FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

Similar documents
FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

FMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

Colibri. Automatic Tank Gauge CL6 Series Installation Guide

Fuel Management System Setup Guide

TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms

AUTOMATIC TANK GAUGES

Manual No: Revision: G. Sensor Products. Application Guide

Manual No: Revision: D. Sump Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Interstitial Liquid Sensor - Fiberglass Tanks

Manual No: Revision: J. Groundwater Sensor. Installation Guide

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Manual No: Revision: H. MicroSensor. Installation Guide

2 To 1 Sensor Input Box

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

AUTOMATIC TANK GAUGES

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

MODELS 304GC, 304GCX, 314GC, and 314GCX

Refrigerant Recovery Machine. Model No Operating Manual

Installation Electric Dryers Instructions 01

Teflon Rotary Drum Pump

INSTALLATION GUIDE Dual Fuel Ranges

Required Tools The following tools are required for the installation of the kit: Open-end Wrench Set Flat-tip Screwdriver Cross-tip Screwdriver

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual

MODELS ASHP, ASHH, ASUP, and ASUH

Table of Contents. Important Safety Instructions. WARNING: If the instructions contained in this manual are not followed

LS500 Auto Learn Line Leak Detection

Safe Operation Manual. Honeywell IQ Force Gas Detector

EW 40 Wireless Fan Control

M1500 SiteSentinel itouch Tank-Gauge Monitoring System Installation Guide. Part Number: M1500, Rev. 5

Getting Started Quick Reference Guide

Multi-Function Cooktop

Part#: 26B113 HEAVY DUTY CAST IRON ROTARY DRUM PUMP

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

C Electrical Connection Kit

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

Installation Manual INTEGRATED MONITORING SYSTEM.

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Installation Instructions Remote Blowers

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.com

INSTRUCTION MANUAL. Revised: July 2, 2017 DRAWING NO REV. A LC1000 SERIES INTRINSICALLY SAFE ALARM CONSOLE

BID-SPEC_INTEGRA_100 Rev. 0. Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System

INSTALLATION & OPERATING INSTRUCTIONS

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Hydraulic Crimping Systems

TLS Monitoring Systems

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

IMPORTANT SAFETY INFORMATION:

Automatic Water System Pump SERIES

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.ca

LGB Gas fired boiler

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

User s Manual and Operating Instructions

Please Read and Save These Instructions.

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

Variable Speed Flow Controller

2 INLET / HIGH HEAD DRAIN PUMP SYSTEMS MODELS , INSTALLATION INSTRUCTIONS PREINSTALLATION CHECKLIST

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

PO Box 827 Hawley, MN (218) Fax (218)

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

RK-05 Combustible Gas Transmitter Operator s Manual

GARAGE HEATER WITH REMOTE INSTRUCTION MANUAL MODEL: HA24-100E HA24-150E. Figure 1

FOOD WASTE DISPOSER INSTALLATION AND USE MANUAL

SiteSentinel Integra 100 /500 Automatic Tank Gauge System Installation Manual

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

Installation Instructions

OPERATING INSTRUCTIONS AND OWNER S MANUAL

CYLINDER NOT INCLUDED

Installation Guide. 15 W. Undercounter/Freestanding Nugget Ice Machine U L. Viking Range, LLC. 111 Front Street

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Dishwasher Installation Manual

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

STOP. SAFETY INFORMATION Please read and understand this entire manual before attempting to assemble, operate or install the product.

Dryer. User manual DV22K6800** DV22K A-00_EN (US)_ indd :15:41

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G

Installation Instructions

3M Benchtop Air Ionizer 963E. User s Guide

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

OPERATORS MANUAL FOR Mi-T-M CORONA DISCHARGE OZONE GENERATORS

Industrial Dehumidifier Operating Instructions. Model: VG 1500

User s Manual and Operating Instructions

Air Filter. Filter for Removing Dust and Drain in Compressed Air. Filter for Drain and Dust (Filtering Accuracy: 5µm)

KEROSENE FORCED AIR HEATER User s Manual & Operating Instructions

User s Information Manual

Residential Gas Hybrid Water Heater

Transcription:

FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information contained in this manual at the time of printing, we recommend that you refer to franklinfueling.com for the most current version of this manual. All product specifications, as well as the information contained in this publication, are subject to change without notice. Franklin Fueling Systems does not assume responsibility and expressly disclaims liability for loss, damage, or expense arising out of, or in any way connected with, installation, operation, use, or maintenance by using this manual. Franklin Fueling Systems assumes no responsibility for any infringement of patents or other rights of third parties that may result from use of this manual or the products. We make no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Copyright 2017 Franklin Fueling Systems, Madison, WI 53718. All world rights reserved. No part of this publication may be stored in a retrieval system, transmitted, or reproduced in any way, including, but not limited to, photocopy, photograph, magnetic, or other record, without the prior written permission of Franklin Fueling Systems. For technical assistance, please contact: Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Web: franklinfueling.com Telephone: USA and Canada: +1.608.838.8786, +1.800.225.9787 USA and Canada Technical Support: +1.800.984.6266 UK: +44 (0) 1473.243300 Mexico: 001.800.738.7610 China: +86.10.8565.4566 BRITESENSOR is a registered trademark and EVO is a trademark of Franklin Electric Company, Inc. 000-2084 r3

Contents Introduction...1 Conventions used in this manual...2 Operating precautions...3 Questions and concerns...4 Installation...5 Installing an FMP-HIS or FMP-HIS-XL sensor...5 Equipment required...5 Installation procedure...6 Installation notes...7 Electrical wiring...8 BRITESENSOR wiring...8 Universal Device Protocol wiring...8 Control drawing 1...9 Control drawing 2...10 Maintenance...11 Testing the sensor...11 Sensor location record...11

Intentionally Blank

Introduction The FMP-HIS sensor is an intelligent BRITESENSOR that is used to monitor the brine levels inside hydrostatic interstitial reservoirs of double-walled tanks. A low brine or high brine level are alarm conditions and indicate a leak in either the outer tank or the inner storage tank. The FMP-HIS-XL sensor is an extra long version of this sensor. 23 INCH (584.2 mm) FMP-HIS-XL/ FMP-HIS-XL-U Extra Long Hydrostatic Interstitial Sensor 20 INCH (508 mm) REF. FMP-HIS/ FMP-HIS-U Hydrostatic Interstitial Sensor 9.75 INCH (247.7 mm) Ref. 4 to 4.5 INCH (102 TO 114 mm) Normal Brine Level 12.5 inch (307.5 mm) 7.5 Inch (190.5 mm) High Brine Level 11.0 Inch (279.4 mm) High Brine Level 1.0 INCH (25.4 mm) Low Brine Level 6.25 TO 5.75 INCH (159 TO 146 mm) Normal Brine Level Datum 2.5 Inch (63.5 Mm) Max. Dia. [ Typ ] 2.38 Inch (60.5 Mm) DIA. [ TYP ] Both sensors have upper and lower magnetic reed switch floats, which detect changes in the interstitial reservoir brine level. The sensors use intrinsically safe (IS) leak detection circuits and are approved for use in Class 1, Division 1, Group D Hazardous Areas. 1

Like other BRITESENSORs, these sensors have a microprocessor that analyzes the environmental conditions at the sensor and transmits data to the Automatic Tank Gauge (ATG) console. The FMP-HIS sensors detect and communicate a HIGH BRINE alarm level, a LOW BRINE alarm level, and a NORMAL no-alarm state (lower float submerged and upper float dry). The ATG also transmits a specific sensor ID code. The FMP-HIS and FMP-HIS-XL are offered in two communication options: The original BRITESENSOR protocol. The new Universal Device Protocol (UDP). The BRITESENSOR protocol uses 3 wires and is compatible with the T1 Series, T5 Series, EVO 550, and EVO 5000 ATGs. The UDP uses 2 wires and is compatible with the EVO 200 and EVO 400 ATGs. Sensor Communication Method Compatible ATGs FMP-HIS BRITESENSOR protocol T1 Series, T5 Series, EVO 550, and EVO 5000 FMP-HIS-XL BRITESENSOR protocol T1 Series, T5 Series, EVO 550, and EVO 5000 FMP-HIS-U Universal Device Protocol EVO 200 and EVO 400 FMP-HIS-XL-U BRITESENSOR protocol T1 Series, T5 Series, EVO 550, and EVO 5000 Included with the sensor are: No-strip electrical wire connectors. 25 feet of cable (attached). Model ID tags. Cord-grip fittings (for connection to a weatherproof electrical junction box). A vented riser cap (model TSP-KV4) is required for this installation so the brine level can rise or fall (hydrostatically) along with atmospheric pressure without building up positive or negative pressures inside the interstitial area. Conventions used in this manual This manual includes safety precautions and other important information presented in the following format: NOTE: This provides helpful supplementary information. IMPORTANT: This provides instructions to avoid damaging hardware or a potential hazard to the environment, for example: fuel leakage from equipment that could harm the environment. CAUTION: This indicates a potentially hazardous situation that could result in minor or moderate injury if not avoided. This may also be used to alert against unsafe practices. WARNING: This indicates a potentially hazardous situation that could result in severe injury or death if not avoided. DANGER: This indicates an imminently hazardous situation that will result in death if not avoided. 2

Operating precautions Franklin Fueling Systems (FFS) equipment is designed to be installed in areas where volatile liquids such as gasoline and diesel fuel are present. Working in such a hazardous environment presents a risk of severe injury or death if you do not follow standard industry practices and the instructions in this manual. Before you work with or install the equipment covered in this manual, or any related equipment, read this entire manual, particularly the following precautions: IMPORTANT: To help prevent spillage from an underground storage tank, make sure the delivery equipment is well-maintained, that there is a proper connection, and that the fill adaptor is tight. Delivery personnel should inspect delivery elbows and hoses for damage and missing parts. CAUTION: Use only original FFS parts. Substituting non-ffs parts could cause the device to fail, which could create a hazardous condition and/or harm the environment. WARNING: Follow all codes that govern how you install and service this product and the entire system. Always lock out and tag electrical circuit breakers while installing or servicing this equipment and related equipment. A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accidentally turned on while you are installing or servicing this product. Refer to this manual (and documentation for related equipment) for complete installation and safety information. WARNING: Before you enter a containment sump, check for the presence of hydrocarbon vapors. Inhaling these vapors can make you dizzy or unconscious, and if ignited, they can explode and cause serious injury or death. Containment sumps are designed to trap hazardous liquid spills and prevent environmental contamination, so they can accumulate dangerous amounts of hydrocarbon vapors. Check the atmosphere in the sump regularly while you are working in it. If vapors reach unsafe levels, exit the sump and ventilate it with fresh air before you resume working. Always have another person standing by for assistance. WARNING: Follow all federal, state, and local laws governing the installation of this product and its associated systems. When no other regulations apply, follow NFPA codes 30, 30A, and 70 from the National Fire Protection Association. Failure to follow these codes could result in severe injury, death, serious property damage, and/or environmental contamination. WARNING: Always secure the work area from moving vehicles. The equipment in this manual is usually mounted underground, so reduced visibility puts service personnel working on it in danger from moving vehicles that enter the work area. To help prevent this safety hazard, secure the area by using a service truck (or some other vehicle) to block access to the work area. WARNING: Make sure you check the installation location for potential ignition sources such as radio waves, ionizing radiation, and ultrasound sonic waves. If you identify any potential ignition sources, you must make sure safety measure are implemented. 3

Questions and concerns In case of emergency, follow the procedures established by your facility. If you have questions or concerns about safety or need assistance, use the information below to contact Franklin Fueling Systems: Web: franklinfueling.com Telephone: USA and Canada: +1.608.838.8786, +1.800.225.9787 USA Technical Support: 1.800.984.6266 UK: +44 (0) 1473.243300 Mexico: 001.800.738.7610 China: +86.10.8565.4566 4

Installation Installing an FMP-HIS or FMP-HIS-XL sensor Equipment required TSP-DB1 epoxy seal kit for no-strip electrical connectors. (See step 1 of the "Procedure" section in this chapter.) This is optional and is recommended for sites where one or more of the following apply: The area is in a flood zone. The groundwater table is high. There is poor drainage Junction boxes are not used. Model TSP-KS unistrut mounting kit. This is optional and is recommended for mounting the sensors. ½ or ¾ inch NPT (National Pipe Thread, tapered), Rigid Metal Conduit (RMC), or nonmetallic (PVC) if allowed by local code. EYS seal fittings and epoxy to fill the fitting after operational testing. Weatherproof junction box, gasket, cover, and a ¾ to ½ inch NPT reducing bushing if you use ½" RMC. (See the ATG Installation Guide for recommended electrical junction boxes.) Wire: THHN, TFFN or THWN, 18 AWG: Red, White, & Black, or Alpha Cable # 58113, 0.131" (3.3 mm) OD, 1,500' (457 meters) maximum length. Use alpha cable 58113 with nonmetallic (PVC) conduit. Slip joint pliers. UL-classified thread sealant or pipe dope. Standard adjustable or pipe wrench for a 2" square fitting. TSP-KV4 vented riser cap (included with sensor). 5

