VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

Similar documents
VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN VITOLADENS 300-T Oil Unit condensing boiler 35.4 to 53.7 kw

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

VIESMANN VITOLADENS 300-C Oil condensing boilers 12.9 to 28.9 kw

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

Floorstanding Gas Condensing Boilers VITOCROSSAL 100

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Operating and service instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Gas condensing boilers 87 to 1400 kw. Technical guide. VITOCROSSAL 200 Type CM2. VITOCROSSAL 300 Type CM3. VITOCROSSAL 300 Type CT3U

VIESMANN. Service instructions. MatriX radiant burner. for contractors

Technical guide VITOMAX 200 HS. Notes on design and operation. Vitotec technical guide folder, register 1. File in:

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

Installation and maintenance instructions

WOLF GAS CONDENSING BOILERS COMFORTLINE

Uni 3000 F Output range 420 to 1850 kw. Oil/gas boiler. Installation and maintenance instructions for the contractor (2014/10) UK

Technical documentation. ComfortLine gas condensing boilers CGB-2(K) CGW-2 CGS-2 CSZ-2 NEW

Installation and maintenance instructions

Installation and service instructions for contractors Logano plus SB625. Burner shroud not available in UK and Ireland

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

VITOPLEX. Low temperature oil and gas fired boilers Rated output Vitoplex 100: 575 to 1750 kw Vitoplex 200: 90 to 560 kw Vitoplex 300: 80 to 1750 kw

Pellet Boiler VITOLIGNO 300-P. Test winner Good (2.1) Pellet boiler VITOLIGNO 300-P. In the test: 10 systems 1 winner

WOLF WALL MOUNTED GAS CONDENSING BOILERS COMFORTLINE

ENTROPIE boiler TT100-01

Installation and maintenance instructions

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Installation and maintenance instructions

ENTROPIE boiler TT300

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

Installation and maintenance instructions

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Sirius FS. Working towards a cleaner future

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

Installation and maintenance instructions

VIESMANN. Installation and service instructions VITODENS 100. for heating engineers

Technical Data Manual Model Nos. and pricing: see Price List

Steel Shell Boilers. Max-3 plus kw. Max-3 E & Max-3 condens E kw. CompactGas kw. SR-plus and SR-H plus kw

INSTALLATION AND OPERATION MANUAL

CAST IRON ATMOSPHERIC BOILERS

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Oil/gas boilers and low pressure hot water boilers up to 22 MW

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

VIESMANN. Service instructions VITODENS 200-W. for contractors

Installation and maintenance instructions

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

/2005 GB(EN) For the user. Wall-mounted condensing gas combi boiler Buderus /C, /C

Users manual. Buderus /29/43/60 and Buderus T25/29T25 H/V. Wall-mounted condensing gas boiler. For the user

5 YEAR ADVANCE PLUS WARRANTY. High efficiency condensing combi and system boilers

Operating instructions

Technical Data Manual Model Nos. and pricing: see Price List

For the user / for the installer. Instructions for Use and Installation. time SWITCH hour time clock

Service Instructions for use by heating contractor

Sirius WH. Working towards a cleaner future

VERY LOW TEMPERATURE CONDENSING UNIT Low NOx Class 5 MODELS SEASONAL EFFICIENCY A A A A A A A

Wall Hung Condensing Boilers. Working towards a cleaner future. heating specialists

Logamax plus GB172/GB172T. Heat is our element. Technical Guide Issue 2011/06. Fügen Sie auf der Vorgabeseite das zur Produktgruppe passende Bild ein.

Transcription:

VIESMANN VITOMAX -WS Rated heating output 1.75 to 11.63 MW Datasheet VITOMAX -WS Type M250 Oil/gas low pressure hot water boiler CE designation in accordance with the Gas Appliances Directive Permissible operating pressure 3 bar 5/2013

