2.2 NOISE EMISSION... 28 2.3 OVERALL DIMENSIONS AND WEIGHT OF THE MAIN UNITS... 28 2.4 OVERALL DRAWINGS OF THE MAIN UNITS... 30 3 TECHNICAL DATA OF OPTIONAL HYDRONIC MODULES... 39 3.1 CHARACTERISTIC CURVES OF THE HYDRAULIC PUMPS ASSOCIATED TO THE UNITS... 39 3.2 OVERALL DIMENSIONS AND WEIGHT OF OPTIONAL HYDRONIC MODULES... 45 3.3 OVERALL DRAWINGS OF OPTIONAL HYDRONIC MODULES... 46 4 INSTALLATION... 50 4.1 INSTALLATION CLEARANCE REQUIREMENTS... 50 4.2 VOLUME OF WATER IN THE SYSTEM... 50 5 OPERATING LIMITS... 52 5.1 WORKING LIMITS... 53 5.2 WATER FLOW TO EVAPORATOR... 53 6 CALIBRATION OF CONTROL DEVICES... 54 Page 3 of 56

Declaration of conformity The declaration of conformity is attached to each machine Page 4 of 56

1 General description 1.1 LEW units LEW reversible water chillers and heat pumps are air or process fluid conditioning units, designed for both domestic and industrial use and in operation 24 hours a day. They cover a thermal output range from 40 to 429 kw, guaranteeing a high level thermodynamic performance and a wide range of configuration possibilities, both in accessories and cooling circuit. LEW machines have been built in a fully faired framework to make the assembly extremely silent. They can therefore be installed in open environments without needing to be closed off. The all new new rounded off shape enhances their appearance. The exclusive use of R410A refrigerant and of high quality components in the chiller, hydraulic and electrical parts makes the LEW units state of the art chillers in terms of efficiency, reliability and emitted sound output. 1.1.1 Product configurations The series of LEW models consists in a wide range of products, meeting all system needs: LEW C water chillers cold water only LEW D water chillers cold water only (interlocked by Dry Cooler or Evaporative turret) LEW H water heat pumps chiller side reversible water LEW W water water only heating heat pumps All the above mentioned versions are available in sizes referred to in the table below. The sizes of the LEW units are expressed in the X coordinates of the table in terms of rated cooling capacity [kw], obtained in conditions with chilled water produced at 7 C and combined with the evaporative turret with dissipation circuit water at 29 inlet and 35 outlet. Table I Table summarising the range of LEW products by size and Efficiency Pack: Sizes: 040 050 060 070 080 090 110 130 140 160 180 200 210 240 280 310 340 370 420 480 Efficiency Pack 1 Efficiency Pack 2 Efficiency Pack 3 Efficiency Pack 4 F1 F1 F1 F1 F1 F1 F2 F2 F2 F2 F2 F1 F1 F1 F1 F1 F1 F2 F2 F2 F2 F2 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 The first column of Table I shows the available "Efficiency Packs". These determine the configuration of the cooling circuit. For further details see paragraph 1.3 Cooling circuit. For example, the size LEW 2 090 develops a 90 kw chiller output and is implemented with Efficiency Pack 2 (two compressors, one cooling circuit). The dimensions of the "Frames" of the units are listed in the cells, by means of reference symbols F1 F2 F3 (with increasing dimensions); all the information concerning the weight of the machines and the dimensions corresponding to each frame is available in paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set up or the "L" soundproof set up, covering the compressor and outer panelling with soundproof material. The LEW units are identified with the following symbol: LEW 072 CS 1 2 3 4 5 Page 5 of 56

1 Identification symbol of Hiref Model (e.g.: LEW unit) 2 Unit sizes expressed in rated chilling output x10 [kw] (e.g.: 70 kw) 3 Efficiency Pack: cooling circuit and compressor layout (e.g.: Efficiency Pack 2) 4 Machine version (e.g.: C, Chiller) 5 Machine execution (e.g.: S soundproofing not available) 1.1.2 Configuration and accessories List of standard features R410A refrigerant Scroll compressors Galvanised and painted sheet-metal structure Flow switch included Brazed plate heat exchangers Second set point on utility side that can be activated from an external input List of options Version CMP-1 Chiller condensed with well or mains water C Chiller condensed with water from a dry-cooler or evaporative tower D Reversible heat pump H Non-reversible heat pump (hot only) W Execution CMP0 standard S low-noise L 1 - Electric power supply CMP1 400/3/50 + N 0 400/3/50 + Motor circuit breakers 2 2 - control microprocessor and expansion device CMP2 base + electronic expansion valve 0 base + mechanical expansion valve A programmable (LCD display 8x22) + electronic expansion valve B programmable (LCD display 8x22) + mechanical expansion valve C 3 - Partial heat recovery (mandatory condensation control) CMP3 absent 0 de-superheater (40% Pf recovered under normal circumstances) D Not available if Field 4 = 0 4 - Flow rate modulation on source side CMP4 absent 0 condens. control with 0-10V modulated output signal P Not available if Field 2 = 0,A 5 - Flow rate modulation on utility circuit CMP5 absent 0 6 - Remote communication CMP6 absent 0 RS485 serial board (Carel or Modbus protocol) 1 Serial board Lonworks 2 Not available if Field 2 = 0,A GSM modem kit 3 Not available if Field 2 = 0,A Ethernet board (SNMP or BACNET protocol) + clock board 4 Not available if Field 2 = 0,A Ethernet board + clock board + supervision software 5 Not available if Field 2 = 0,A 7 - Vibration isolation CMP7 absent 0 Rubber anti-vibration mounts at unit base G Spring anti-vibration mounts at unit base M 8 - Package CMP8 standard 0 Page 6 of 56

wooden cage 1 wooden cage 2 9 - Remote control CMP9 absent 0 Simplified remote control panel 1 Remote display for standard microprocessor 2 Not available if Field 2 = B,C Remote display for programmable microprocessor 3 Not available if Field 2 = 0,A 10 - External insulated hydraulic module separated from the main unit CMP10 No hydraulic module 0 LP utility pump + LP dissipation 1 LP utility pump + modulating LP dissipation 2 Not available if Field 2 = 0,A LP utility pump + HP dissipation 3 LP utility pump + modulating HP dissipation 4 Not available if Field 2 = 0,A HP utility pump + LP dissipation 5 HP utility pump + modulating LP dissipation 6 Not available if Field 2 = 0,A HP utility pump + HP dissipation 7 HP utility pump + modulating HP dissipation 8 Not available if Field 2 = 0,A List of accessories Shunt condensers A Soft-starter kit B Service kit (probe kit for quick diagnostics) C Not available if Field 2 = 0,A Clock board D Not available if Field 2 = 0,A ON-OFF status of compressors E Remote contact for (step-based= power limitation F Not available if Field 2 = 0,A Configurable digital alarms board G Not available if Field 2 = 0,A Pressure gauges H Not available if Field 2 = 0,A G - Four Vic-Taulic joints for quick water IN-OUT connection I Filter cut-off kit (solenoid and cock on liquid line) L Outdoor temperature sensor for set-point compensation M Not available if Field 2 = 0,A Dissipation side water temp. probe for Version = "H" or "W" N Not available if Field 10 = 1.2 1.1.3 Field of application LEW units are designed for cooling heating water and solutions containing up to 30% glycol (percentage by weight) in civil, industrial and technological air conditioning systems. The units cannot operate outdoors, as the metalwork provides an IP43 insulation. Please contact the technical office for these applications. LEW series units must be used within the operating limits shown in this document or the warranty required by the sales contract will be voided. LEW multifunction machines have 4 water connections associated with two different water circuits for 2 pipe systems: Circuit 1, production of cold or hot water for utility; Circuit 2, production of hot or cold water for dissipation in opposition to the utility; Accordingly, the multifunction units have 2 heat exchangers: Plate heat exchanger 1 with both evaporation and condensation function, intended for the utility circuit; Plate heat exchanger 2 with both evaporation and condensation function, intended for the dissipation circuit; Cooling LEW machine: view of the water connections and of the thermodynamic circuit For the correct direction of the connections, always refer to the dimensional drawing attached with the documentation. Page 7 of 56

DISSIPATION UTILITY LEW C machines are designed for cold only production: in the utility circuit only the production of chilled water is envisaged. The LEW H machines are reversible heat pumps: in the utility circuit hot water and chilled water can be produced alternatively. The following points briefly illustrate the operating functions of the LEW C, D, H, W units: Chilling LEW C, D, H units in Chiller mode cool the water to cool down the environment on the utility side, thereby dissipating condensation heat with the water cooled by the dissipation heat exchanger. Heating LEW H, W units in Heat Pump mode heat the water in the condenser to heat the utility side, thereby dissipating the evaporation cooling capacity by means of the water which is heated in the dissipation heat exchanger. In other words, a certain amount of heat is drawn from a thermal source and is then transferred to the utility after it has reached a sufficient thermal level that is suitable for its needs. Page 8 of 56

Air conditioning applications often need to be able to dispose of heat to heat up domestic hot water or for post heating control in air treatment facilities where an autonomous Temperature and humidity control will be implemented. The heat required can be drawn from the condensing section of the thermodynamic unit, which is at a higher temperature. If only part of the heat is drawn, a de superheater sends gas sensitive heat to the delivery pipe towards the third thermal source at a higher temperature. Upon specific demand, all cold only units of the LEW series can be equipped with a de superheater for partial heat recovery. The available thermal output that can be used for domestic hot water, for example, depends on the unit's operating conditions. Layout of partial heat recovery circuit Page 9 of 56

