Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Similar documents
A Novel Approach for the Thermal Management. of PC Power Supply

A study of Transient Performance of A Cascade Heat Pump System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Optimisation of cooling coil performance during operation stage for improved humidity control

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

HVAC Water chiller selection and optimisation of operation

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Computing Services Center

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Implementation of the Laboratory Air Handling Unit Systems (LAHU)

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

MD and Its Impact on Lab Facilities

Comfort and health-indoor air quality

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

ASHRAE JOURNAL ON REHEAT

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

AN EXPERIMENTAL INVESTIGATION INTO THE EFFECT OF THERMOSTAT SETTINGS ON THE ENERGY CONSUMPTION OF HOUSEHOLD REFRIGERATORS

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Study on an environmental simulation system of low/high temperature. for great space

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

Dehumidifying with Dedicated Outdoor Air

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance Measurement of R32 Vapor Injection Heat Pump System

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Active desiccant integration with packaged rooftop HVAC equipment

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Don t Turn Active Beams Into Expensive Diffusers

City of Duluth Festival Center 04/25

CHAPTER 4. HVAC DELIVERY SYSTEMS

Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Purdue e-pubs. Purdue University

Development of the San Ace Airflow Tester - A Measuring Device for System Impedance and Operating Airflow of Equipment

Civil Engineering Building

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Design of Multi-Sensors Cooperation Control System for Intelligent Building

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Specific Energy Consumption of Heat Pump Drying System

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Bench Top Cooling Tower H893

Evaluation study of the performance of dual core energy recovery system for dwellings in the Arctic

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

APC APPLICATION NOTE #109

OPTIMISATION OF NOZZLE ARRANGEMENTS ON DESCALING HEADERS. Jürgen W. Frick Lechler GmbH D Metzingen / Germany

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Cold Weather Operation Of Cooling Towers

How to ensure Thermal Comfort in buildings with CFD

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Transcription:

Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang Weng a, Che-Ming Chiang b a Department of Energy and Refrigerating Air-Conditioning Engineering, National Taipei University of Technology, Taipei, Taiwan b Department of Architecture, National Cheng-Kung University, Tainan, Taiwan Received 27 December 2005; received in revised form 5 June 2006; accepted 17 June 2006 Abstract An innovative low temperature differential variable air volume fan-coil unit (LTD-VAV FCU) was developed to improve the defects of variable air volume (VAV) and cold air distribution energy-saving technologies. A test bench and procedures according to its unique air supply features were established to investigate the energy-saving and IAQ improving potential experimentally. The experimental results of the prototype indicated the supply air volume can be continuously varied between 0.09 m 3 /s (200 CFM) and 0.38 m 3 /s (813 CFM), controlled by the bypass damper giving an air supply/air return temperature difference from only 2.30 to 8.09 8C. The effect of reducing the supply/return air temperature differential not only makes people feel comfortable, but also improves the cold draft and condensing at the outlet generated by ordinary air supply method. In addition, continuous capacity variations range from 0.45 kw (383 kcal/h) to 5.29 kw (4550 kcal/h) rendering to achieve the effect of comfort at a stable indoor thermal condition. Moreover, the temperature difference of chilled water ranges from 0.42 to 5.05 8C, the chiller plant not only can be unloaded at a low temperature difference to enhance energy-saving, but also complement other areas for multi-area application. # 2006 Elsevier B.V. All rights reserved. Keywords: LTD-VAV FCU; Energy-saving; Cold air distribution; IAQ; Cold draft 1. Introduction Energy consumption and huge emission of waste heat have already caused serious global problems like the global warming and hot island effects and therefore become urgent issues in the international community. Since HVAC has become an indispensable facility in human life, energy economy and environmental friendly air conditioning will be the trend in the future to accomplish the goal of sustainable existence with the ecology and the earth. The VAV supply system has become quite popular on the market, thanks to its improvements in critical defects of a typical constant air volume (CAV) one. The air conditioning capacity of both VAV and CAV systems are both controlled by the supply air volume. When the air circulation rate or air age is inconsistent with the load needed in an occupied room, certain problems occur. Five major problems are: * Corresponding author. Tel.: +886 2 27712171; fax: +886 2 27314919. E-mail address: mtke@ntut.edu.tw (M.-T. Ke). (1) bad mixing of the circulating air and the indoor air, (2) insufficient outdoor air circulation, (3) dumping happens when air volume is inadequate leading to local air circulation only, (4) the ventilation rate reduces as the load decreases, (5) the air supply temperature reduces abruptly when the load decreases. A greater inlet and outlet air temperature difference makes human bodies become uncomfortable extremely (cold draft effect). Accordingly, an innovative concept of a new generation air conditioner, LTD-VAV FCU, is proposed in this research. The applications of VAV technology are introduced in detail in ASHRAE handbook [2]. Hung et al. [4] studied the effect of flow controllers on VAV system performance by simulations and field measurements. They concluded that the flow controllers can modulate the supply air to provide a stable air temperature. Zaheer-Uddin and Zheng [6] found that there is an optimal air supply temperature with and return air used in a climate where the relative humidity is high. Engdahl and Johansson [3] optimized the air supply temperature of a VAV 0378-7788/$ see front matter # 2006 Elsevier B.V. All rights reserved. doi:10.1016/j.enbuild.2006.06.011