Specification Specification Rated heating output MW 1.75 2.33 2.91 3.49 4.65 5.82 6.98 8.14 9.30 11.63 Rated heat input MW 1.86 2.47 3.09 3.71 4.95 6.19 7.42 8.66 9.89 12.37 CE designation see page 6 Permiss. flow temperature *1 (= safety temperature) C 110 Pressure drop on the hot gas Pa 650 700 750 750 800 800 900 950 0 1050 side mbar 6.5 7.0 7.5 7.5 8.0 8.0 9.0 9.5 10.0 10.5 Shipping dimensions - Total length m 4.6 4.6 4.7 5.5 5.7 6.1 6.3 7.1 7.2 7.4 - Total width m 2.1 2.3 2.5 2.5 2.8 2.9 3.1 3.2 3.4 3.7 - Total height m 2.5 2.7 2.9 2.9 3.2 3.3 3.5 3.6 3.8 4.1 Foundation - Length m 4.1 4.1 4.2 4.9 5.1 5.4 5.6 6.4 6.5 6.7 - Width m 1.4 1.5 1.6 1.6 1.6 1.9 1.9 2.1 2.3 2.3 Dry weight *2 t 5.1 5.7 6.8 8.6 10.7 12.5 16.4 18.9 22.0 27.2 Boiler with thermal insulation Combustion chamber diameter 7mm 845 965 1083 1066 1166 1294 1382 1382 1475 1623 Combustion chamber length mm 3560 3560 3635 4400 4600 4940 5160 5930 6030 6 Boiler water content m 3 6.1 7.6 8.7 11.1 14.0 15.9 18.7 22.5 25.5 31.4 Connections Boiler flow and return PN 16 DN 150 250 250 250 300 300 300 Safety valve connector at the boiler, SIV1 PN 16 DN 65 80 80 125 125 150 150 150 at the distributor *3, SIV2 PN 16 DN - - - - - - - - - 2 DHW circulation pipe PN 16 DN 65 80 80 125 125 125 150 150 Drain PN 40 DN 40 40 40 40 40 40 - - - - PN 16 DN - - - - - - 50 50 50 50 Flue gas parameters *4 Temperature - at rated heating output C 150 - at min. heating output C Mass flow rate - for natural gas t/h 1.5225 x rated heat input in MW - for fuel oil EL t/h 1.5 x rated heat input in MW Required draught Pa/mbar 0 Flue gas connection - internal Ø mm 400 440 500 550 600 700 750 800 900 0 - external Ø mm 408 448 510 560 610 710 760 810 910 1010 Flue gas volume Combustion chamber and hot gas flues m 3 3.2 4.4 5.5 6.8 8.9 12.1 14.4 17.5 20.5 26.3 *1 The maximum achievable flow temperature is approx. 15 K below the permissible flow temperature (= safety temperature). *2 Deviations are possible, subject to order. *3 Distributors for fitting 2 safety valves with smaller nominal diameters are available as accessories. *4 Calculation values for sizing the flue system to DIN 4705 relative to 13 % CO 2 for fuel oil EL and 10 % CO 2 for natural gas. Flue gas temperatures captured as gross values at 20 C combustion air temperature. The details for partial load refer to 50 % of the rated heating output. Calculate the flue gas mass flow rate accordingly if the partial load differs from that stated (subject to operating mode). 2 VIESMANN VITOMAX -WS

Specification (cont.) d SIV e KR ML f KV KTH 270 R1/2 R3/4 STB KTH KTS g b a l SW s t o Øc 150 KAB R LV R ME R HL m n SCH r q ZR KOA uaga k h p E HL Caution hot surface! AGA Flue outlet (upon request also available as top exit version) E Drain connector HL Handhole KAB Boiler cover KOA Condensate drain R ½ KR Boiler return KTH Fem. connection R ½ for boiler thermometer KTS Fem. connection R ½ for boiler water temperature sensor KV Boiler flow LV Fem. test connection R ¼ ME Test port R ½ ML Manhole R Cleaning aperture SCH Inspection port SIV Boiler connector for safety valve STB Fem. connection R ½ for high limit safety cut-out SW Feedwater connector ZR DHW circulation pipe Dimensions Rated heating output MW 1.75 2.33 2.91 3.49 4.65 5.82 6.98 8.14 9.30 11.63 a mm 4520 4520 4595 5360 5560 6020 6240 7010 7110 7280 b mm 3830 3830 3905 4670 4870 5210 5430 6 6300 6470 c Ø mm 434 534 534 534 602 602 602 602 710 710 d mm 340 350 350 360 370 370 390 390 420 420 e mm 850 875 875 925 1050 1050 1150 1220 1330 1420 f mm 2415 2335 2410 3115 2950 3490 3590 4270 4230 4310 g mm 325 325 325 325 325 425 425 425 425 425 h mm 0 2 2380 2420 2680 2850 3020 3110 3300 3620 k mm 1 1300 1400 1400 1400 1700 1700 1900 2 2 l mm 700 700 800 800 800 900 900 900 0 0 m mm 1160 1235 1330 1360 1510 1610 1675 1705 1825 1975 n mm 2205 2405 2585 2625 2885 3055 3220 3310 3500 3820 o mm 2400 2600 2780 2820 3080 3250 3420 3510 3700 4020 p mm 295 335 240 255 340 335 360 460 465 495 q mm 605 600 670 640 725 750 765 805 815 855 r mm 1655 1790 1945 1995 2195 2370 2500 2580 2705 2945 s mm 400 435 465 495 577 600 640 685 730 815 t mm 535 610 670 675 770 830 875 890 950 1050 u mm 1 1190 1260 1320 1410 1550 1625 1720 1820 0 VITOMAX -WS VIESMANN 3

