Installation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents

Similar documents
Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

HW 22 District heating substation for indirect heating and domestic hot water systems

WL Instantaneous water heater

Akva Lux VX District heating substation for indirect heating and domestic hot water systems

Akva Lux TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems

Akva Vita Instantaneous water heater

Instructions for installation and use Akva Lux II VX substations 1. Contents

MAKING MODERN LIVING POSSIBLE. Akva Lux II TDP-F. Instructions for installation and use. Danfoss District Energy

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg

Instructions. VX Solo II. 1.0 Table of contents

Wall-mounted substation PKL-113

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy

ISCG90SS _03 ISCG90SS

Installation, operating and servicing instructions

T. +44 (0) E.

FW422. Integrated In Column Larder Fridge. Installation, use and maintenance.

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

ModuSat TP. Energy. Heat Interface Units

TH100 Three in One Instant Hot Water Tap

Reno Exchange of gas boilers.

Alarm System SECURE AS 302

Box60/ 70/ 90. Box60_70_90 v8

Instructions for the fan motor control system, SILVER C

ModuSat TP. Energy. Heat Interface Units

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

EcoAdvance Dual Plate

Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro

ADVANCE ECB ELECTRIC COMBINATION BOILER

EDD61 & EDD91 Extractors

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Operating Manual ECCO/ECG Couch

60 C water temperature ensures thermal disinfection during hot water production

FF820 freestanding full height larder fridge Manual for Installation, Use and Maintenance

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

Baxi Megaflo System HE IE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Boiler

ELECTRIC BOILERS FOR CENTRAL HEATING

FW821 extra large integrated larder fridge Manual for Installation, Use and Maintenance

Sanitary Water Tank INSTALLATION & SVC MANUAL

1ZSE en, Rev. 4. On-load tap-changers, type UZ User s manual

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

Operating Manual 3 part Multi Couch 2017

> ENGLISH VERSION. Instructions HERU 50 HERU / utg 2

Water Boiler. Instruction manual. Model: GL346-A/GL347-A/GL348-A/GL349-A

Instruction Manual, Toftejorg Rotary Spray Heads Toftejorg MultiMidget, Toftejorg MultiMagnum

WHE 2.24 / WHE 2.24 FF

Operating instructions

Operating Manual 3 part Endoscopy Couch

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

Operating instructions

UV Flame Supervision System

PC87 American Style Double Door Fridge Freezer Manual for Installation, Use and Maintenance

User instructions DHP-AT

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation and Operation Manual REV. L

ir-range 8G /03.15 Changes reserved.

Edition 8 From serial no Publ. no OM 5030NHD; Orwak 5030-NHD OPERATING INSTRUCTIONS (IN THE ORIGINAL)

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

Safety and Instruction Manual

MEH600/900 MEP600/900 Extractors. Manual for Installation, Use and Maintenance

PRESSURE WASHER MODEL NO: JETSTAR 1750 OPERATION & MAINTENANCE INSTRUCTIONS. WARNING Read the instructions before using the machine PART NO:

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

Ropox Bathtub. Keep this manual with the product at all times! User Manual & Mounting Instructions PDF 6128 /

heat interface units A BOILER WITHOUT A FLAME

Ultracom cxi. Instructions for Use. High Efficiency Condensing System Boilers. To b e l e f t w i t h t h e u s e r.

Friwa Compact. Operating instructions EN

INSTRUCTIONS. OJ-DV-Relay-Module. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. Optional module for OJ-DV motor controller

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

HW3 Handwash Installation and Operating Instructions

FF820 Freestanding Full Height Larder Fridge Manual for Installation, Use and Maintenance

30% Take lead on your project with an efficient system concept. lower energy.

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

Installation Guide DSA 1 MINI. Contents

FW422 Integrated In Column Larder Fridge Manual for Installation, Use and Maintenance

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

Miniature Thermoelectric Cooler Controller MTCC-01 user's guide

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional.