1.1.4 Product innovation LEW units provide excellent thermodynamic performance and maximum flexibility of use thanks to constant product research. The joint application of scroll compressors, advanced control systems and R410A refrigerant gas achieves compact circuits and high COPs. The possibility of keeping the evaporator on the inside allows you not to add glycol to the water in the system, with clear advantages in terms of thermodynamic performance, preservation from corrosion and respect for the environment. It also makes it possible for all the components requiring maintenance to be installed in an easily accessible space. Chiller units can be applied even when no dissipation source other than air is available: a water Dry Cooler provides thermal exchange with the atmosphere while maintaining a compact sized circuit. For large buildings, air conditioning can be implemented as the floors/zones are sold or rented by installing a LEW unit for each floor in a small size technical room, thus spreading the investment over time. The overall dimensions of the units (less than 90 cm depth in the higher output sizes) make them easy to be installed since they fit through any door. The main innovations which this product presents are summarised in the following list: Option of using water without glycol in the utility circuit Heat pump mode with chiller side cycle inversion Option of even heat pump versions using condensation control Electronically controlled electric expansion valve High COP (Coefficient of performance) of thermodynamic cycle Reduced refrigerant load Option of applying chiller mode even when air is used as dissipation source It occupies less space on the floor plan (specific powers up to 153 kw/m 2 ) Innovative aesthetic features and full safety since units are completely closed No noise on the outside, less noise on the inside due to dual soundproofing in low noise versions. 1.2 Structure All LEW series units have the load bearing base and panelling in galvanised sheet metal painted with polyester powders and polymerised in the oven at 180 C. The unit has an attractive design and when closed all the components are inaccessible. This, along with the extensive use of soundproofing material inside the compartment and around the compressors (available for the low noise version), reduces sound to exceptionally low levels (Lp < 67 db A @1 metre for bigger sizes). The hydraulic/chiller connections are envisioned on the right side, when looking at the electrical control board, to reduce the technical space required for installation. All the panels are removable (except for the one on the right, upon which all the hydraulic connections are fitted) making the unit fully accessible even though routine maintenance only needs accessing from the front. 1.3 Cooling circuit The cooling circuit is manufactured in our factory, with top brand components and operators trained, according to Directive 97/23, on all the brazing operations. The range can be configured in the cooling circuit mode (Efficiency Pack) which, depending on the size, can be a dual compressor on a double circuit (Efficiency Pack 1) for a highly redundant system, dual compressor (tandem) on single circuit (Efficiency Pack 2) for greater efficiency in partial loads, three compressors (trio) on single circuit (Efficiency Pack 3) combining economical implementation and partial load efficiency and four compressors (two tandems) on a double circuit (Efficiency Pack 4) for a system which is both redundant and efficient with the reduced load. Page 10 of 56

Table II List and graphical representation of the layout of the components in four Efficiency Packs: Efficiency Pack ONE: Efficiency Pack TWO: Efficiency Pack THREE: Efficiency Pack FOUR: Solutions with more than one circuit provide the utmost reliability thanks to redundancy, while those with more than one compressor on a circuit provide partial loads with ideal efficiency, also thanks to increased heat exchange surfaces. 1.3.1 Compressors Only top international brand Scroll compressors are used on LEW units. Scroll compressors, up to a power output of 182 kw for single circuit, are the best solution in terms of reliability and efficiency. They also provide the lowest amount of sound emissions. Process optimisation, along with a carefully selected intrinsic volumetric compression ratio (RVI), clearly improves the isentropic compression performance and reduces energy losses. The use of a scroll compressor allows low viscosity oils to be used. This, in comparison to higher viscosity oils, reduces thermal resistance at the evaporator. It also increases the evaporation temperature by more than 1.5 C (EER increases by more than 5.5%) compared to other solutions. Compressor motors are protected against overheating, overloads and high delivery gas temperatures. They are mounted on rubber anti vibration mounts, complete with oil charge and inserted in a soundproof compartment with sound absorbing material. Also complete with automatic oil heater to prevent the oil from being diluted by the refrigerant when the compressor stops. NOTE: Scroll compressors, like all air tight compressors, are classified as pressurised containers. The low pressure section, referred to by the PS on the data plate, complies with PED CE 97/23. 1.3.2 Heat exchangers Only brazed plate heat exchangers are used, made of austenitic stainless steel AISI 316, with AISI 316L connections. These feature a reduced carbon content that favours brazing operations. The brazed plate heat exchanger represents the state of the art in terms of thermal exchange efficiency and allows a strong reduction of the refrigerant load compared to standard solutions. The high level of turbulence generated by internal plate corrugation, along with plate smoothness, makes it difficult for dirt to accumulate or for limescale to build up on the condenser circuit. These heat exchangers also make it possible to use R410A fluid which, thanks to the high level thermal conductivity of its liquid phase and to its azeotropic behaviour, enhances thermal exchange during evaporation. The performances are improved over other methane derivative fluids of the HFC group. Page 11 of 56

NOTE: due to thermal insulation the data plate (in compliance with PED CE 97/23) is not legible. However, the serial number of the heat exchanger and the declaration of conformity are both recorded during production and are an integral part of Hiref's archive. 1.3.3 De-superheater for partial heat recovery (optional) The option of partial heat recovery is implemented with a braze welded plate heat exchanger placed in series on the finned pack condenser and its size limits pressure drops on the refrigerant side to a minimum. All machines configured with heat recovery use as per standard modulating condensation control. To prevent a lack of balance in the cooling circuit, if the water temperature is too low when the recovery starts, the hydraulic recovery circuit is implemented as indicated in the following figure: a low water temperature at recovery would cause a drop in the condensation temperature and therefore an insufficient pressure jump on the expansion valve with the ensuing risk of the safety devices being triggered. TANK DIVERTER RECIRCULAT ION PUMP HEAT The bulb of the 3 way mixer valve is placed at the de superheater exchanger inlet, which by mixing the hot water produced with colder water from the tank allows you to limit the time needed for the system to reach full operating capacity to a few moments. A buffer tank must be placed between the unit and the utility since the demand for hot water and its availability are not simultaneous, because it needs the compressors to be running. It should be pointed out that the heat recovery output is linked to the dispensed cooling output and that, therefore, in partial load situations it is also reduced just the same; this aspect must be taken into consideration for the dimensions of the buffer tank. The partial heat recovery option is supplied only with the de superheater exchanger. The other components of the circuit laid out in the previous figure are not included in the supply. 1.3.4 Utility and dissipation side cycle inversion valves (optional) When LEW H reversible chillers switch from chiller to heat pump, and vice versa, they perform two cycle inversions: one on the coolant circuit and one on the water circuit. The inversion valve of the water side cycle switches from position A to position B and vice versa by means of an electrical driver without changing the direction of travel for the outside utilities. This allows you to invert the direction of the flow in the heat exchangers, keeping them against the flow in relation to the refrigerant fluid in every operating mode. The water side cycle inversion valve is an optional component. Page 12 of 56

Refrigerant side cycle inversion valve Heat transfer fluid side cycle inversion valve 1.3.5 Electronically controlled electric expansion valve The electronically controlled valve with external equalisation and built in MOP function is managed by the software and therefore makes cooling circuit operation very efficient, stabilising and decreasing the power absorbed by the system when a sudden thermal load variation occurs. The shutter in the central part of the valve can always slide vertically with an ample stroke allowing variation of the degree of opening of the orifice of the fluid passage. Using this valve reduces compressor energy consumption when the surrounding conditions bring the pressure difference between the evaporator and the air conditioner below 5 bar, thus improving performance. Page 13 of 56

1.3.6 Other cooling components Molecular sieve filter dryer Sight glass with humidity indicator One way valves (only reversible heat pump) Liquid receiver marked in compliance with EC Directive 97/23 PED (only reversible heat pumps or units with remote condenser) High and low pressure switches Schrader valves for control and/or maintenance Page 14 of 56

Diagram of the dual circuit cold only version (please note: this is a standard layout, refer to the layout enclosed with the unit). To consult the layouts, please refer to the symbols in the following table. Page 15 of 56

Diagram of the dual circuit reversible heat pump version (please note: this is a standard layout, refer to the layout enclosed with the unit). Page 16 of 56

Reference table for numbering used in layouts Page 17 of 56

1.4 Electric panel The electric panel is built and wired in accordance with standard EN 60204 1. The electric panel is accessed from the front of the machine. Before it can be accessed, the unit must be disconnected from the power supply using the main switch, which functions as a door lock. All the remote controls are implemented with low voltage signals at 24 V, powered by an isolation transformer positioned inside the control board. All the control boards have an air circulation system with auxiliary fans. The position of the main switch makes wiring operations in the work site easier. This avoids several difficult operations as well as having to twist the power cords. All the utilities are protected against surges and short circuits. The circuit breaker set up can be configured for any load (optional). Thermal protection, however, is carried out by thermistor chains. These are set in the windings of each electric motor and are controlled by onboard electronics. All machines are standard equipped with a phase sequence relay which inhibits compressor operation if the phase sequence is not carried out: only one direction of rotation is possible for scroll compressors, as well as for the screw and Rotary compressors. The unit is rated IP43 which makes it suitable for outdoor installation. The control board with the open panel maintains an IP20 rating. Inside the electrical control board of the Basic control there are two manual selectors to enable remote switching on off, seasonal changeover (only heat pumps) and to select local or remote control: remote consents are implemented by very low voltage contacts placed on the terminal board. 1.4.1 Control microprocessor LEW series units have two different microprocessor control levels: Basic Carel µchiller Advanced Carel series pco The latter, in addition to the functions described below, can customise the software to meet all system requests. These include cascade management of the units with step control or cascade logic. The microprocessor on board the unit controls the various operating parameters with an electric panel keypad; Compressor connection/disconnection to maintain the set point of the chiller inlet water T; Alarm management: High / low pressure; Antifreeze / Flow switch; Pump alarm Alarm signals Display of operating parameters Evaporator anti freeze protection Control of maximum number of compressor starts RS232, RS485 serial output control (optional) Incorrect phase sequence (not viewed on display, prevents the compressor from starting) As for remote communication, the controls can be connected to advanced BMS systems. The HSD (HiRef Software Department) structure is capable of assisting customers in integration operations. System interconnectivity capabilities are summarised below: Available serial ports RS232 RS485 Ethernet ( HiWeb board) GSM Modem: with prepaid card and relative antenna on board the machine for autonomous two way control of alarms and/or set point variations Protocols Carel [Built In] Modbus [Built In with Advanced controls] Modbus [With external gateway with Basic controls] LonWorks [Dedicated serial board to be requested when ordering the machine] BACnet [With external gateway] TCP IP [With external gateway] TREND [Dedicated serial board to be requested when ordering the machine] (ref. Microprocessor control manual for further details) Page 18 of 56

