Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Similar documents
Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

DX-9100/9120 Local Sonalert Logic

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

York 25-Ton VAV Rooftop Unit

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Fire Operator Workstation (Fire OWS) User s Guide

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Reciprocating Chiller

DX-9100 Applications from Engineering Services

iworx Air Side Application Wiring Guide

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator TITUS Application

Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren

Digital Precise Air Control - DPAC

Multistate Alarm. Introduction

Metasys Integrator Compu-Aire Application

Metasys System Extended Architecture Smoke Control System

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

QA16 Addressable System

Data Aire DAP TM III. Metasys Control Points

TC-9102 Applications

Metasys Integrator Airflow Application

P2000 and Metasys System Integration

JCI - Smoke Control Systems Overview 10/27/2016

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

Installation, Start-Up, and Operating Instructions

MicroTech Self-Contained Air Conditioning System

Tebis application software

FIB_FGBS-001 Universal Binary Sensor

Simplex Panel Interface Guide

Verasys System Operation Overview Technical Bulletin

FlexiSmoke WSC 520 / 540 / 560. Utilization examples

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

Using the Room View Window

Odyssey. issue 01c. system manual

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Introduction. Introduction

HVAC Control Sequences of Operation

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option

Section 4: Operating Instructions

Smoke Detector and Siren. Manual

10 Year Smoke Detector and Siren

Document # R01

REMOTE CONTROLLER KSWM units

P2000 and Metasys System Integration

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

TV2 Room Pressure Monitor Quick Start Guide

TABLE OF CONTENTS TABLE OF CONTENTS 1

Z24 Wireless Zone Controller Professional Installation Guide

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Thank you very much for purchasing our air conditioner. Please read this owner's manual carefully before using your air conditioner.

DI220 Using the Optional Docking Station The maintenance and operating functions of the Micro IV can be automated with the Micro IV Docking Station.

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

Ovation Alarm Management System

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

Dual Mixing Application

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0

ProStar 325 UV-Vis Detector

The supplier and installer of the system should be approved by the local civil defence authority.

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Network Hardware and wiring (quiz)...

Avigilon Control Center System Integration Guide

ENERVEX ADC100 DRAFT CONTROL

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Metasys Integrator Vilter Application

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Metasys Integrator McQuay Application

CERTIFICATION BULLETIN

INTELLIGENT FIRE ALARM CONTROL PANEL

POP_ Smoke Detector

INSTALLATION MANUAL PC15OO

Notification Appliance Circuit Module

TEC210x-2 Series Networked Thermostats

FieldServer Driver - Serial FS Notifier NCA

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

Commercial Thermostat

HIGH-RISE RETROFIT ORDINANCES - NO and NO

Commercial Thermostat Submittal Data

Premier 2-Zone Controller model Installer Guide

rpsa FIRE PROTECTION ENGINEERS

POP_ Smoke Detector

Alarms Updated 03/26/2018

Air Conditioning Control. Air Cond. to program : AC001. MODEL 3000 / ACCESS 4000 Programmer s Manual - Aircon. Rev 4.50 [MENU 7-5-6] p 1.

TV2 Clean Room Monitor

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

2000 Series. Program Entry Guide. Control Panels

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

SEQUENCE OF OPERATIONS

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

User s Manual. System Information... 3 Using the Touchpad Buttons... 3 General Operation... 4 Using Systems with Keyswitches... 4

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Transcription:

Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description 3 Sequence of peration 3 Design onsiderations *5 Application Details 9 Main Function 9 Location *9 / Requirements 9 Process 10 GPL Screens 10 * ndicates those sections where changes have occurred since the last printing. 1997 Johnson ontrols, nc. 1 ode No. LT-6363357

2 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

ntroduction Application Description Sequence of peration This application provides warehouse smoke exhaust and reset logic for a rooftop unit. During a fire alarm, the process described in this document controls rooftop unit to minimize the spread of smoke. Note: This application note presents only an example of a smoke control strategy. Realize that since every building is unique, the details of applying the strategy will vary. This application note, then, is offered to assist you in developing an application that will be appropriate for your project. When an automatic detector in a warehouse indicates an alarm, an alarm input triggers the Warehouse Smoke Exhaust and Reset Logic process. The process turns off the supply fan, turns on the exhaust fan, opens the modulated exhaust dampers, closes the return air dampers, closes the outside air dampers, and closes the inlet vanes. n addition, the process locks out heating and cooling and all other commands for this HVA equipment. As a result, the warehouse is purged of smoke and hot gases because the supply fan is off and the exhaust fan is on, creating a negative pressure in the warehouse. Negative pressure in the warehouse also prevents the smoke from spreading to other areas of the building. GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 3

4 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Design onsiderations Keep the following design considerations in mind when designing a warehouse smoke exhaust and reset logic system for a rooftop unit. n addition, please refer to the Smoke ontrol Technical Bulletin (LT-636330) in this manual. You can find important instructions and guidelines for using GPL compounds in How to Use the Metasys Smoke ontrol Library (LT-636332), located in the Smoke ontrol section of this manual. For information on the definition and the initial configuration of the objects and the function blocks, use GPL to examine the compound in this example. You must define system and object names for all objects. You must define the hardware location for each object. The Warehouse Smoke ontrol process has a priority of 2. A process priority of 1 is the highest, whereas a process priority of 4 is the lowest. The location for setting the process priority is in the GPL process compound s template. The process period is 00:00:00, meaning this process will not be triggered periodically. This process is designed to be triggered by Warehouse Smoke/Fire Alarm inputs and/or the Manual Reset input. f the Warehouse Smoke/Fire Alarm inputs and/or Manual Reset input are not triggerable, give the process a non-zero period, so it triggers periodically. Query the process compound to view or change the process period. A typical process period would be from 5-10 seconds. Be aware that the shorter the process period, the busier the Network ontrol Module (NM) is.! WARNNG: Setting the process period to one second ties up the NM. The NM may reboot repeatedly, or it may be unable to run other processes. This automatic smoke control application does not provide a manual override. For the details on override logic, see the Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit; ndependent Manual verride Application Note (LT-6363358) and the Fire Fighter s Smoke ontrol Station (FSS) Application Note (LT-6363351). GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 5