Installation procedure WARNING: To avoid electrical shock hazards, make sure all power going to the ATG console is turned off, tagged, and locked-out at the power panel before doing any maintenance or installation work at the ATG console. Brine Fill Level Cover For 14 inch (35.56 cm) Min. Dia. Manhole Manhole FMP-HIS Sensor Interstitial Reservoir Double Wall Tank Vented Riser Cap W/cord Grip Concrete Slab Per NFPA 30 Clean Fill Material (Gravel Typical) Weatherproof Junction Box Compression Fitting (Cord Grip) Eys Seal Fitting 1/2 or 3/4 inch Conduit 4 inch (101.6 mm) Riser Pipe Brine Filled Interstitial Area Brine Fill Level: = 4 inches (102 mm) For Standard TSP-HIS Sensors, or = 6 inches (152 Mm) For Extra Long TSP-HIS-XL Sensors Vent Lever Thru Holes for Locking Cap 1. Install a manhole. 2. Install the conduit, EYS fittings, and weatherproof junction box. (See the diagram at the beginning of this procedure.) 3. Turn off power to the console. 4. Pull the sensor cable through the cord grip fitting at the junction box. (Leave enough cable to allow for the installation of the sensor in the interstitial area.) Before you pull wires, mark them to avoid confusion when you connect to the ATG console. 5. Tighten the cord-grip fitting at the junction box, trim the wires and cables in the junction box to a 6 8" (156 20 cm) length, and then splice the sensor and console cable and wires together (as shown in the diagram at the beginning of this procedure) for the appropriate communication type, BRITESENSOR or UDP. 6. Turn on power to the console. 6

7. Test the sensor: Remove the sensor from the brine solution. This should produce a Low Brine Alarm at the ATG console. Rotate the sensor with the cable down. This should produce a High Brine Alarm at the ATG console. If these tests produce the expected alarms, seal the EYS seal fittings with epoxy. 8. Turn off power to the console if you are going to install other devices. 9. Reinstall all safety covers and guards, as well as junction box gasket and covers. Use pipe-dope to seal all fitting threads. 10. Install the manhole cover. 11. Record the location where the sensor was installed in the "Sensor location record" at the end of this manual. You will need this information when you set up the ATG. 12. Turn on power to the console, and program the ATG. (For more information, refer to the documentation for your ATG.) Installation notes WARNING: Conduits must have EYS seal fittings installed in accordance with NFPA 70 (National Electric Code) and NFPA 30A (Automotive and Marine Service Station Code). If you do not to seal conduits in accordance with NFPA 30A, and NFPA 70, flammable vapors could travel through the conduit in the ATG console. An explosion could result causing property loss, serious injury, and death. CAUTION: Seal all threaded fittings and conduit connections so that there is a weatherproof seal in place during installation and maintenance. IMPORTANT: It is the installer s responsibility to comply with all applicable federal, state and local codes. Failure to do so may create an environmental hazard. IMPORTANT: You must install a weatherproof, electrical junction box inside each manhole. The junction box should be installed high on the manhole wall to prevent it from being submerged during heavy rains. Fill the bottom of the manhole with crushed stone to facilitate drainage. Do not cover the sensor or access bung hole with fill material it must remain accessible for sensor installation, service, and testing. Plan your conduit routing. Dig trenches as necessary to install conduit from each manhole junction box to the intrinsically safe (IS) knockouts at the ATG console. The conduit may enter the manhole from either the bottom or the side. You will need only one knockout when, inside the building, there is a junction box that you can use as a pull box to combine multiple sensor cables. 7

Electrical wiring Refer to your ATG installation documentation for sensor wiring information. BRITESENSOR wiring These sensors are compatible with T1 Series, T5 Series, EVO 550, and EVO 5000 ATGs. Blk 3 Wht +Red Blk 2 Wht +Red Blk 1 Wht +Red PWR (RED) IN (WHT) 3 Wires/cable from console 3-conductor cable from sensor GND (BLK) Note: The PWR (red) terminal is only used with 3-wire sensors Insert the unstripped wires fully into the self-sealing, no-strip electrical connector. Use slip-joint pliers and seat the black portion to make a good electrical connection TO 3-WIRE SENSOR Universal Device Protocol wiring These sensors are compatible with EVO 200 and EVO 400 ATGs. 3 Blk +Red 2 Blk +Red 1 Blk +Red PWR (RED) GND (BLK) 2 Wires/cable from console 2-conductor cable from sensor Insert the unstripped wires fully into the self-sealing, no-strip electrical connector. Use slip-joint pliers and seat the black portion to make a good electrical connection 8

Control drawing 1 Exia JJG Franklin Fueling Systems 9

Control drawing 2 0539 II 1 G IECEx UL 14.0086X Ex ia IIA T4 Ga DEMKO 14 ATEX 1372X JJG Franklin Fueling Systems 10

Maintenance Testing the sensor Dip the sensor in 2" (50 mm) of water, and remove it after one minute to produce a LOW BRINE alarm. Rotate the sensor 180 degrees (float up) to cause a HIGH BRINE alarm at the ATG console. Test the sensor for proper operation every year or as required by local code.. Sensor location record Sensor Channel Number/Notes 11

000-2084 r3