2 Main units technical data The following chapter provides the technical data for the LEW unit. Performance values are accurately reported and can be interpolated to know specific operating conditions. Table I Technical data of LEW chillers in standard operating conditions RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 15/30 C Efficiency pack 1 2 1 2 1 2 1 2 1 2 LEW CS / CL 41 42 51 52 61 62 71 72 81 82 Cooling capacity kw 51.9 51.1 60.2 60.1 69.1 69.2 77.9 77.9 89.1 89.1 Rated absorbed power kw 9.3 8.7 11.2 11.2 12.4 12.4 14.3 14.3 15.9 15.9 Evaporator side pressure drops kpa 38 37 51 51 40 40 50 50 39 39 Evaporator side flow rate l/h 8933 8791 10360 10344 11888 11897 13406 15326 15330 15326 Condenser pressure drops kpa 7 7 9 9 12 12 15 15 18 18 Condenser side flow rate l/h 3483 3402 4062 4057 4637 4639 5246 5972 5974 5972 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2/2 2/1 2/2 2/1 2/2 2/1 2/2 2/1 2/2 2/1 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1594 1594 Length mm 1174 1174 1174 1174 1174 1174 1174 1174 1174 1174 Depth mm 772 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 30.0 30.0 37.0 37.0 40.0 40.0 46.0 46.0 50.0 50.0 Booster current (LRA) A 111.0 111.0 156.0 156.0 157.0 157.0 164.0 164.0 176.0 176.0 LRA with soft starter kit A 73.0 73.0 83.0 83.0 102.0 102.0 107.0 107.0 117.0 117.0 EER 5.75 6.05 5.46 5.45 5.72 5.73 5.54 5.54 5.76 5.76 Refrigerant load kg 6 5 6 5 6 6 7 7 7 7 RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 15/30 C Efficiency pack 1 2 1 2 1 2 1 2 4 LEW CS / CL 91 92 111 112 131 132 141 142 144 Cooling capacity kw 99.3 99.3 118.9 118.9 135.6 135.5 157.2 157.3 156.9 Rated absorbed power kw 18.0 18.0 21.3 21.3 24.6 24.6 27.9 27.9 28.8 Evaporator side pressure drops kpa 48 48 39 39 50 50 47 47 47 Evaporator side flow rate l/h 17075 17077 20448 20454 23326 23309 27039 27061 26983 Condenser pressure drops kpa 22 22 30 30 38 38 19 19 19 Condenser side flow rate l/h 6674 6675 7978 7980 9118 9112 10532 10538 10563 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1854 Length mm 1174 1174 1674 1674 1674 1674 1674 1674 2374 Depth mm 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 61.0 61.0 70.0 71.0 79.0 79.0 91.0 91.0 92.0 Booster current (LRA) A 203.0 203.0 238.0 275.0 244.0 244.0 289.0 289.0 197.0 LRA with soft starter kit A 137.0 137.0 176.0 210.0 182.0 182.0 224.0 224.0 140.0 EER 5.60 5.60 5.71 5.71 5.58 5.58 5.73 5.74 5.54 Refrigerant load kg 8 8 12 12 13 12 15 13 15 Page 19 of 56

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 15/30 C Efficiency pack 1 2 4 1 2 3 4 4 LEW CS / CL 161 162 164 181 182 184 204 214 Cooling capacity kw 174.9 175.1 176.2 204.5 204.8 198.9 219.1 235.1 Rated absorbed power kw 32.1 32.1 31.9 37.9 37.9 36.4 39.3 42.7 Evaporator side pressure drops kpa 51 51 52 54 54 51 51 57 Evaporator side flow rate l/h 30076 30113 30302 35180 35218 34211 37680 40444 Condenser pressure drops kpa 23 23 23 30 31 29 28 33 Condenser side flow rate l/h 11771 11783 11838 13788 13803 13386 14703 15805 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 4 / 2 2 / 2 2 / 1 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1854 1594 1594 1854 1854 1854 Length mm 1674 1674 2374 1674 1674 2374 2374 2374 Depth mm 772 772 772 772 772 877 877 877 Maximum current (FLA) A 102.0 102.0 100.0 116.0 116.0 122.0 132.0 142.0 Booster current (LRA) A 298.0 298.0 211.0 361.0 361.0 250.0 321.0 328.0 LRA with soft starter kit A 233.0 233.0 152.0 278.0 278.0 184.0 256.0 263.0 EER 5.53 5.54 5.59 5.46 5.47 5.54 5.64 5.55 Refrigerant load kg 15 15 15 16 15 22 22 22 RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 15/30 C Efficiency pack 3 4 3 4 4 4 4 4 4 LEW CS / CL 243 244 283 284 314 344 374 424 484 Cooling capacity kw 267.9 279.0 313.0 316.4 349.7 377.4 410.6 453.5 520.7 Rated absorbed power kw 47.8 47.9 56.4 56.3 64.7 70.4 74.5 81.6 92.5 Evaporator side pressure drops kpa 51 55 40 41 49 56 54 56 53 Evaporator side flow rate l/h 46080 47979 53828 54419 60144 64905 70623 78003 89412 Condenser pressure drops kpa 21 23 28 28 35 36 33 33 39 Condenser side flow rate l/h 17961 18601 21017 21207 23571 25469 27652 30446 35016 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 3 / 1 4 / 2 3 / 1 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 3 3 3 3 3 3 3 Height mm 1854 1854 1854 1854 1854 1854 1854 1854 1854 Length mm 2374 2374 2374 2374 2374 2374 2374 2374 2374 Depth mm 877 877 877 877 877 877 877 877 877 Maximum current (FLA) A 153.0 159.0 174.0 182.0 204.0 218.0 232.0 281.0 302.0 Booster current (LRA) A 336.0 301.0 401.0 355.0 374.0 437.0 442.0 490.0 525.0 LRA with soft starter kit A 271.0 239.0 318.0 290.0 309.0 354.0 359.0 420.0 454.0 EER 5.68 5.86 5.68 5.75 5.49 5.41 5.57 5.60 5.63 Refrigerant load kg 21 30 28 35 35 35 40 40 40 Page 20 of 56

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 40/45 C 30% glyc. Efficiency pack 1 2 1 2 1 2 1 2 1 2 LEW DS / DL 41 42 51 52 61 62 71 72 81 82 Cooling capacity kw 43.06 43.06 50.6 50.6 57.9 57.8 65.7 65.8 75.5 75.5 Rated absorbed power kw 12.8 12.8 15.2 15.2 16.8 16.8 19.5 19.5 21.5 21.5 Evaporator side pressure drops kpa 27 27 37 37 30 30 37 37 29 29 Evaporator side flow rate l/h 7407 7311 8700 8702 9953 9946 11306 11316 12982 12970 Condenser pressure drops kpa 51 51 71 71 55 55 71 71 53 53 Condenser side flow rate l/h 10871 10650 12807 12811 14541 14534 16582 16595 18877 18865 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1594 1594 Length mm 1174 1174 1174 1174 1174 1174 1174 1174 1174 1174 Depth mm 772 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 30.0 30.0 37.0 37.0 40.0 40.0 46.0 46.0 50.0 50.0 Booster current (LRA) A 111.0 111.0 156.0 156.0 157.0 157.0 164.0 164.0 176.0 176.0 LRA with soft starter kit A 73.0 73.0 83.0 83.0 102.0 102.0 107.0 107.0 117.0 117.0 EER 3.36 3.36 3.33 3.33 3.45 3.44 3.37 3.37 3.51 3.51 ESEER 5.61 6.04 5.39 5.78 5.73 6.11 5.59 6.01 5.89 6.25 Refrigerant load kg 4 4 4 5 5 5 5 6 7 7 RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 40/45 C 30% glyc. Efficiency pack 1 2 1 2 1 2 1 2 4 LEW DS / DL 91 92 111 112 131 132 141 142 144 Cooling capacity kw 83.7 83.8 101.5 101.4 115.3 115.5 132.8 132.9 133.5 Rated absorbed power kw 24.6 24.6 28.7 28.7 33.4 33.4 38.1 38.1 38.7 Evaporator side pressure drops kpa 35 35 30 30 37 37 35 35 35 Evaporator side flow rate l/h 14400 14421 17451 17448 19833 19864 22848 22867 22957 Condenser pressure drops kpa 67 67 55 55 71 71 65 65 67 Condenser side flow rate l/h 21078 21098 25347 25338 28945 28973 33277 33292 33520 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1854 Length mm 1174 1174 1674 1674 1674 1674 1674 1674 2374 Depth mm 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 61.0 61.0 70.0 71.0 79.0 79.0 91.0 91.0 92.0 Booster current (LRA) A 203.0 203.0 238.0 275.0 244.0 244.0 289.0 289.0 197.0 LRA with soft starter kit A 137.0 137.0 176.0 210.0 182.0 182.0 224.0 224.0 140.0 EER 3.40 3.41 3.54 3.53 3.45 3.46 3.49 3.49 3.45 ESEER 5.81 6.25 6.05 6.48 6.00 6.43 5.90 6.17 6.09 Refrigerant load kg 7 7 13 12 13 12 15 13 15 Page 21 of 56