AGS 2 SOLAR PUMP STATION FOR SOLAR DOMESTIC HOT WATER SYSTEMS UK/IE

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

Operating instructions

Built-under larder fridge instruction manual RBL4. Contact Caple on or for spare parts

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Crown Boiler Company

XGUARD-10/-5. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

ascent Installation & maintenance instructions Customer/technical services Guarantee Mono basin filler with infrared sensor GUARANTEE REGISTRATION

1592P01. for liquids in piping DN

Original operating instructions Safety switch with guard locking AC901S AC902S

Flow Factor ~

Edition 8, From serial no Publ. no OM 5030, Orwak 5030 OPERATING INSTRUCTIONS (IN THE ORIGINAL)

Rigoletto 60,90 & 120 Built-In Cupboard Hood

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

INSTRUCTION MANUAL T30 1MN0107 REV. 0. operates with ISO9001 certified quality system

Transcription:

1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................ 4 4.0 Mounting... 5 4.1 Mounting........................................................... 5 4.2 Start-up.............................................................. 7 4.3 Electrical connections............................................. 8 8.0 Troubleshooting... 13 8.1 Troubleshooting in general...................................... 13 8.2 Troubleshooting DHW............................................ 13 8.3 Disposal............................................................. 14 9.0 Danfoss installations guide... 15 9.1 Danfoss installations guide...................................... 15 10.0 Declaration... 19 10.1 Declaration of conformity........................................ 19 5.0 Wiring... 9 5.1 Wiring description................................................. 9 5.2 Wiring diagram..................................................... 9 6.0 Design... 10 6.1 Design............................................................... 10 6.2 Schematic diagram... 11 7.0 Controls... 12 7.1 Maintenance........................................................ 12 Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 1

2 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

2.0 Functional description Manifold system for floor heating The Termix distribution unit can be directly connected to the Termix VMTD, VMTD mixer, VX and VVX units. The unit is supplied with meter fitting piece for domestic water, safety set or Combiluk as required. The Termix distribution unit for connection of water and heating pipes in connection with hidden pipe installations allows for a large number of connections for cold water, hot water, radiators and floor heating with in dimensions of 530 x 565 x 380 mm (h x w x d). The compact solution ensures that even though all connections are in use the unit still fits into a 60 cm cupboard. The Termix distribution unit can be mounted with a spear in the ground in the early stages of building. When the building is finished and protected against theft the Termix district heating unit can be mounted. The reliability is very high. The wireless controls comply with the newest EU standards (868 MHz) for electronic equipment. At this frequency the risk of signal disturbances from other electronic household appliances is very low. The controls for the Termix distribution unit include a program for exercise of valves and pump and a pump stop to protect the circulation pump. Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 3