M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 703 system theoretically by minimize the system energy use. Ke [5] proposed a variable-power VAV FCU and established a test bench and experimental method to evaluate and rate its energysaving potential. Beside this research currently there are few published literatures or reports about VAV FCU. Not to mention on the present LTD-VAV FCU. Therefore, this study proposed a standard test procedure in according with the unique features of LTD-VAV FCU and performed detailed ratings of its operation capability and energy-saving efficiency. 2. LTD-VAV FCU The design principle of the LTD-VAV FCU is shown in Fig. 1. There are two air return ways inside the unit. One is the primary air, Q A, which the return air passes by the cooling coil for heat exchange. The other is the bypass air, Q B, which the return air is drawn through the variable opening bypass damper and goes into the mixing chamber directly. These two air sources are mixed evenly in the mixing chamber by the supply fan to become the mixed air, Q T (Q T = Q A + Q B ), and provide air supply required in an occupied space. As the traditional VAV system may cause discomfort for the people indoors while running at a low load, the variable speed fan and the variable opening damper of the LTD-VAV FCU may adjust the primary air volume Q A automatically under low load running. Thus, cooling capacity and load tend to be balanced and the bypass air volume Q B is increased simultaneously to maintain the air supply volume Q T as desired. Accordingly, the mixing rate of the indoor air and air distribution can be maintained. Furthermore, the return air of the room temperature is brought in by the bypass damper and enforced to mix with the cold air passing by the dry cooling coil to increase the air supply temperature and to minimize the temperature difference between air supply and indoor air, which prevents the cold draft effect and discomfort resulted from a tremendous supply air temperature drop as well as larger supply/return air temperature differential by a low air volume supply at a low load running. Not being limited to air supply or ventilation volume, the total air circulating rate and the ventilation rate of the LTD-VAV FCU can be controlled by the variable speed fan and the variable opening damper independently in compliance with air-conditioning requirements. The capacity is automatically adjusted by the primary air in accordance with the cooling load. Consequently, the demand for indoor air circulation or ventilation can be met. Besides, better dehumidifying effect will be achieved as the FCU is running at a low load, the inlet and outlet temperature difference of the cooling water reduces significantly and the apparatus dew point (ADP) lowers when the setting temperature is reached. Air supply and return temperature difference is therefore lowered and the energy consumed satisfies the cooling load exactly; i.e., the most healthy and comfortable environment is created at the lowest energy consumption. The LTD-VAV FCU system presented in this research is based on a new concept of low temperature differential air supply, which not only copes with the requirements for comfort and health, but also saves energy and achieves the goal of environmental friendliness. 3. Experimentation and measurement instruments Currently, there is no testing standard published regarding the VAV fan-coil units. Various kinds of testing standards regarding the fan-coil units including ASHRAE s standard were established based on the CAV FCU. At the present time, ANSI/ASHRAE 79-2002 is the most popular and widely accepted testing standard [1]. This research established experimentation including equipment considerations, testing platform, laboratory requirements according to the requirements with this standard and the VAV testing method [5] as reference. An environmental control room and experiment platform was therefore established as shown in Fig. 2. Required environmental conditions at a constant temperature and humidity for testing are maintained to conduct a series of parametric experiments. Strict requirements for measurement instruments specified by ASHRAE are complied. A set of nozzle and differential pressure measurement system is applied to measure the air volume as well as air temperature and humidity. Various instruments and apparatuses adopted in this testing experiment are listed in Table 1. All of the measurement data will be collected in the computer by the data acquisition system simultaneously for follow-up reduction and analysis. Fig. 1. Schematic diagram of LTD-VAV FCU.