Most rooftop units have a purge function used when the cooling or heating system ends its n cycle. This should not be confused with a smoke control purge process or used as such. You can simply reset from Alarm mode back to Monitor mode without running purge. An alarm occurs if command does not equal condition for any controlled device output. Each Binary utput (B) object for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The B s Alarm attribute indicates when command does not equal condition. The Alarm attribute must be used in other applications, such as initiating the Local Sonalert application. When all of the fire alarms have been cleared, you must reset the process from Alarm mode back into Monitor mode. To do this, command the Manual Reset input to n. All of the objects for the rooftop unit will automatically receive a Release Priority command at Priority 2. The reset object is then automatically commanded back to ff at Priority 3. Each B object has an alarm number. n the GPL HVA Library, the controlled devices Bs are set to Alarm Number 1. Use the Report Router/Alarm Management feature to create alarm messages and link the alarm messages to alarm numbers. For example, the alarm message may read: Alarm Number 1 - Feedback does not match the command sent to the Binary utput bj. This application, as it exists in the GPL Smoke ontrol Library, complies with the UL 864 UUKL Smoke ontrol Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the local Authority Having Jurisdiction (AHJ). Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. n the case of fan start after damper close, these times are additive. f the damper must be closed before the fan starts, the total response time could be up 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (ontrol system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) 6 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

To maintain UL 864 UUKL Smoke ontrol Listing, you must connect a printer model number PRN-3 or PRN-4 to the Fire WS or directly to the Fire Network ontrol Module (NM). For printer installation, refer to the manual included with the printer. Also, configure the Report Router/Alarm Management feature to route your alarm messages to the printer. For specific wiring requirements, refer to Metasys Smoke ontrol Wiring Technical Bulletin (LT-636331). GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 7

8 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Application Details Main Function Location The main function of this application is to provide warehouse smoke exhaust and reset logic for a rooftop unit. During a fire alarm, this process controls a rooftop unit to minimize the spread of smoke. The Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit application is located under the Fire/Security/L onference of the Engineering Services Bulletin Board System (BBS). nce logged on the BBS, you can download the file to your computer. The application is also located on the Advisor. Follow the path ffices>systemservicesmilwaukee>engineeringservices>fire&security. / Requirements Table 1: / Requirements nput Requirements Name of Type of Block Data Engineer Units Req? Range Default Value Description RESET Binary n\ff Yes - - Manual Reset ALARM Binary Alm\Nor Yes - - Warehouse Smoke/Fire Alarm utput Requirements Name of Type of onnection Data SFANSS Dual ommand Engineer Units Req? Range Description n/ff Yes - Rooftop Unit Supply Fan Start/Stop SFAN_REL ommand - Yes - Supply Fan Release Priority ommand EFANSS Dual ommand n/ff Yes Exhaust Fan (with Attached Exhaust Dampers) EFAN_REL ommand - Yes - Exhaust Fan Release Priority ommand DA_DPRS ommand % pen Yes - utside Air Dampers DA_REL ommand - Yes - utside Air Release Priority ommand RET_DPRS ommand % pen Yes - Return Air Dampers RET_REL ommand - Yes - Return Air Release Priority ommand LG_L ommand n/ff Yes - ooling Lockout ommand HTG_L ommand Enable/ Disable Yes - Heating Lockout ommand NLT_VN ommand % pen Yes - nlet Vanes NLV_REL ommand - Yes - nlet Vane Release ommand RSET_FF ommand - - - Manual Reset ff GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 9

Process GPL Screens This is a process compound. n the screen, click once on the compound block for process information. The set of figures in this section show each GPL screen of the Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit application. WAREHUSE SMKE NTRL RESET ALARM ALM_PR RSET_LG EXHAUST MMANDS RELEASE EXH_MDS QP QT QA QA Q Q QA SFANSS EFANSS DA_DFRS RET_PRS LG _L HTG_L NLV_VNE RP RP R R R R R Q SFAN_REL EFAN_REL DA_REL RET_REL LG _L HTG_L NLV_REL RSET_FF SMKE_TL\WAREHUS scrn-50 Figure 1: Warehouse Smoke ontrol 10 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

ALARM PRESSNG AND RESET LG MPUND RESET NT R ALARM J 2 AND LTH PULS NE-SHT ENA_MD SMKE_TL\WAREHUS RSET_LG scrn-51 Figure 2: Alarm Processing and Reset Logic ompound MMANDS SENT T BJET N THE EXHAUST MDE ENA_MD NST..% PN NST..% PN NST FF NST FF NST..% PN E V V V MD STP E E MD START E E MD SET AD E E MD SET AD E E MD SET BD E E MD SET BD E E MD SET AD QP QT QA QA Q Q QA SFANSS EFANSS DA_DFRS RET_PRS LG _L HTG_L NLV_VNE SMKE_TL\WAREHUS MMANDS scrn-52 Figure 3: ommands Sent to bject in Exhaust Mode GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 11

J 2 Figure 4: Release of Exhaust Mode ommands and Resetting Manual Reset bject ontrols Group FAN 636 507 E. Michigan Street Metasys Network Technical Manual P.. Box 423 Printed in U.S.A. Milwaukee, W 53201 12 GPL Applications Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit