Smoke Detector Testing

Similar documents
Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

OH110, OP110, HI110 Automatic fire detectors

OH110, OP110, HI110. Automatic Fire Detectors. Automatic Fire Detector For collective and conventional detector lines

OOH740-A9-Ex Multi-sensor fire detector

OOH740-A9-Ex Multisensor fire detector

FDOOT241-A9-Ex Multisensor fire detector

Desigo Fire Safety intelligent detectors for complete safety

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

A Building Manager s Guide to Maintaining Fire Code Compliance

Intelligent Detection Devices

Model OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors

ARCHITECT AND ENGINEER SPECIFICATIONS

OOH740, OOHC740 Automatic fire detectors

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

SMOKE ALARM SUMMIT Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager

COMITÉ EUROPÉEN DES ASSURANCES

FDOOT241-A3, FDOOT241-A4, FDOOT241-A5, FDOOT241-A9, FDOOT241-8

THE NEXT GENERATION IN VISIBILITY SENSORS OUTPERFORM BOTH TRADITIONAL TRANSMISSOMETERS AND FORWARD SCATTER SENSORS

FDOOT221, FDO221, FDT221

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Filtrex A Smoke Detector for Difficult Environments

Fire Safety Basics II: Detection & Warning Systems

OH720, OP720, HI720, HI722

InstrumentationTools.com

CerberusTM. PRO intelligent protection. A comprehensive fire protection system. Answers for infrastructure.

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

Fire Detection System: An Overview

TrueAlarm Smoke Detectors

FDOOT241-9, FDOOT241-A, FDO241, FDT241

LEARNING SPECIAL HAZARD DETECTION TYPES

EXTINGUISHING SYSTEM DETECTION AND CONTROL

A P P L I C A T I O N S G U I D E. Single-Ended Reflected Beam Smoke Detector

Chapter 1. Introduction

Presented at 6 th Pipeline Technology Conference Hannover, Germany April 4-5, 2011

Smoke detection in hazardous areas:

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

UL268 7 th challenge with single infrared smoke detector

Carbon Monoxide Alarms Smoke and Carbon Alarms Upgrade Requirements for Single and Two Family Dwellings

Intelligent Earliest Warning Aspirating Fire Detector

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

Consultant Specification AGILE Wireless Fire Detection System

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

ISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Fact File 66. Guide to Beam Smoke Detectors

Chapter 17, Initiating Devices

ALK-V PHOTOELECTRIC SMOKE SENSOR

Intelligent Signature Series Analog Detection

Exercise 1. Introduction to Sensors EXERCISE OBJECTIVE

Directories. B.1 Keyword Directory B.2 Tables B.3 Figures B.4 End Notes Fire Safety Guide / Siemens Switzerland Ltd

Detection, and Suppression Systems

optical detector multisensor detector heat detector mounting bases product guide

ID50series. intelligent fire alarm panels

Laser Technology Smoke Detector

ICC CODE CORNER 2012 IFC Code & Commentary

Section PERIMETER SECURITY SYSTEMS

Australian Standard. Fire detection and alarm systems. Part 6: Carbon monoxide fire detectors using electro-chemical cells

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

ISO INTERNATIONAL STANDARD

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Conventional Detectors

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

Loss Prevention Standard

LaserFOCUS VLF-250 Engineering Specification

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

-Industrial. W hen All Else Fails... Difficult Applications. The Only TRULY Industrial Air Sampling Detector For Hostile and Difficult Environments

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

Draft for Public Comment Australian Standard

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand.

Leak Detection Systems. Workshop UNECE / Berlin. Ted Smorenburg SABIC Pipelines Netherlands

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

Technician Tools CAN/ULC-S CAN/ULC-S537-13

I N T E L L I G E N T A S P I R A T I N G. Intelligent Aspirating Fire Detector. Intelligent Earliest Warning Aspirating Fire Detector

Notifier by Honeywell: SMART Detection. SMART Detection. The Ultimate in False Alarm Technology...Make the SMART choice

SD119 Range of Conventional Smoke and Smoke/Heat Detectors (refer to attached appendix for details and conditions)

Fire protection for emergency power supply

GM Ultrasonic Gas Leak Detection Gas Detection at the Speed of Sound. How fast does your Gas Detection System detect leaks?