704 M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 Fig. 2. Layout of environmental control room and experiment platform. 4. Experimental procedure First, the test environment in the laboratory is to maintain the dry-bulb temperature (DB) at 27.0 0.2 8C and the wet-bulb temperature (WB) at 19.5 0.2 8C. The chilled water circulating pump is actuated to control the inlet chilled water at a temperature of 7.0 0.2 8C and a flow rate of 2.5 10 4 1.67 10 5 m 3 /s. Meanwhile, the standard wind tunnel experiment equipment is adjusted to maintain an external static pressure of 0 0.05 Pa. Upon stabilizing all testing requirements, the bypass damper of the LTD-VAV FCU is opened at 08, 308, 608 and 908 separately before adjusting speed of the fan motor from minimum to maximum in order. When air supply of the LTD- VAV FCU becomes steady, data of air supply volume, power consumption, temperature/humidity at the air inlet/outlet, chilled water flow and the chilled water temperature at the inlet and outlet of the LTD-VAV FCU with different opening angles of the bypass damper and fan speed were measured and recorded in the computer. The experiment flowchart is indicated in Fig. 3. 5. Results and discussion 5.1. Bypass damper opening at 08 Performance test of the LTD-VAV FCU with the bypass damper opened at 08 is mainly to simulate air supply fully provided by air return that passes by the cooling coil when the bypass damper is shut with Q B = 0 and Q A = Q T. At this time the supply air volume is controlled by the continuously variable speed fan motor. The experimental results are shown in Figs. 4 and 5. When the maximum air volume is 0.36 m 3 /s (788 CFM) with an input power as 173 W, the cooling capacity is 5.29 kw at an air supply temperature of 15.3 8C. The chilled water leaving temperature is 12.05 8C and the temperature difference between the inlet and the outlet of chilled water is 5.05 8C. When the air volume is minimized to 0.09 m 3 /s (200 CFM), Table 1 Instruments and accuracy used in present study Measuring item Instrument (brand) Approximate accuracy Remark Velocity Hot-wire anemometer (TESTO) (0.03 m/s 4% of mv) Pitot tube (TESTO) (0.3 Pa 0.5% of mv) Flow rate Nozzle and differential pressure measurement system 0.5 2.0% Air side Magnetic flowmeter (YOKOGAWA) 1% Water side Pressure Precision pressure probe (TESTO) (0.3 Pa 0.5% of mv) Inclined manometer (Dwyer) Temperature Liquid-in-glass thermometers 0.05 8C Resistance thermometers (TESTO) 0.3 8C Humidity Compact transducer (capacitive humidity sensor) 2%RH Power (HIOKI) 0.3% Stroboscope (SHIMPO) 0.2 rpm (200 4000 rpm)

M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 705 Fig. 3. Test procedures for rating LTD-VAV FCU. power consumed is 37 W, cooling capacity is down to 0.56 kw and the supply air temperature is 12.4 8C. The chilled water leaving temperature is 9.2 8C and the temperature difference between the inlet and the outlet of chilled water is reduced to 2.2 8C. These experimental data indicate the performance features of the LTD-VAV FCU equal those of the VAV-FCU when the damper opening is at 08. The capacity adjustment feature helps the VAV system supply the air volume in compliance with the required capacity; i.e., the cooling capacity and the load are balanced automatically for energy economy. However, as the capacity is still confined to the air supply volume, the cold draft effect and dumping may occur possibly when running at a low load. Fig. 4. Performances of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 08). Fig. 5. Temperature variations of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 08).