3.0 Safety notes 3.1 Safety Notes general The following instructions refer to the standard design of substation. Special versions of substations are available on request. This operating manual should be read carefully before installation and start-up of the substation. The manufacturer accepts no liability for damage or faults that result from non-compliance with the operating manual. Please read and follow all the instructions carefully to prevent accidents, injury and damage to property. Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. Please comply with the instructions issued by the system manufacturer or system operator. Corrosion protection All pipes and components are made of stainless steel and brass. The maximum chloride compounds of the flow medium should not be higher than 150 mg/l. The risk of equipment corrosion increases considerably if the recommended level of permissible chloride compounds is exceeded. Energy source The substation is designed for district heating as the primary source of energy. However, also other energy sources can be used where the operating conditions allow it and always are comparable to district heating. Application The substation is designed to be connected to the house installation in a frost-free room, where the temperature does not exceed 50 C and the humidity does not exceed 60%. Do not cover or wall up the substation or in any other way block the entrance to the station. Authorized personnel only Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. Please observe instructions carefully To avoid injury to persons and damage to the device, it is absolutely necessary to read and observe these instructions carefully. Warning of high pressure and temperature Be aware of the installation s permissible system pressure and temperature. The maximum temperature of the flow medium in the substation is 120 C. The maximum operating pressure of the substation is 10 bar. PN 16 versions are available on enquiry. The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded. The substation installation must be equipped with safety valves, however, always in accordance with local regulations. Choice of material Choice of materials always in compliance with local legislation. Safety valve(s) We recommend mounting of safety valve(s), however, always in compliance with local regulations. Connection The substation must be equipped with features that ensure that the substation can be separated from all energy sources (also power supply). Emergency In case of danger or accidents - fire, leaks or other dangerous circumstances - interrupt all energy sources to the station if possible, and seek expert help. In case of discoloured or bad-smelling domestic hot water, close all shut-off valves on the substation, inform the operating personnel and call for expert help immediately. Warning of hot surface The substation has got hot surfaces, which can cause skin burns. Please be extremely cautious in close proximity to the substation. Power failure can result in the motor valves being stuck in open position. The surfaces of the substation can get hot, which can cause skin burns. The ball valves on district heating supply and return should be closed. Warning of transport damage Before substation installation, please make sure that the substation has not been damaged during transport. Storage Any storage of the substation which may be necessary prior to installation should be in conditions which are dry and heated. IMPORTANT - Tightening of connections Due to vibrations during transport all flange connections, screw joints and electrical clamp and screw connections must be checked and tightened before water is added to the system. After water has been added to the system and the system has been put into operation, re-tighten ALL connections. 4 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

4.0 Mounting 4.1 Mounting Installation must be in compliance with local standards and regulations. District heating (DH) - In the following sections, DH refers to the heat source which supplies the substations. A variety of energy sources, such as oil, gas or solar power, could be used as the primary supply to Danfoss substations. For the sake of simplicity, DH can be taken to mean the primary supply. Authorized personnel only Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. Connections: Floor heating flow line (FHFL) Floor heating return line (FHRL) Connection sizes: FHFL + FHRL: G ¾ (int. thread) Dimensions (mm): H 710 x W 505 x D 175 Weight (approx.): 20 kg Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 5

4.1.1 Installation Mounting: Adequate space Please allow adequate space around the substation for mounting and maintenance purposes. Orientation The station must be mounted so that components, keyholes and labels are placed correctly. If you wish to mount the station differently please contact your supplier. Drillings Where substations are to be wall-mounted, drillings are provided in the back mounting plate. Floor mounted units have support. Keyhole for mounting. Labelling Each connection on the substation is labelled. Before installation: Clean and rinse Prior to installation, all substation pipes and connections should be cleaned and rinsed. Thightening Due to vibration during transport, all substation connections must be checked and tightened before installation. Unused connections Unused connections and shut-off valves must be sealed with a plug. Should the plugs require removal, this must only be done by an authorized service technician. Installation: Strainer If a strainer is supplied with the station it must be fitted according to schematic diagram. Please note that the strainer may be supplied loose. Connections Internal installation and district heating pipes connections must be made using threaded, flanged or welded connections. 6 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

4.2 Start-up Start-up, Heating with mixing loop Start-up: 1: Pump speed Set the pump to highest speed before start-up. Re-thighten connections After water has been added to the system and the system has been put into operation, re-tighten ALL connections. 2: Start pump Start the pump and heat through the system. 3: Open shut-off valves The shut-off valves should then be opened and the unit observed as it enters service. Visual checking should confirm temperatures, pressures, acceptable thermal expansion and absence of leakage. If the system operates in accordance with design, it can be put to regular use. Pump The pump must be switched off during system fill. 4: Vent system Switch off the pump and vent the installation after the radiators have been warmed up. 5: Adjust pump speed Set the pump to the lowest speed consistent with comfort and electricity consumption. Normally the change-over switch is set in the mid position (default). However for systems with under floor heating or single pipe loop systems, it may be necessary to turn the change-over switch upwards. Higher pump speeds are only used if the heating requirement increases. Under floor heating: Pump stop function If the substation is used in connection with under floor heating, the circulation pump must be connected to the pump stop function in the under floor heating controller. The pump must be stopped if all under floor heating circuits are closed. Warranty If this is not possible, then flow must be continued through the by-pass. Failing this, the pump will be at risk of seizure and any remaining warranty will be withdrawn. Summer operation: Switch off pump In summer the circulation pump must be switched off and the shut-off valve to HE supply closed. Running pump bi-weekly It is recommended to start up the circulation pump (for 2 minutes) once a month during summer; the shut-off valve of the HE supply must be shut. Electronic controller Most electronic controllers will start up the pump automatically (please note manufacturer s instructions). Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 7