TrueAlarm Analog Sensing

FiberSystem. Fiber Optic Linear Heat Detection for Special Hazard Applications

Multi-Criteria Fire Alarm (Mcfa)

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

Analogue Detectors. Series 200 plus

Meeting NFPA standards for

SEC Millenium Carbon Dioxide Gas Detector

DT1101A / DT1102A / DO110xA Automatic fire detectors

Dräger PIR 7200 Toxic Gas Detection Transmitter

Research on Evaluation of Fire Detection Algorithms

Committed to security

ISO INTERNATIONAL STANDARD. Fire detection and alarm systems Part 3: Audible alarm devices

Model : LPSA-40A Please read this manual carefully before using the instrument Labnics Equipment

Cerberus PRO intelligent fire protection. A comprehensive portfolio of innovative and industry-leading technology.

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

Flame Detection Jon Sarfas

INTERNATIONAL STANDARD

Are You Prepared? The impending impact of Code on Servicing Security Systems

GASSONIC Ultrasonic Gas Leak Detection. How fast does your Gas Detection System detect leaks? Because every life has a purpose...

The Worldwide Use of Fire Sprinklers

TacBio: A UV-based Biological Aerosol Detector. TacBio Overview Page 1

Transcription:

Smoke Detector Testing Allen Hess CFAA Presentation April 2011 1 Building Technologies

Agenda Requirements Consumer Needs Challenges with Industry Acceptance How siemens a Detector sans italic Works Effects siemens of sans Time black on detector performance Maintenance Best Practices Conclusion Building Technologies

What our Standard Prescribes Building Technologies

What prescribes the testing and maintenance of Smoke detectors? CAN/ULC-S536-04 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS... 4 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1 General 5.7.4.1.1 Each smoke detector shall be visually inspected for cleanliness. When required, cleaning shall be in accordance with the manufacturer s recommendations. Ensure detector can and is operating 5 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1 General 5.7.4.1.1 Each smoke detector shall be visually inspected for cleanliness. When required, cleaning shall be in accordance with the manufacturer s recommendations. 5.7.4.1.2 Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instructions. Ensure physical operability 6 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1 General 5.7.4.1.1 Each smoke detector shall be visually inspected for cleanliness. When required, cleaning shall be in accordance with the manufacturer s recommendations. 5.7.4.1.2 Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instructions. 5.7.4.1.3 siemens sans Each bold smoke detector shall be tested to confirm that it is siemens within sans its italic rated operating range using a test method described siemens in Clause sans italic 5.7.4.1.6. bold (Refer to Appendix E3.1, Field Device siemens Testing-Legends sans black and Notes.) Ensure calibration is within operating range and will respond as early as required 7 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1 General 5.7.4.1.1 Each smoke detector shall be visually inspected for cleanliness. When required, cleaning shall be in accordance with the manufacturer s recommendations. 5.7.4.1.2 Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instructions. 5.7.4.1.3 Each smoke detector shall be tested to confirm that it is within its rated operating range using a test method described in Clause 5.7.4.1.6. (Refer to Appendix E3.1, Field Device Testing-Legends and Notes.) Corrective Action 5.7.4.1.4 siemens sans A smoke black detector whose sensitivity is not within the required operating range shall be cleaned, retested in accordance with Clause 5.7.4.1.3, and if still not within its rated sensitivity, replaced with a compatible smoke detector. (Refer to Appendix E3.1, Field Device Testing-Legends and Notes.) 8 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1 General 5.7.4.1.1 Each smoke detector shall be visually inspected for cleanliness. When required, cleaning shall be in accordance with the manufacturer s recommendations. 5.7.4.1.2 Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instructions. Provide evidence 5.7.4.1.3 Each smoke detector shall be tested to confirm that it is within Siemens its rated sansoperating range using a test method described in Clause siemens 5.7.4.1.6. sans bold (Refer to Appendix E3.1, Field Device Testing-Legends and Notes.) 5.7.4.1.4 siemens sans A smoke italic boldetector whose sensitivity is not within the required siemens operating sans black range shall be cleaned, retested in accordance with Clause siemens 5.7.4.1.3, black and italic if still not within its rated sensitivity, replaced with a compatible smoke detector. (Refer to Appendix E3.1, Field Device Testing-Legends and Notes.) 5.7.4.1.5 Each smoke detector sensitivity measurement and if applicable, the cleaning date shall be recorded on the individual device record. (Refer to Appendix E3.1, Field Device Testing-Legends and Notes.) 9 Building Technologies

5.7.4 Smoke Detectors 5.7.4.1.6 Acceptable methods of determining the smoke detector sensitivity are: A Manufacturer s recommended test instrument, equipment, or method; B Installed control units or transponders designed to test the sensitivity of individual smoke detectors; or siemens C Calibrated black italic instruments that provide the operation as described in CAN/ULC-S529, Standard for Smoke Detectors for Fire Alarm Systems, for the purpose of testing smoke detector sensitivity. 10 Building Technologies