706 M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 When the supply air volume reduced to 0.09 m 3 /s (200 CFM), fan power consumption was 32 W. As the bypass effect was enhanced causing airflow resistance reduced, power consumed was less than that having the bypass damper opened at 08. Nevertheless, the cooling capacity was reduced to 1.26 kw, which accounted for only 24.2% of full capacity. The air supply temperature was 20.1 8C and the air supply temperature difference reduced to be 6.9 8C, which was significantly lower than 14.6 8C when the damper was opened at 08. Apparently, control of the bypass damper indeed may put the ideal of low temperature differential air supply into practice, which not only improves the defects like the cold draft effect and condensing/dewing at the outlet, but also modulates the chilled water temperature difference between 1.2 and 3.1 8C alleviating the chilled water loads and achieving the benefit of energy economy. Fig. 6. Performances of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 308). 5.2. Bypass damper opening at 308 Results of the performance test with the bypass damper opening at 308 are shown in Figs. 6 and 7. As the damper opened, airflow resistance increases. When the maximum air volume was 0.36 m 3 /s (788 CFM) at this time, fan power consumption increased to 188 W and the air supply capacity, due to the bypass effect, reduced to 3.59 kw, which was 67.8% of the capacity with the damper opened at 08. It is obvious to see that the cooling capacity is no longer limited to the air supply volume like a traditional air supply system. Moreover, the air supply temperature rises to 18 8C, the chilled water leaving temperature is 10.1 8C and the chilled water temperature difference to 3.1 8C, which helps save energy on the chilled waterside. 5.3. Bypass damper opening at 608 Experimental results of the performance test with the damper opening at 608 are shown in Figs. 8 and 9. When the LTD-VAV FCU was running at the maximum air volume of 0.38 m 3 /s (810 CFM) at this time, fan power consumption was 188 W and the cooling capacity was 2.93 kw. The supply air temperature was 23.2 8C, the chilled water leaving temperature was 9.8 8C and the chilled water temperature difference was 2.8 8C. When the air volume was reduced to the minimum of 0.09 m 3 /s (200 CFM), fan power consumption was 32 W and the cooling capacity was 0.56 kw. At this time the supply air temperature became 24.3 8C and the chilled water temperature difference was reduced to 0.54 8C. Accordingly, the performance with the damper opened at 608 is similar to that with the damper opened at 308. The bypass effect increases significantly as the damper is opened wider. The cooling capacity at the maximum air volume was 53.8% of the full capacity and was only 10.8% of the capacity when the air volume was at Fig. 7. Temperature variations of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 308). Fig. 8. Performances of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 608).