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 40/45 C 30% glyc. Efficiency pack 1 2 4 1 2 3 4 4 LEW DS / DL 161 162 164 181 182 184 204 214 Cooling capacity kw 149.4 149.5 150 175 174.9 169.6 187 201.2 Rated absorbed power kw 42.6 42.6 75.1 50 50 48.6 52.7 57.3 Evaporator side pressure drops kpa 38 38 38 40 40 38 38 43 Evaporator side flow rate l/h 25700 25712 25806 30104 30078 29178 32165 34601 Condenser pressure drops kpa 57 57 59 64 64 60 60 70 Condenser side flow rate l/h 37388 37403 37539 43812 43775 42476 46666 50309 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 4 / 2 2 / 2 2 / 1 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1854 1594 1594 1854 1854 1854 Length mm 1674 1674 2374 1674 1674 2374 2374 2374 Depth mm 772 772 772 772 772 877 877 877 Maximum current (FLA) A 102.0 102.0 100.0 116.0 116.0 122.0 132.0 142.0 Booster current (LRA) A 298.0 298.0 211.0 361.0 361.0 250.0 321.0 328.0 LRA with soft starter kit A 233.0 233.0 152.0 278.0 278.0 184.0 256.0 263.0 EER 3.51 3.51 2.00 3.50 3.50 3.49 3.55 3.51 ESEER 5.80 6.17 6.24 5.84 6.29 6.33 6.46 6.44 Refrigerant load kg 15 13 15 16 15 22 24 27 RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7 C; 40/45 C 30% glyc. Efficiency pack 3 4 3 4 4 4 4 4 4 LEW DS / DL 243 244 283 284 314 344 374 424 484 Cooling capacity kw 231.8 240.2 266.2 269.4 298.3 321.4 349.1 386.7 442.05 Rated absorbed power kw 63.6 65.6 75.2 75.9 86.3 93.3 100.4 109.2 126.57 Evaporator side pressure drops kpa 23 24 29 31 37 42 40 42 39 Evaporator side flow rate l/h 39864 41306 45790 46344 51312 55284 60038 66514 75914 Condenser pressure drops kpa 42 45 55 56 70 66 65 63 72 Condenser side flow rate l/h 57517 59548 66463 67235 74861 80719 87499 96550 105646 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 3 / 1 4 / 2 3 / 1 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 3 3 3 3 3 3 3 Height mm 1854 1854 1854 1854 1854 1854 1854 1854 1854 Length mm 2374 2374 2374 2374 2374 2374 2374 2374 2374 Depth mm 877 877 877 877 877 877 877 877 877 Maximum current (FLA) A 153.0 159.0 174.0 182.0 204.0 218.0 232.0 281.0 302.0 Booster current (LRA) A 336.0 301.0 401.0 355.0 374.0 437.0 442.0 490.0 525.0 LRA with soft starter kit A 271.0 239.0 318.0 290.0 309.0 354.0 359.0 420.0 454.0 EER 3.64 3.66 3.54 3.55 3.46 3.44 3.48 3.54 3.22 ESEER 6.37 6.62 6.34 6.21 6.15 6.13 6.20 6.45 6.56 Refrigerant load kg 28 30 28 31 31 31 31 31 31 Page 22 of 56

Table II Technical data of LEW heat pumps in standard operating conditions RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10 C; 40/45 C Efficiency pack 1 2 1 2 1 2 1 2 1 2 LEW HS / HL LEW WS / WL 41 42 51 52 61 62 71 72 81 82 Cooling capacity kw 43.31 42.7 50.85 50.86 58.19 58.13 66.09 66.14 75.74 75.81 Utility side pressure drops kpa 26 25 36 36 36 36 35 35 27 27 Heat sink pressure drops kpa 39 38 55 55 41 41 54 54 41 41 Heating capacity kw 60.17 59 70.91 70.9 80.5 80.52 91.69 91.72 104.38 104.38 Rated absorbed power kw 12.8 12.13 15.29 15.3 16.85 16.85 19.46 19.47 21.42 21.43 Evaporator side pressure drops kpa 47 45 65 65 49 49 64 64 49 49 Evaporator side flow rate l/h 10350 10148 12196 12194 13846 13850 15770 15775 17953 17953 Condenser pressure drops kpa 32 31 44 44 44 44 43 43 33 33 Condenser side flow rate l/h 8258 8166 9698 9695 11093 11096 12591 12594 14454 14451 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2/2 2/1 2/2 2/1 2/2 2/1 2/2 2/1 2/2 2/1 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1594 1594 Length mm 1174 1174 1174 1174 1174 1174 1174 1174 1174 1174 Depth mm 772 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 30.0 30.0 37.0 37.0 40.0 40.0 46.0 46.0 50.0 50.0 Booster current (LRA) A 111.0 111.0 156.0 156.0 157.0 157.0 164.0 164.0 176.0 176.0 LRA with soft starter kit A 73.0 73.0 83.0 83.0 102.0 102.0 107.0 107.0 117.0 117.0 COP 4.79 4.93 4.63 4.63 4.76 4.76 4.71 4.71 4.94 4.93 ESEER 5.61 6.04 5.39 5.78 5.73 6.11 5.59 6.01 5.89 6.25 H version refrigerant load kg 8 6 8 7 8 7 9 8 10 9 W version refrigerant charge kg 5 4 5 4 5 4 7 6 7 6 RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10 C; 40/45 C Efficiency pack 1 2 1 2 1 2 1 2 4 LEW HS / HL LEW WS / WL 91 92 111 112 131 132 141 142 144 Cooling capacity kw 84.19 84.3 102.02 101.96 116.12 116.09 133.77 133.65 134.19 Utility side pressure drops kpa 34 34 30 30 36 36 34 34 34 Heat sink pressure drops kpa 51 51 42 42 54 54 50 50 51 Heating capacity kw 116.87 116.89 140.29 140.31 160.24 160.28 184.3 184.18 185.49 Rated absorbed power kw 24.42 24.4 28.56 28.55 33.19 33.16 37.89 37.87 38.71 Evaporator side pressure drops kpa 61 61 50 50 64 64 60 59 61 Evaporator side flow rate l/h 20102 20105 24129 24134 27561 27568 31699 31679 31904 Condenser pressure drops kpa 42 42 36 37 44 44 42 42 42 Condenser side flow rate l/h 16112 16118 19463 19469 22138 22150 25507 25491 25579 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 2 / 2 2 / 1 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1594 1594 1594 1594 1594 1594 1854 Length mm 1174 1174 1674 1674 1674 1674 1674 1674 2374 Depth mm 772 772 772 772 772 772 772 772 772 Maximum current (FLA) A 61.0 61.0 70.0 71.0 79.0 79.0 91.0 91.0 92.0 Booster current (LRA) A 203.0 203.0 238.0 275.0 244.0 244.0 289.0 289.0 197.0 LRA with soft starter kit A 137.0 137.0 176.0 210.0 182.0 182.0 224.0 224.0 140.0 COP 4.79 4.79 4.95 4.95 4.81 4.82 4.86 4.86 4.79 ESEER 5.81 6.25 6.05 6.48 6.00 6.43 5.90 6.17 6.09 H version refrigerant charge kg 13 12 22 21 22 21 22 21 41 W version refrigerant charge kg 7 6 10 9 12 10 12 12 24 Page 23 of 56

RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10 C; 40/45 C Efficiency pack 1 2 4 1 2 3 4 4 LEW HS / HL LEW WS / WL 161 162 164 181 182 184 204 214 Cooling capacity kw 149.21 149.37 149.82 177.59 177.67 172.56 187.01 204.32 Utility side pressure drops kpa 38 38 38 33 33 32 37 35 Heat sink pressure drops kpa 56 56 57 49 49 47 56 53 Heating capacity kw 206.27 206.31 207.12 244.39 244.28 237.95 257.95 281.31 Rated absorbed power kw 42.83 42.82 43.08 49.94 49.95 48.24 52.89 57 Evaporator side pressure drops kpa 66 66 67 58 58 56 66 63 Evaporator side flow rate l/h 35479 35485 35624 42035 42016 40928 44368 48385 Condenser pressure drops kpa 46 46 46 41 41 40 45 43 Condenser side flow rate l/h 28481 28488 28584 33875 33855 33046 35727 39071 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 2 / 2 2 / 1 4 / 2 2 / 2 2 / 1 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 Height mm 1594 1594 1854 1594 1594 1854 1854 1854 Length mm 1674 1674 2374 1674 1674 2374 2374 2374 Depth mm 772 772 772 772 772 877 877 877 Maximum current (FLA) A 102.0 102.0 100.0 116.0 116.0 122.0 132.0 142.0 Booster current (LRA) A 298.0 298.0 211.0 361.0 361.0 250.0 321.0 328.0 LRA with soft starter kit A 233.0 233.0 152.0 278.0 278.0 184.0 256.0 263.0 COP 4.78 4.79 4.78 4.90 4.89 4.94 4.85 4.92 ESEER 5.80 6.17 6.24 5.84 6.29 6.33 6.46 6.44 H version refrigerant charge kg 25 22 41 31 28 42 42 43 W version refrigerant charge kg 13 12 25 15 13 25 25 27 RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10 C; 40/45 C Efficiency pack 3 4 3 4 4 4 4 4 4 LEW HS / HL LEW WS / WL 243 244 283 284 314 344 374 424 484 Cooling capacity kw 232.74 241.14 267.41 270.57 300.02 326.54 354.46 393.07 450.32 Utility side pressure drops kpa 38 25 29 30 36 35 34 33 35 Heat sink pressure drops kpa 57 33 41 43 53 51 51 50 55 Heating capacity kw 318.09 329.52 367.31 371.69 413.83 451.62 487.71 538.48 617.22 Rated absorbed power kw 63.37 65.38 75.13 75.62 85.81 93.13 100.44 109.69 126.84 Evaporator side pressure drops kpa 67 39 49 51 63 61 60 58 63 Evaporator side flow rate l/h 54711 56677 63178 63930 71179 83886 83886 92618 107266 Condenser pressure drops kpa 47 30 36 37 44 43 42 41 42 Condenser side flow rate l/h 44356 45994 50902 51573 57157 67474 67474 74696 85417 Electrical power supply V/ph/Hz 400 3N 50Hz Scroll compressors / cooling circuits No. 3 / 1 4 / 2 3 / 1 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 Victaulic hydraulic connections inches 2 1/2 2 1/2 3 3 3 3 3 3 3 Height mm 1854 1854 1854 1854 1854 1854 1854 1854 1854 Length mm 2374 2374 2374 2374 2374 2374 2374 2374 2374 Depth mm 877 877 877 877 877 877 877 877 877 Maximum current (FLA) A 153.0 159.0 174.0 182.0 204.0 218.0 232.0 281.0 302.0 Booster current (LRA) A 336.0 301.0 401.0 355.0 374.0 437.0 442.0 490.0 525.0 LRA with soft starter kit A 271.0 239.0 318.0 290.0 309.0 354.0 359.0 420.0 454.0 COP 4.97 5.12 4.93 4.95 4.81 4.84 4.85 4.91 4.87 ESEER 6.37 6.62 6.34 6.21 6.15 6.13 6.20 6.45 6.56 H version refrigerant charge kg 41 44 43 53 55 55 55 55 55 W version refrigerant charge kg 25 28 25 28 31 31 31 31 31 Page 24 of 56