What Consumers Need Building Technologies

Role of Detection The six fire safety subsystems recognized in the SFPE Engineering Guide to Performance-Based Fire Protection Analysis and Design of Buildings are [2007]: Fire initiation and development Spread, control, and management of smoke Fire detection Fire suppression Occupant siemens sans behavior italic and egress Passive fire protection Fire detection is one of the six subsystems identified in the SFPE Guide and hence is an essential component for achieving fire safety goals 12 Building Technologies

Fire Development and Intervention Flashover Building Technologies

Consumers Needs Early Warning Benefit Cost Benefit Cost Detection Reliably Affordably Protect People and Valuables Building Technologies

What is this Issue? Building Technologies

Industry Feedback/Perceptions Test tools not Approved Testing Impractical Too many test tools Subjective siemens evaluation sans italic of values Devices will false alarm in time Tools too expensive Testing Meaningless Physical testing more relevant Recommendations not acted on 16 Building Technologies

How A Detector Works Building Technologies

Ionization Detector 18 Building Technologies

Ionization Detector 19 Building Technologies

Photo Electric Detector (Scattering) 20 Building Technologies

Photo Electric Detector (Scattering) 21 Building Technologies

Multi Sensor Photo Detector 22 Building Technologies

Automatic Smoke Detectors Improvements in Quality and Quantity ASA (False Alarm Immunity)... Newer Generation Mio. Pcs. 40 35 Backward scattering 30 25 20 15 10 5 1943 1953 1963 1973 1983 1993 2003 0 Building Technologies

ASA False Alarm Immunity 3 000 # of detectors per false alarm per year Neural smoke detector 2'500 2'000 1'500 1'000 siemens Standard black italic Smoke detector 500 0 Wide spectrum smoke detector Wide spectrum smoke detector Neural smoke detector System innovation Field statistics Lab results Standards requirements 24 Building Technologies

Effects of Time on Detector Performance Building Technologies

Environmental effects on detectors Artificial aerosols and non-typical fire Siemens phenomena sans Detector locking Sabotage Dust, fibers, insects High-grade, patented optic Selectable parameters and multi-criteria evaluation Arrangement of grid and labyrinth Vibration, shock Construction and material selection Corrosive vapors Humidity protected electronic, highgrade components innovative, highly integrated electronic circuitry Extreme Temperatures Electromagnetic interference 26 Building Technologies

Effects of time on conventional Ionization detectors Dirt builds up in chamber causing leakage Airborne dusts absorb ions decreasing current Reduces detection capability Creates false alarms Conclusion Without compensation or maintenance/cleaning: - most likely will experience increase in false alarms with time 27 Building Technologies

Effects of time on conventional Photoelectric detectors Dust accumulates on transmitter/receiver reducing signal Dirt builds up on labyrinth causing reflections Airborne dusts cause reflects light Reduces sensitivity to smoke Creates false signals Creates false signals Conclusion Depending on construction and environment photo detectors - may become less or more sensitive with time 28 Building Technologies

U.S. EXPERIENCE WITH SMOKE ALARMS AND OTHER FIRE DETECTION/ALARM EQUIPMENT 2007 Nuisance alarms were the leading cause of disabled alarms. Problems associated with smoke alarm age may Include: sensitivity drift, which refers to a shift in the range of visibility obscuration or particulate density that will activate the smoke alarm. Such a shift can mean either an increase in nuisance activations (if sensitivity increases) or a decreased ability to react promptly to real fires (if sensitivity decreases). 29 Building Technologies

Maintenance Best Practices Building Technologies

Detector Revision Process (Cleaning) Detector sensitivity after 4 years field exploration Production limits Detector sensitivity after revision process Production limits # Detectors siemens 10 sans 30% bold out of the limits Sensitivity [%/m] Optical components after 4 years field exploration # Detectors Sensitivity [%/m] Optical components after revision process 31 Building Technologies

Best Practices, Global Comparison Building Technologies

International Standards Comparison 33 Building Technologies

Conclusion Building Technologies

Conclusions Canadian detector testing and maintenance Standards are consistent with global standards. Calibration (Sensitivity) testing continues to be important to ensure performance. Canada is lacking in defined intervals for detector replacement Shorter interval for replacement would reduce both the relevance and challenge of sensitivity testing Need a Green solution for detector replacement siemens Need sans to demonstrate italic cost/benefit to industry and end consumer 35 Building Technologies

Thank you for your attention! Siemens AG 2009. All rights reserved 36 Building Technologies