4.3 Electrical connections Before making electrical connections, please note the following: Safety notes Please read the relevant parts of the safety notes. 230 V The substation must be connected to 230 V AC and earth. Disconnection The substation must be electrically connected so that it can be disconnected for repairs. Authorized electrician Electrical connections must be made by an authorized electrician only. Local standards Electrical connections must be made in accordance with current regulations and local standards. Outdoor temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direct sunlight. They should not be placed close to doors, windows or ventilation outlets. The outdoor sensor must be connected to the station on the terminal block under the electronic control. 4.3.1 Thermoactuators Activating the thermoactuators The thermoactuators are supplied with a first open function, such that they are slightly open for frost protection until the electrical controller is installed. During commissioning, the first open function is disabled by removing the red mounting split on the thermoactuator. Please check that the thermoactuators can fully close following disablement of the -first open function. See the installation guide included with the thermoactuator. 8 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

5.0 Wiring 5.1 Wiring description Connecting the system s circulation pump The system s circulation pump should be connected to the contact relay in the electrical floor heating controller, so the pump can automatically start and stop, depending on whether the thermoactuators are open or closed. If the pump pushes against closed valves it can overheat and burn out. The electric floor heating controller is not approved to supply power to the circulation pump. The pump must therefore be supplied from an external connection box, such that only the 230 V phase (active) is fed through the relay contact on the electrical floor heating controller. The neutral and earth connections must not enter the floor heating controller. 5.2 Wiring diagram Junction box 230 V AC connector plug with Earth Danfoss CF-MC Master Controller 230V AC power supply 230V plug is cut off! Safety thermostat Pump Relay in Danfoss CF-MC Master Controller Circulator pump Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 9

6.0 Design 6.1 Design Your substation might look different than the substation shown. Design description J Electronic controller floor heating 35 Ball valve/non-return valve FHFL Manifold system for floor heating flow line M Electrical wiring box 48 Air vent, manual FHRL Manifold system for floor heating return line 7 Thermostatic controller, HE 49 Safety thermostat 10 Circulation pump 55 Thermoactuator 20 Filling/drain valve 10 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

6.2 Schematic diagram (M) (A) (B) (C) Your substation might look different than the schematic diagram shown. Schematic description (A) Termix unit J Electronic controller floor heating 35 Ball valve/non-return valve (B) Floor heating flow line 1 Ball valve 39 Connection closed (C) Floor heating return line 7 Thermostatic valve 48 Air vent, manual (M) Electrical wiring box 10 Circulation pump 49 Safety thermostat 20 Filling/drain valve 55 Thermoactuator 6.2.1 Technical parameters Technical parameters Nominal pressure: PN 10 (PN 16 versions are available on enquiry) Max. DH supply temperature: 120 C Min. DCW static pressure: 0.5 bar Brazing material (HEX): Copper Sound level: 55 db Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 11

7.0 Controls 7.1 Maintenance The substation requires little monitoring, apart from routine checks. It is recommended to read the energy meter at regular intervals, and to write down the meter readings. Regular inspections of the substation according to this Instruction are recommended, which should include: Authorized personnel only Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. Strainers Cleaning of strainers. Meters Checking of all operating parameters such as meter readings. Temperatures Checking of all temperatures, such as DH supply temperature and DHW temperature. Connections Checking all connections for leakages. Safety valves The operation of the safety valves should be checked by turning the valve head in the indicated direction. Venting Checking that the system is thoroughly vented. Inspections should be carried out minimum every two years. Spare parts can be ordered from Danfoss. Please ensure that any enquiry includes the substation serial number. 12 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