M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 707 Fig. 9. Temperature variations of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 608). minimum. The air supplied and returned temperature difference ranges from 2.7 to 3.8 8C. The effect of low temperature differential air supply was enhanced significantly as well. These experimental results indicate plenty of problems caused by a typical VAV-FCU running at a low load at the outlet can be improved by the LTD-VAV FCU presented here. The chilled water temperature difference can be reduced to 0.54 8C due to reduction of the cooling capacity, which is quite suitable for multi-area central chilled water occasions since the loads of the chilled water plant can be relieved and complementary capacity among areas with different loads may be balanced. 5.4. Bypass damper opening at 908 Results of the performance test with the damper opened at 908 (vertical) are illustrated in Figs. 10 and 11. When the LTD- Fig. 11. Temperature variations of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 908). VAV FCU was running at the maximum air volume of 0.38 m 3 /s (813 CFM) at this time, power consumption was 188 W and the air cooling capacity was reduced to 2.23 kw, which was 42.6% of the standard capacity only. The air supply temperature was 23.8 8C and the chilled water outlet temperature was 9.13 8C with a temperature difference of 2.13 8C. When the air volume was reduced to the minimum 0.09 m 3 /s (200 CFM), power consumed was 40 W and the air cooling capacity was 0.45 kw, which merely accounted for 8.5% of the standard capacity. The outlet air temperature was increased to 24.5 8C and the chilled water outlet temperature was reduced to 7.42 8C with a reduced temperature difference of 0.42 8C. Accordingly, the air supplied and returned temperature difference at a damper angle of 908 was between 2.5 and 3.2 8C and the cooling capacity was modulated from 8.5 to 42.6% of the standard capacity. It is obvious to see that the cooling capacity and the air supply volume can be controlled separately, which not only improves the limitation to the air (or ventilation) volume for a typical CAV system, but also achieves the energy economy benefit of the VAV system, thanks to its modulation feature by over 90%. 6. Conclusion Fig. 10. Performances of present LTD-VAV FCU under various supply air volumes (bypass damper opening at 908). To correct the defects of energy saving and indoor comfort found in traditional air supply system, an LTD-VAV FCU prototype was developed and an experimental platform for detail performance rating was designed and evaluated in this research. The parametric experimental results indicate the air supply and return temperature difference can be ranged from 2.5 to 11.7 8C by controlling the bypass damper and the fan motor, causing the low temperature differential effect to improve the cold draft effect at a low air supply volume and condensing/dewing at the outlet when air is supplied at a low temperature found in a typical VAVor cold air distribution system. The cooling capacity and the air volume can be adjusted between 0.45 and 5.29 kw with a variable air volume of 0.09 0.38 m 3 /s (200 813 CFM). The inlet and outlet temperature difference of chilled water ranges from

708 M.-T. Ke et al. / Energy and Buildings 39 (2007) 702 708 0.42 to 5.05 8C. When the temperature difference is lowered, the load of the chilled water plant can be reduced to promote energy economy and capacities in multiple areas may be complemented. Besides, the energy consumed by the fan motor ranges from 30 to 188 W, which can be modulated to develop the energy-saving effect. These experimental results prove that in addition to the energy-saving feature found in a typical VAV system, the LTD- VAV FCU proposed in this research may control the cooling capacity and the air supply (or ventilation) volume independently via the variable opening bypass damper and the variable speed fan motor to improve the shortcomings found in a traditional CAV system. Moreover, the ventilation volume can be adjusted spontaneously according to the zone requirements and load changes to provide a most healthy and comfortable environment for human bodies at the lowest energy required. Acknowledgements This research was conducted with financial support from the National Science Council of R.O.C. through Grant No. NSC 93-ET-7-027-003-ET. The authors would also like to acknowledge the contribution of Mr. M.C. Tsai to some of the experiments. References [1] ASHRAE, Methods of Testing for Rating Room Fan-Coil Air Conditioners, American Society of Heating, Refrigerating and Air-Conditioning Engineers (ANSI/ASHRAE Standard 79-2002), Atlanta, GA, 2002. [2] ASHRAE, ASHRAE Handbook Application, Chapter 37, SI ed., American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA, 2003. [3] F. Engdahl, D. Johansson, Optimal supply air temperature with respect to energy use in a variable air volume system, Energy and Buildings 36 (3) (2004) 205 218. [4] C.Y.S. Hung, H.N. Lam, A. Dunn, Dynamic performance of an electronic zone air temperature control loop in a typical variable-air-volume air conditioning system, HVAC&R Research 5 (4) (1999) 317 337. [5] M.T. Ke, Design of test method and detailed ratings of variable air volume fan-coil units, Building and Environment 37 (2002) 447 453. [6] M. Zaheer-Uddin, G.R. Zheng, A VAV system model for simulation of energy management control functions: of normal operation and duty cycling, Energy Conversion and Management Journal 35 (11) (1994) 917 931.