2.1 Performance of LEW C, D, H, W heat pump units All the data in the paragraph refers to ΔT = 5 C on the evaporation and condensation side. Pf = chiller power [kw] ; Pa = absorbed power [kw]. In order to calculate the thermodynamic EER and COP factors, take the Pf / Pa ratio. The performance was calculated with different glycol percentages in a solution, even though from a thermodynamic point of view, with up to 30% of glycol in a solution, there is a minor performance drop: nonetheless refer to paragraph 4.1 Use of glycol solutions for further information. Table III: performance of LEW C D H units with cold water production mode. Size LEW 041/2 LEW 051/2 LEW 061/2 LEW 071/2 LEW 081/2 LEW 091/2 LEW 111/2 LEW 131/2 LEW 141/2 LEW 144 LEW 161/2 LEW 164 LEW 181/2 LEW 184 LEW 204 LEW 214 LEW 243 LEW C LEW D LEW H Tcond [ C] 10/30 15/30 20/30 30/35 35/40 40/45 10/30 15/30 20/30 Tev [ C] Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa 20/15 66.8 9.4 66.5 9.5 66.1 9.6 61.6 10 58.5 11.0 55.7 13 65.9 8.6 66.5 9.5 65.2 8.9 15/10 57.4 9.3 57.1 9.4 56.8 9.5 52.8 9.9 50.0 11.0 47.1 12.1 56.5 8.5 56.2 8.7 56.1 8.9 10/5 49 9.1 48.7 9.2 48.4 9.3 45.5 10.5 43.0 11.6 40.5 12.6 49.0 9.1 48.7 9.2 48.4 9.3 20/15 77.9 11.5 77.6 11.7 77 11.8 72.8 13.2 69.1 14.3 65.3 15.6 78.1 11.5 77.6 11.7 77.1 11.8 15/10 66.7 11.2 66.3 11.4 66 11.5 62.4 12.8 59.2 14.1 55.9 15.3 66.7 11.2 66.3 11.4 66.0 11.5 10/5 56.5 11 56.22 11.1 55.8 11.2 53 12.5 50.4 13.8 47.7 15 56.5 11.0 56.2 11.1 55.8 11.2 20/15 89 12.6 88.7 12.7 87.8 12.9 83.7 14.2 79.3 15.6 74.8 17.1 89.8 12.4 89.2 12.5 88.7 12.7 15/10 76.4 12.4 76.2 12.5 75.5 12.7 71.8 14 67.9 15.5 64 16.9 76.9 12.2 76.7 12.3 75.9 12.5 10/5 65.2 12.1 64.9 12.3 64.4 12.5 61.2 13.7 57.8 15.2 54.4 16.6 65.6 11.9 65.3 12.1 64.7 12.3 20/15 99.7 14.4 99 14.6 98.5 14.8 94.1 16.3 89.6 17.9 84.5 19.7 100.4 14.1 99.8 14.3 99.3 14.6 15/10 85.8 14.3 85.3 14.4 84.9 14.6 81 16.1 76.9 17.8 72.7 19.5 86.6 14.1 86.1 14.2 85.5 14.4 10/5 73.7 14 73.2 14.2 72.6 14.4 69.3 15.9 65.7 17.6 62.1 19.3 74.3 13.8 73.8 14 73.1 14.2 20/15 114.4 16.2 113.8 16.4 112.7 16.7 108.7 18 103.2 19.7 97.3 21.7 116.1 15.7 115.6 15.9 144.8 16.1 15/10 98.5 15.8 97.8 16.1 97.1 16.3 93.4 17.6 88.4 19.5 83.4 21.4 100.0 15.2 99.3 15.5 98.3 15.8 10/5 83.9 15.6 83.6 15.7 83 16 79.8 17.3 75.4 19.3 71 21.3 85.1 15.2 84.8 15.3 83.9 15.7 20/15 128.4 18 127.4 18.3 126.4 18.5 121.6 20.2 115.5 22.2 108.9 24.6 130.3 17.4 129.8 17.6 128.7 17.9 15/10 109.8 17.9 109.1 18.1 108.3 18.5 104.1 20 98.6 22.2 93 24.4 111.8 17.3 111.1 17.5 109.9 18.0 10/5 93.6 17.8 93 18 92 18.3 88.4 19.9 83.7 22.1 78.9 24.3 95.3 17.2 94.7 17.4 93.3 17.8 20/15 153.3 21.5 152.1 21.8 151.3 22.2 146.7 23.5 139.3 26.0 131.1 28.8 157.1 20.4 156.2 20.6 155.2 20.9 15/10 131.7 21.2 130.6 21.5 129.4 21.9 125.8 23.3 119.1 26.0 112.4 28.6 135.3 19.9 134.2 20.3 132.2 20.9 10/5 112.3 20.9 111.4 21.3 110.7 21.6 107.1 23 101.3 25.7 95.4 28.4 115.3 19.6 114.4 20.1 113.0 20.6 20/15 174.2 25 172.8 25.4 171.5 25.8 166.8 27.3 158.3 30.2 149.1 33.4 178.8 23.7 178 24 176.6 24.3 15/10 149.7 24.5 148.8 24.9 147.6 25.3 143.2 26.9 135.5 30.1 127.8 33.2 153.8 23.0 152.9 23.5 150.8 24.1 10/5 128 24.1 126.9 24.5 125.9 25 122 26.7 115.4 29.9 108.8 33 131.8 22.6 130.7 23.1 128.8 23.8 20/15 201.8 28.1 201.1 28.4 199.3 28.9 191.6 31.4 180.0 34.5 171.4 38.1 204.8 27.3 203.7 27.6 202.4 28.0 15/10 173.8 27.7 172.7 28 171.6 28.6 164.6 31 155.9 34.5 147.1 37.9 176.3 26.9 175.2 27.2 173.5 27.9 10/5 148.6 27.4 147.7 27.7 146.6 28.2 140.7 30.7 132.9 34.2 125.1 37.7 150.4 26.6 149.5 26.9 148.0 27.5 20/15 201.1 29 199.9 29.4 198.2 29.9 190.7 32.4 181.4 35.7 171.5 39.2 203.4 28.1 202.4 28.4 201.4 28.9 15/10 173.1 28.6 172.5 29 171 29.5 164.3 32 156.0 35.4 147.6 38.7 175.2 27.7 174.6 28.1 172.6 28.7 10/5 148.4 28.23 147.3 28.7 146.5 29 140.6 31.5 133.2 34.9 125.8 38.2 150.4 27.3 149.3 27.8 148.1 28.2 20/15 224.7 32 224 32.4 222.1 33 214.9 35.3 204.4 38.8 193.1 42.7 228.2 31.0 227.3 31.3 225.6 31.8 15/10 193.6 31.7 224.7 32.2 190.8 32.7 184.7 35 175.1 38.7 165.4 42.4 164.1 30.6 195.3 31.1 167.8 31.8 10/5 165.4 27.4 164.4 32 163.2 32.4 157.8 34.8 149.2 38.6 140.5 42.3 167.6 26.3 166.6 30.8 164.9 31.4 20/15 226.4 32.6 225.1 33 223.6 33.5 216.2 35.8 234.2 43.9 193.7 43.2 229.6 31.6 228.5 31.9 227.1 32.4 15/10 195.1 31.8 193.7 32.3 192.2 32.8 185.6 35.1 175.9 38.9 166.1 42.7 198.0 30.7 196.6 31.2 194.5 31.9 10/5 166.3 31.3 165.3 31.7 164.4 32 158.5 34.6 149.9 38.5 141.2 42.4 168.9 30.1 167.9 30.5 166.4 31.0 20/15 263.3 38 261.3 38.6 258.9 39.4 251.6 41.7 238.9 45.9 225.3 50.4 272.0 36.0 270.5 36.5 269.0 37.0 15/10 226.5 37.6 224.7 38.2 222.6 38.9 216.4 41.2 204.9 45.6 193.3 49.9 234.6 35.4 232.9 36.1 228.9 37.1 10/5 193.6 37.2 192.4 37.7 190.5 38.4 185.2 40.7 175.0 45.1 164.7 49.4 200.2 35.1 199.1 35.7 195.6 36.7 20/15 256.9 36.3 255.3 36.7 253.6 37.4 246.3 39.8 234.2 43.9 220.8 48.5 266.4 34.3 265.2 34.7 263.3 35.2 15/10 220.5 36 219.1 36.5 217.5 37.2 210.5 39.5 199.6 43.6 188.4 48.3 228.4 34.2 227.2 34.6 225.4 35.1 10/5 187.5 35.8 186.7 36.2 185.1 36.9 179.3 39.2 169.5 43.5 159.8 48.1 194.3 34 193.8 34.4 192.4 34.9 20/15 282.7 39.4 280.5 40.1 278.3 40.7 270.4 43.2 256.9 47.7 242.5 52.7 288.5 37.6 286.8 38.1 285.3 38.7 15/10 242.2 39 240.8 39.6 238.5 40.4 231.8 42.8 219.3 47.7 206.8 52.5 247.6 40.0 246.2 40.6 242.7 41.2 10/5 206.5 38.6 205.2 39.2 203.5 39.8 197.1 42.4 186.6 47.3 176 52.2 211.2 36.7 209.9 37.4 207.1 38.3 20/15 303.4 43 302.3 43.5 299.4 44.3 290.9 47 275.6 51.9 260.8 57.3 315.1 40.7 313.2 41.2 311.7 41.8 15/10 260.9 42.3 259.2 42.9 256.7 43.7 249.7 46.4 236.3 51.7 222.8 57 270.5 39.9 269 40.6 264.2 41.7 10/5 222.7 47 221.3 42.4 219 43.2 212.6 46 200.8 51.4 189 56.8 230.6 44.3 229.4 40.1 225.2 41.2 20/15 344.1 47.7 356 49.5 339.5 49.2 332.3 52.7 316.1 57.9 298.5 63.7 353.9 45.8 352.4 46.3 350.2 47.0 15/10 295.9 47.4 294.2 48 292 48.8 285.8 52.3 271.0 57.9 256.1 63.4 305.0 45.3 303.4 46 299.1 47.1 10/5 252.7 47 251.3 47.6 249.4 48.4 244.2 51.9 231.1 57.5 218 63 260.7 44.9 259.4 45.6 255.6 46.7 Page 25 of 56