Specification (cont.) Recommended minimum clearances 600 () To facilitate installation and maintenance, observe the stated clearance dimensions; maintain the minimum clearances where space is tight (dimensions in brackets). 600 a 500 (400) 600 () A Boiler B Burner Rated heating output MW 1.75 2.33 2.91 3.49 4.65 5.82 6.98 8.14 9.30 11.63 a mm 3800 3800 3800 4600 4800 5 5300 6000 6000 6 Dim. a: This space in front of the boiler is required to enable the removal of the turbulators. Installation conditions Avoid air contamination by halogenated hydrocarbons (e.g. as contained in sprays, paints, solvents and cleaning agents) Avoid very dusty conditions Avoid high levels of humidity Prevent frost and ensure good ventilation Otherwise, the system may suffer faults and damage. In rooms where air contamination through halogenated hydrocarbons may occur, install the boiler only if adequate measures can be taken to provide a supply of uncontaminated combustion air. Pressure drop on the heating water side Boiler flow and return A DN 150 B DN C DN 250 D DN 300 60 Pressure drop in mbar 20 10 5 40 60 Flow rate in m³/h 400 600 0 4 VIESMANN VITOMAX -WS

Specification (cont.) Flue gas temperature and boiler efficiency Subject to the boiler heating output at a boiler water temperature of 80/60 C and a residual oxygen content in the flue gas of 3 % 160 150 150 145 96 Flue gas temperature in C (gas) 140 130 120 110 90 Flue gas temperature in C (oil) 140 130 120 110 90 A B 40 50 60 70 80 90 Boiler heating output in % relative to the maximum possible rated heating output 96 95 94.5 94 93 Boiler efficiency in % (oil) 95 94 93 Boiler efficiency in % (gas) A Flue gas temperature in C B Boiler efficiency in % (lower limits averaged across all boiler sizes) Delivered condition Boiler shell with burner plate, fitted cleaning door, flue outlet with cleaning aperture, fitted thermal insulation, fitted walk-on boiler cover. With transport protection. The cleaning equipment and the combustion chamber sight glass are supplied inside the combustion chamber. (Lower limits averaged across all boiler sizes.) Control unit versions For single boiler systems: With Vitotronic burner control panel For operation with a constant boiler water temperature or for a modulating boiler water temperature in conjunction with a control panel or an external control unit With Vitotronic burner control panel For modulating boiler water temperature For modulating boiler water temperature with mixer control up to two heating circuits For a single or multi boiler system: With Vitocontrol control panel For a constant boiler water temperature or modulating boiler water temperature, boiler sequence control and controlled or uncontrolled heating circuits including DHW heating according to customer requirements Operating conditions Requirements 1. Heating water flow rate None 2. Boiler return temperature (minimum value) *5 65 C 3. Lower boiler water temperature 75 C 4. Two-stage burner operation None 5. Modulating burner operation None Requirements 6. Reduced mode Not possible 7. Weekend setback Not possible For water quality requirements, see the technical guide to this boiler. *5 The technical guide (system examples) contains a relevant system example for the installation of a return temperature raising facility. VITOMAX -WS VIESMANN 5

Design information Installation of a suitable burner The burner must be suitable for the respective rated heating output and the pressure drop on the hot gas side of the boiler (see burner manufacturer's specification). Burners with a special design, e.g. rotary atomisers, can necessitate boiler conversions. We therefore recommend checking with the factory that your burner is compatible. The material of the burner head must be suitable for operating temperatures of at least 500 C. Pressure-jet gas burner The burner must be tested to EN 676 and be CE-designated in accordance with Directive 90/396/EEC and must conform to EN 12953-7. Burner adjustment Adjust the oil or gas throughput of the burner to the rated boiler heating output. Burner connection On request, the burner plate can be prepared at the factory. For this, please state the burner make and type when ordering. Otherwise, create the blast tube aperture and fixing holes on site in the blank plate supplied. Pressure-jet oil burner The burner must be tested and designated to EN 267 and must conform to EN 12953-7. Fuels Oil: Fuel oil EL to DIN 51603. These boilers are not approved for operation with fuel oil S (heavy oil). Gas: Natural gas and LPG in accordance with DVGW Code of Practice G 260/I and II or in accordance with local regulations. Alternative fuels on request. Further information on design/engineering See the technical guide to this boiler. Tested quality CE designation according to current EC Directives. Subject to technical modifications. Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com 6 VIESMANN VITOMAX -WS