8.0 Troubleshooting 8.1 Troubleshooting in general In the event of operating disturbances, the following basic features should be checked before carrying out actual troubleshooting: the substation is connected to electricity, the strainer on the DH supply pipe is clean, the supply temperature of the DH is at the normal level (summer, at least 60 C - winter, at least 70 C), the differential pressure is equal to or higher than the normal (local) differential pressure in the DH network if in doubt, ask the DH plant supervisor, pressure on the system - check the HE pressure gauge. Authorized personnel only Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. 8.2 Troubleshooting DHW Problem Possible cause Solution Too little or no DHW. Hot water in some taps but not in all. Tap temperature too high; DHW tap load too high. Temperature drop during tapping. Thermostatic control valve does not close Strainer in supply or return line clogged. DHW circulation pump out of order or with too low setting. Defective or clogged non-return valve. No electricity. Wrong setting of automatic controls, if any. Scaling of the plate heat exchanger. Defective motorized valve. Defective temperature sensors. Defective controller. DCW is being mixed with the DHW, e.g. in a defective thermostatic mixing valve. Defective or clogged non-return valve on circulation valve. Thermostatic valve adjusted to a too high level. Scaling of the plate heat exchanger. Larger DHW flow than the substation has been designed for. Temperature difference between DH supply and DHW set point too low. Clean strainer(s). Check circulation pump. Replace clean. Check. To adjust an electronic controller for DHW, pls. note enclosed instructions for electronic controller. Replace rinse out. Check (use manual function) replace. Check replace. Check replace. Check replace. Replace clean. Check set. Replace rinse out. Reduce DHW flow. Lower the set point temperature or increase the DH supply temperature. Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 13

8.3 Disposal Disposal This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal. Always follow the local disposal regulations. 14 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

21.0 c Installation Guide 9.0 Danfoss installations guide 9.1 Danfoss installations guide Installation - CF2 3. 4. 5. 6. 7. 8. 9. ch2 ch4 ch1 ch3 x1 x1 (= ch2) x2 (= ch3) x3 (= ch4) 10. 21.0 c 11. x1 A x1 21.0 c ch4 B x5 21.0 c Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 15

Installation - CF2 14.A A x1 21.0 c B x5 21.0 c x1 21.0 c Installation - CF2 1. 2. 3. ch2 ch4 ch1 ch3 x1 (= ch2) x2 (= ch3) x3 (= ch4) 4. 5. 6. ch4 21.0 c x5 x1 16 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 17

18 DEN-GT VI.GP.O2.02 / LUK40900 Danfoss District Energy

10.0 Declaration 10.1 Declaration of conformity Declaration of compliance We: Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds do hereby on our own responsibility declare that the following products: Termix Substations covered by this declaration is in conformity with the following directive(s), standard(s) or other normative document(s), provided that the products are used in accordance with our instructions. EU Directives: Machinery Directive 2006/42/EEC EN ISO 14121-1 Safety of machinery - Risk assessment EN 60204-1 Safety of machinery - Electrical equipment of machines EMC Direct ive 2004/108/EEC EN 61000-6-2 2007 Electromagnetic compatibility - Generic standard: Immunity industry EN 61000-6-3 2007 Electromagnetic compatibility - Generic standard: Emission for residential, commercial and light industry PED Directive 97/23/EEC All substations that falls under Article 3.3 and category 1 shall not be CE-marked according to this directive, however all essential safety requirements from the PED Directive 97/23/EEC are followed to ensure hydraulic safety This declaration is immediately annulled, if the product is interfered with in any way, which interferes with the above mentioned directives and standards, without the written consent from Gemina Termix A/S. 2010.01.05 Sunds Time and place Lars Ginnerup Responsible for quality Danfoss District Energy VI.GP.O2.02 / LUK40900 DEN-GT 19

Produced by Danfoss A/S 01/2012