LEW 244 LEW 283 LEW 284 LEW 314 LEW 344 LEW 374 LEW 424 LEW 484 20/15 358.8 48.7 402.9 57.6 353.6 50.4 344.8 54 327.5 59.6 309.1 65.9 370.3 46.9 368.1 47.4 365.3 48.1 15/10 308.2 47.8 307 48.4 304 49.3 296.7 53.1 281.1 59.3 265.5 65.4 318.0 45.6 317 46.3 311.7 47.5 10/5 263.8 47 262 47.6 259.5 48.6 253.5 52.5 239.8 58.8 226 65 272.5 44.8 270.8 45.5 266.2 46.8 20/15 400.7 56.6 445.4 65.6 394.9 58.5 381.8 62.8 362.6 69.1 341.8 76 408.6 53.9 406.5 54.7 403.6 55.6 15/10 345.3 56.1 343.2 56.8 340.4 57.9 328.9 62.1 311.4 68.6 293.8 75.1 352.5 53.4 350.4 54.2 346.0 55.7 10/5 295.7 55.4 293.9 56.2 291.5 57.1 281.5 61.3 266.2 67.9 250.8 74.4 301.8 52.7 300 53.6 296.2 54.9 20/15 405.9 56.7 480 71.4 399.2 58.6 386.9 62.7 367.9 69.0 347 76.1 413.7 54.3 411.4 54.9 408.9 55.9 15/10 350.1 55.9 347.4 56.8 344.2 57.8 333.3 62 315.5 68.8 297.7 75.6 357.5 53.2 354.8 54.2 349.9 55.6 10/5 298.5 55.4 297.2 56.1 294.4 57.2 284.8 61.3 269.3 68.3 253.8 75.2 304.8 52.8 303.5 53.6 299.3 55.1 20/15 448.7 64.6 521.5 76.7 441.5 66.8 428.4 71.4 407.1 78.5 384.1 86.3 457.0 61.8 454.6 62.6 451.9 63.7 15/10 386.5 64.1 383.6 65 381.1 66.2 368.3 70.9 349.1 78.4 329.9 85.8 394.1 61.2 391.2 62.2 387.0 63.8 10/5 330.7 63.8 328.7 64.5 325.6 65.7 314.9 70.4 297.9 77.9 280.9 85.3 337.4 60.9 335.4 61.7 330.8 63.3 20/15 482.4 70.3 480 71.4 475.7 72.7 460.9 77.6 438.0 85.4 414.3 93.9 498.8 66.9 496.9 67.9 492.9 69.0 15/10 416.6 69.8 414 70.7 410.2 72 397.8 76.9 376.6 85.0 355.3 93.1 430.4 66.2 428 67.3 420.9 69.1 10/5 357.1 69.1 355 69.9 351.6 71.2 340 76 321.3 84.2 302.5 92.4 368.1 65.8 366.2 66.7 360.2 68.5 20/15 524.7 75.8 521.5 76.7 518 78.2 500.5 83.8 474.7 92.4 448.2 101.6 541.9 72.2 538.1 73.1 534.9 74.3 15/10 453.6 74.9 450.1 76.1 446.6 77.3 432 82.9 408.4 91.7 384.8 100.4 467.6 71.0 464.3 72.4 457.5 74.1 10/5 388.4 74 385.4 75.1 382.3 76.3 369.2 81.9 349.3 90.7 329.3 99.4 400.3 70.5 397.5 71.7 391.6 73.4 20/15 578.5 84.6 574.1 85.8 568.8 87.2 550.3 93 522.4 101.8 492.9 111.8 599.9 81.1 597.8 82.1 592.5 83.4 15/10 498.8 82.1 496.1 83.3 491.4 84.7 475.5 90.4 450.5 100.0 425.4 109.6 517.8 78.5 515.5 79.8 506.2 81.7 10/5 428.3 79.6 426.4 80.6 423.2 82 407.9 88 385.8 98.0 363.6 107.9 444.5 76.1 443 77.2 435.9 79.1 20/15 657.9 92.9 654.7 94.3 650.5 96.0 628.3 103.7 596.5 115.0 560.6 128.1 685.6 88.2 683.5 89.3 677.8 90.9 15/10 571.7 91.9 568.8 93.3 564.9 95.0 545.5 102.3 515.9 113.9 485.3 126.8 594.5 87.4 592.6 88.5 588.0 90.0 10/5 494.5 90.8 490.9 92.1 486.4 93.8 468.9 101.1 443.8 112.5 416.7 125.3 512.1 86.5 510.2 87.6 507.6 88.9 In the heat pump performance calculation, in 5/0 evaporator conditions, a 10% glycol mixture was used on the dissipation side; in 0/ 5 conditions, a 25% glycol mixture was used. Table IV: performance of LEW H W units in heat pump mode. Tcond [ C] LEW H LEW W 30/35 40/45 50/55 Size Tev [ C] Pf Pa Pf Pa Pf Pa LEW 041/2 LEW 051/2 LEW 061/2 LEW 071/2 LEW 081/2 LEW 091/2 LEW 111/2 LEW 131/2 15/10 63.9 10.7 60.2 12.8 55.3 14.9 10/5 54.5 9.9 51.75 12.4 49 14.9 5/0 47.2 9.8 45.2 12.4 43.2 15 0/ 5 40.6 9.8 39.25 12.45 37.9 15.1 15/10 75 12.8 70.9 15.3 66.5 18.4 10/5 65.3 12.5 62.25 15.4 59.2 18.3 5/0 56.4 12.2 54.4 15.15 52.4 18.1 0/ 5 48.2 11.9 47.15 14.9 46.1 17.9 15/10 85.5 14 80.5 16.9 75.3 20.5 10/5 74.6 13.7 70.65 17 66.7 20.3 5/0 64.6 13.4 61.7 16.75 58.8 20.1 0/ 5 55.4 13.1 53.45 16.45 51.5 19.8 15/10 96.8 16.1 91.7 19.5 86.2 23.7 10/5 84.8 15.9 80.65 19.7 76.5 23.5 5/0 73.9 15.6 70.75 19.45 67.6 23.3 0/ 5 63.7 15.3 61.6 19.15 59.5 23 15/10 110.8 17.6 104.4 21.4 97.5 26.4 10/5 96.7 17.3 91.65 21.85 86.6 26.4 5/0 84 17 80.3 21.65 76.6 26.3 0/ 5 72.2 16.9 69.8 21.55 67.4 26.2 15/10 123.5 20 116.9 24.4 109.6 30 10/5 107.9 19.9 102.55 25 97.2 30.1 5/0 93.6 19.8 89.75 25 85.9 30.2 0/ 5 80.5 19.7 77.95 25 75.4 30.3 15/10 148.6 23.3 140.3 28.6 131.6 35.3 10/5 129.7 23 123.15 29.15 116.6 35.3 5/0 112.5 22.9 107.75 29.15 103 35.4 0/ 5 96.7 22.8 93.5 29.05 90.3 35.3 15/10 169.4 26.9 160.3 33.2 150.7 41.2 10/5 148.2 26.6 140.95 33.9 133.7 41.2 Page 26 of 56

LEW 141/2 LEW 144 LEW 161/2 LEW 164 LEW 181/2 LEW 184 LEW 204 LEW 214 LEW 243 LEW 244 LEW 283 LEW 284 LEW 314 LEW 344 LEW 374 LEW 424 LEW 484 5/0 128.7 26.4 123.45 33.75 118.2 41.1 0/ 5 110.8 26.2 107.3 33.5 103.8 40.8 15/10 194.9 31 184.3 37.9 172.4 46.5 10/5 170.5 30.8 161.65 38.65 152.8 46.5 5/0 148.1 30.5 141.55 38.45 135 46.4 0/ 5 127.6 30.2 123.05 38.1 118.5 46 15/10 195.6 32 185.5 38.7 174.1 47.1 10/5 171.4 31.5 162.9 39.1 154.4 46.7 5/0 149.2 31 142.85 38.65 136.5 46.3 0/ 5 128.7 30.5 124.3 38.1 119.9 45.7 15/10 218.6 35.3 206.3 42.8 192.5 52.1 10/5 191.2 35.1 181 43.65 170.8 52.2 5/0 166.2 34.8 158.65 43.5 151.1 52.2 0/ 5 143.3 34.5 138.1 43.25 132.9 52 15/10 219.8 35.4 207.1 43.1 193.9 53 10/5 192.2 34.9 182.1 43.95 172 53 5/0 166.7 34.4 159.45 43.65 152.2 52.9 0/ 5 143.5 33.9 138.8 43.3 134.1 52.7 15/10 259.1 41.2 244.4 49.9 227.7 60.7 10/5 226.9 40.8 214.4 50.6 201.9 60.4 5/0 197.2 40.2 187.85 50.2 178.5 60.2 0/ 5 169.9 39.7 163.45 49.7 157 59.7 15/10 252 39.6 238 48.2 222.7 59.3 10/5 219.5 39.3 208.35 49.35 197.2 59.4 5/0 190.2 39 182 49.35 173.8 59.7 0/ 5 163.6 39 158.05 49.45 152.5 59.9 15/10 272.9 43.1 258 52.9 241.7 65.2 10/5 238.5 42.8 226.45 54 214.4 65.2 5/0 206.6 42.6 197.9 54 189.2 65.4 0/ 5 177.5 42.4 171.75 53.95 166 65.5 15/10 297.5 46.4 281.3 57 263.7 70.5 10/5 259.9 46 246.8 58.3 233.7 70.6 5/0 225.5 45.7 215.85 58.15 206.2 70.6 0/ 5 193.8 45.5 187.4 58 181 70.5 15/10 337 52.3 318.1 63.4 296.4 77.3 10/5 294.9 51.9 278.65 64.5 262.4 77.1 5/0 256.4 51.5 243.95 64.2 231.5 76.9 0/ 5 221.2 51 212.2 63.65 203.2 76.3 15/10 348.7 53.1 329.5 65.4 309 81.2 10/5 304.9 52.5 289.25 66.8 273.6 81.1 5/0 264.6 51.9 253.1 66.5 241.6 81.1 0/ 5 228 51.6 220.05 66.1 212.1 80.6 15/10 389.7 62 367.3 75.1 342.4 91.3 10/5 341.5 61.3 322.7 76.05 303.9 90.8 5/0 297.2 60.5 283.05 75.45 268.9 90.4 0/ 5 256.7 59.7 246.8 74.7 236.9 89.7 15/10 393.9 62 371.7 75.6 348 92.9 10/5 344.8 61.3 326.65 77.05 308.5 92.8 5/0 299.4 60.8 286.1 76.65 272.8 92.5 0/ 5 258.8 60.3 249.2 76.05 239.6 91.8 15/10 437.6 70.9 413.8 85.8 386.3 104.3 10/5 383.7 70.4 363.35 87.5 343 104.6 5/0 334.6 69.7 319.15 87.2 303.7 104.7 0/ 5 288.5 69 278.05 86.6 267.6 104.2 15/10 477.7 76.9 451.6 93.1 420.6 113.2 10/5 418.8 76.1 395.9 94.55 373 113 5/0 364.7 75.3 346.7 93.9 328.7 112.5 0/ 5 315.7 74.4 301.75 92.95 287.8 111.5 15/10 517.2 82.9 487.7 100.4 454.8 122.2 10/5 453.3 81.9 428.55 101.7 403.8 121.5 5/0 394.8 80.9 376.1 100.85 357.4 120.8 0/ 5 341 79.7 328 99.8 315 119.9 15/10 571.4 90.7 538.5 109.7 505.6 134.7 10/5 499.8 88.1 474.35 109.7 448.9 131.3 5/0 435.8 85.9 416.45 106.7 397.1 127.5 0/ 5 377.5 84 363.95 104.1 350.4 124.2 15/10 655.3 102.5 617.2 126.8 578.1 157.9 10/5 576.3 101.2 546.1 125.3 514.8 156.5 5/0 502.2 99.7 479.0 124.1 456.6 155.4 0/ 5 438.0 98.5 421.7 122.8 406.9 154.8 Page 27 of 56

2.2 Noise emission Table V: sound emissions for LEW Lw models: Sound power Lp: Sound pressure Sizes: 040 050 060 070 080 090 110 130 140 160 180 200 210 240 280 310 340 370 420 484 Lw [db(a)] Lp [db(a)] @ 10 m Lp [db(a)] @ 5 m Standard Version Low Noise Version Standard Version Low Noise Version Standard Version Low Noise Version 72 72 73 73 74 76 76 77 80 80 81 81 81 82 82 82 83 83 83 86 68 68 69 69 70 72 72 73 76 76 77 77 77 78 78 78 79 79 79 82 44 44 45 45 46 48 48 49 52 52 53 53 53 54 54 54 55 55 55 58 40 40 41 41 42 44 44 45 48 48 49 49 49 50 50 50 51 51 51 54 50 50 51 51 52 54 54 55 58 58 59 59 59 60 60 60 61 61 61 64 46 46 47 47 48 50 50 51 54 54 55 55 55 56 56 56 57 57 57 60 2.3 Overall dimensions and weight of the main units The LEW product range consists of different frames. The overall drawings of the LEW models are reported in the following paragraph. They can be referred to by consulting the identification codes reported in the tables in this paragraph. The tables below report the weights, reference drawings and overall dimensions of all the LEW models. Table VI: weight and reference drawings of the main units of the LEW range with reference to their frames Frame F1 F2 F3 Model Weigh t [kg] CS Chiller Overall Drawing DS Dry Cooler Chiller Weig ht [kg] Overall Drawing HS Heat Pump Weig ht [kg] Overall Drawing WS Hot only Weigh t [kg] Overall Drawing LEW 041 370 HF64000737 370 HF64000737 415 HF64000737 370 HF64000614 LEW 042 360 HF64000737 360 HF64000737 385 HF64000737 360 HF64000614 LEW 051 430 HF64000737 430 HF64000737 475 HF64000737 430 HF64000614 LEW 052 420 HF64000737 420 HF64000737 445 HF64000737 420 HF64000614 LEW 061 440 HF64000737 447 HF64000737 502 HF64000737 447 HF64000614 LEW 062 430 HF64000737 437 HF64000737 467 HF64000737 437 HF64000614 LEW 071 450 HF64000737 457 HF64000737 512 HF64000737 457 HF64000614 LEW 072 440 HF64000737 447 HF64000737 482 HF64000737 447 HF64000614 LEW 081 470 HF64000737 485 HF64000737 530 HF64000737 485 HF64000614 LEW 082 460 HF64000737 475 HF64000737 510 HF64000737 475 HF64000614 LEW 091 510 HF64000737 525 HF64000737 575 HF64000737 525 HF64000614 LEW 092 490 HF64000737 505 HF64000737 540 HF64000737 505 HF64000614 LEW 111 560 HF64000592 585 HF64000592 645 HF64000592 585 HF64000608 LEW 112 550 HF64000592 575 HF64000592 605 HF64000592 575 HF64000608 LEW 131 570 HF64000592 595 HF64000592 660 HF64000592 595 HF64000608 LEW 132 560 HF64000592 585 HF64000592 625 HF64000592 585 HF64000608 LEW 141 630 HF64000592 650 HF64000592 720 HF64000592 650 HF64000608 LEW 142 615 HF64000592 635 HF64000592 685 HF64000592 635 HF64000608 LEW 161 670 HF64000592 705 HF64000592 775 HF64000592 705 HF64000608 LEW 162 650 HF64000592 685 HF64000592 740 HF64000592 685 HF64000608 LEW 181 710 HF64000592 750 HF64000592 825 HF64000592 750 HF64000608 LEW 182 690 HF64000592 730 HF64000592 780 HF64000592 730 HF64000608 LEW 144 720 HF64000581 740 HF64000581 830 HF64000581 740 HF64001344 LEW 164 740 HF64000581 775 HF64000581 865 HF64000581 775 HF64001344 LEW 184 850 HF64000581 890 HF64000581 985 HF64000581 890 HF64001344 LEW 204 870 HF64000581 915 HF64000581 1110 HF64000581 915 HF64001344 LEW 214 920 HF64000581 965 HF64000581 1065 HF64000581 965 HF64001344 LEW 243 950 HF64000581 1060 HF64000609 1120 HF64000609 1060 HF64000627 LEW 244 980 HF64000581 1090 HF64000609 1270 HF64000609 1090 HF64000627 LEW 283 1050 HF64000803 1120 HF64000609 1180 HF64000609 1120 HF64000627 LEW 284 1090 HF64000803 1260 HF64000609 1340 HF64000609 1260 HF64000627 LEW 314 1250 HF64000803 1330 HF64000609 1420 HF64000609 1330 HF64000627 LEW 344 1290 HF64000803 1380 HF64000609 1470 HF64000609 1380 HF64000627 LEW 374 1330 HF64000803 1440 HF64000609 1540 HF64000609 1440 HF64000627 LEW 424 1410 HF64000803 1530 HF64000609 1650 HF64000609 1530 HF64000627 LEW 484 1510 HF64000803 1520 HF64000609 1710 HF64000609 1710 HF64000627 Page 28 of 56

Table VII: overall dimensions of the frames of the main units (F_) Frame of the main unit Height (H) Width (L) Depth (D) F1 1594 1174 772 F2 1594 1644 772 F3 1854 2374 877 Page 29 of 56

2.4 Overall drawings of the main units HF64000737 overall drawing Page 30 of 56

HF64000614 overall drawing Page 31 of 56

HF64000592 overall drawing Page 32 of 56

HF64000608 overall drawing Page 33 of 56

HF64000581 overall drawing Page 34 of 56

HF64000609 overall drawing Page 35 of 56

HF64001344 overall drawing Page 36 of 56

HF64000803 overall drawing Page 37 of 56

HF64000627 overall drawing Page 38 of 56

3 Technical data of optional hydronic modules Hydronic modules, recommended as an optional feature for LEW units, bring together, in just a single, compact and silent solution, the main components of the primary circuit of the hydraulic system served by LEW machines. Each hydraulic module contains both circuits: ON/OFF hydraulic pump Blade type flow switch to prevent ice from forming, which is caused by the evaporation of the refrigerant in the plate heat exchanger. (LEW C D units have a flow switch on the utility side, LEW W H units have a flow switch both on the utility and the source side) Expansion vessel to manage changes in volume affecting the amount of water contained in the LEW unit and the module itself Safety valve (set to 3 bar as standard) The module has its own electric panel, which powers the pumps, protects them with motor overload protections and receives the consent from the LEW units. The power is not supplied by the LEW unit, but directly by the external line. The module is insulated to reduce the sound emissions of the pumps. 3.1 Characteristic curves of the hydraulic pumps associated to the units The graphics displayed in this paragraph show the useful head (net with the internal losses of the units) of the HP pumps and LP pumps in the optional hydronic module. At the nominal flow rates listed in this chapter in Tables I and II, the low pressure LP pumps provide 60 kpa of useful head on the utility side and 70 kpa on the dissipation side. The high pressure HP pumps provide a useful head equal to 140 kpa for both hydraulic circuits. Useful head for LEW 041, 042 pumps on utility side Useful head for LEW 051, 052 pumps on utility side Useful head for LEW 061, 062, 071, 072 pumps on utility side Useful head for LEW 081, 082 pumps on utility side Page 39 of 56

Useful head for LEW 091, 092 pumps on utility side Useful head for LEW 111, 112, 131, 132 pumps on utility side Useful head for LEW 141, 142, 144 pumps on utility side Useful head for LEW 161, 162, 164 pumps on utility side Useful head for LEW 181; 182; 184 pumps on utility side Useful head for LEW 204 pumps on utility side Useful head for LEW 214 pumps on utility side Useful head for LEW 243, 244 pumps on utility side Page 40 of 56

Useful head for LEW 283, 284 pumps on utility side Useful head for LEW 314 pumps on utility side Useful head for LEW 344 pumps on utility side Useful head for LEW 374 pumps on utility side Useful head for LEW 424 pumps on utility side Useful head for LEW 484 pumps on utility side Useful head for LEW 041, 042 pumps on dissipation side Useful head for LEW 051, 052 pumps on dissipation side Page 41 of 56

Useful head for LEW 061, 062 pumps on dissipation side Useful head for LEW 071, 072 pumps on dissipation side Useful head for LEW 081, 082 pumps on dissipation side Useful head for LEW 091, 092 pumps on dissipation side Useful head for LEW 111, 112 pumps on dissipation side Useful head for LEW 131, 132 pumps on dissipation side Useful head for LEW 141, 142 pumps on dissipation side Useful head for LEW 144 pumps on dissipation side Page 42 of 56

Useful head for LEW 161, 162, 164 pumps on dissipation side Useful head for LEW 181, 182, 184 pumps on dissipation side Useful head for LEW 204 pumps on dissipation side Useful head for LEW 214 pumps on dissipation side Useful head for LEW 243 pumps on dissipation side Useful head for LEW 244, 283, 284 pumps on dissipation side Useful head for LEW 314 pumps on dissipation side Useful head for LEW 344 pumps on dissipation side Page 43 of 56

Useful head for LEW 374 pumps on dissipation side Useful head for LEW 424 pumps on dissipation side Useful head for LEW 484 pumps on dissipation side Page 44 of 56

3.2 Overall dimensions and weight of optional hydronic modules The tables below list the weights, reference drawings and overall dimensions of all optional hydronic modules. The overall drawings of the optional modules are reported in the following paragraph. They can be referred to by consulting the identification codes reported the tables in this paragraph. Table VIII: weight and reference drawings of optional modules with reference to the dimensions of the relative main unit and whether or not there is a water side cycle inversion valve. Optional hydronic module with pumps Model Optional module frame Weight [kg] Overall Drawing LEW 041 M1 391 HF64000799 LEW 042 M1 391 HF64000799 LEW 051 M1 400 HF64000799 LEW 052 M1 400 HF64000799 LEW 061 M1 400 HF64000799 LEW 062 M1 400 HF64000799 LEW 071 M1 395 HF64000799 LEW 072 M1 395 HF64000799 LEW 081 M1 395 HF64000799 LEW 082 M1 395 HF64000799 LEW 091 M1 399 HF64000799 LEW 092 M1 399 HF64000799 LEW 111 M1 399 HF64000799 LEW 112 M1 399 HF64000799 LEW 131 M1 412 HF64000799 LEW 132 M1 412 HF64000799 LEW 141 M1 412 HF64000799 LEW 142 M1 412 HF64000799 LEW 161 M1 433 HF64000799 LEW 162 M1 433 HF64000799 LEW 181 M1 543 HF64000799 LEW 182 M1 543 HF64000799 LEW 144 M3 423 HF64000906 LEW 164 M3 433 HF64000906 LEW 184 M3 543 HF64000906 LEW 204 M3 559 HF64000906 LEW 214 M3 559 HF64000906 LEW 243 M3 576 HF64000908 LEW 244 M3 587 HF64000908 LEW 283 M3 587 HF64000908 LEW 284 M3 587 HF64000908 LEW 314 M3 614 HF64000908 LEW 344 M3 614 HF64000908 LEW 374 M3 626 HF64000908 LEW 424 M3 626 HF64000908 LEW 484 M3 626 HF64000908 Table VII: overall dimensions of the frames of the main units (F_) and optional hydraulic modules (M_) used in the LEW range Optional module frame Height (H) Width (L) Depth (D) M1 1594 1174 772 M2 1594 1644 772 M3 1854 1644 877 M4 1854 2374 877 Page 45 of 56

3.3 Overall drawings of optional hydronic modules HF64000799 overall drawing Page 46 of 56

HF64000906 overall drawing Page 47 of 56

HF64000908 overall drawing for LEW C units Page 48 of 56

HF64000908 overall drawing for LEW D W H units Page 49 of 56

4 Installation 4.1 Installation clearance requirements The hydraulic connections are all foreseen on the right side of the unit, when looking at the front panel. This way the back of the unit can be against the wall. It is essential to ensure the following service spaces: rear side: min. 0 m electric panel side: at least 1 m to guarantee access for inspections and/or for maintenance of cooling components right side: 1 m to be able to connect the hydraulic piping properly top side: min. 1 m left side: 0.5 m These distances refer to standard versions of LEW units; the same considerations apply to the optional hydronic modules. When installing the unit, for safety purposes, make sure that the room temperature does not exceed 50 C (with unit on or off). 4.2 Volume of water in the system The ON/OFF type compressors work intermittently, since the cooling power required by the utility is not generally the same as that supplied by the compressor. In systems containing little water, in which the thermal inertia is low, verify that the water content of the delivery section (to users) satisfies the equation below: V Cc Sh Ns V = water content in user section [m3] Sh = specific heat of fluid [J/(kg/ C)] e.g. 2090 [J/(kg/ C)] for water = density of fluid [kg/m3] e.g. 1000 [kg/m3] for water D = minimum time between 2 compressor restarts [s] e.g. 120 [s] DT = admissible differential on water T [ C] e.g. 4 [ C] Cc = Cooling Capacity [W] Ns = N of capacity control steps Page 50 of 56

Inlet water T Inertial Tank Ts C Outlet water T A standard feature of LEW units is a device to control the water flow rate (blade-type flow switch supplied). Any tampering with this device will immediately invalidate the warranty. We recommend installing a metal net filter on the water inlet piping. Warning: Never perform hydraulic connection operations with open flames near or inside the unit. Page 51 of 56

5 Operating limits This paragraph reports a list of operating limits for the LEW chillers relating to the water outlet temperature on the utility side and water inlet temperature at the dissipation exchanger. Applications with water T exceeding the limits indicated they must run with R134a refrigerant (available upon request). You can contact your local Agent for related details. Operating range of LEW units in cooling mode and heat pump mode: Water can be produced at temperatures below 5 C (up to 10 C) using glycol solutions. This lowers the freezing point as shown in the following table: Minimum temperature of produced water Percentage in weight of ethylene glycol Freezing temperature of mixture 5 C 2 C 1 C 5 C 10 C 0 % 10 % 15% 25 % 30 % 0 C 4 C 8 C 14 C 18 C If the water produced is below 0 C, a special insulation needs to be applied to the cold pipes to prevent ice from forming. This is why applications with temperatures produced below 0 C must be considered as special applications. The useful head supplied by the pump, at the same volumetric water flow, depends on the glycol percentage as shown in the following table: Percentage in weight of ethylene glycol Reduction percentage of useful flow rate 0 % 10 % 15% 25 % 30 % 0 % 5 % 8 % 12 % 15 % Performance loss of the thermodynamic circuit is negligible up to concentrations of 30% glycol, in weight. Page 52 of 56