Temperature Distribution of Rotary Heat Recovery Units

Similar documents
THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS

Heat Recovery Units. Heat Recovery 1

AIR HANDLING THERMAL CONDITIONS

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

ASHRAE JOURNAL ON REHEAT

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS

Adding More Fan Power Can Be a Good Thing

THE EFFECT OF ENTHALPY RECOVERY VENTILATION ON THE RESIDENTIAL INDOOR CLIMATE

Cooling the Data Center

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

An experimental study of the impact of tunnel suppression on tunnel ventilation

How to ensure Thermal Comfort in buildings with CFD

Air Handling Units. T F E.

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Residential ventilation concepts based on the idea of displacement airflow distribution

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

The Current (2017) State of the Art for Air Leakage in Ductwork

Material and rotor description.

Bill McCullough. Director ERV Products. Dallas, TX

Computing Services Center

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

HVAC Water chiller selection and optimisation of operation

VERSO Air Handling Units

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

This summarises results from our inspection of the Rendering Plant air extraction system at the Imlay meat works on 12 December 2013.

SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER

4.0 Mechanical Redesign

Trane CDQ Desiccant Dehumidification

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Ventilation System Description. September 8, 2000 HETA

Existing Mechanical System Operation

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Air Conditioning Clinic

APPLICATION, INSTALLATION, AND MAINTENANCE MANUAL CA2XRT, CA3XRT, CA4XRT

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

EU Air Handling Units with SEMCO EXCLU-SIEVE

Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume 17 Number 5 April, 2005

Big Board Rework. Joerg Nolte Ersa GmbH Wertheim, Germany

2. HEAT EXCHANGERS MESA

Heating and Air-Conditioning Testing II. Climatic Test Bench

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

REMOVAL OF AIR BORN MICRO-ORGANISM

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

Mikael Börjesson Product manager. Commercial air handling units Ventilation functionality Building management system integration

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

VERSO Air Handling Units

Purdue e-pubs. Purdue University

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Benefits Offered by Passive Dehumidification Wheel Speed Control

CHAPTER 4. HVAC DELIVERY SYSTEMS

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

WET POSITION BOOSTER FANS FOR REDUCED POWER CONSUMPTION AND OPTIMIZED ENVIRONMENTAL PERFORMANCE OF POWER STATIONS WITH FGD AND WET STACK

Don t Turn Active Beams Into Expensive Diffusers

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger

How to improve air cooler vacuum steam condensers performance in the field

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design

What is the correct type of fan: Axial, radial, diagonal?

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Understanding the different sources of undesirable moisture in HVAC systems can help prevent or solve moisture-related problems.

There are two devices used together for heating crude oil in petroleum refinery as in figure (1), and these devices are:

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Understanding Process Vacuum for Process Improvement

Measuring And Understanding Energy Efficiency

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

Air is our element. energy recovery our passion. Rotors overview. Quick guide GOST VDI 6022

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

Desiccant Cooling with Solar Energy

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Air distribution for clean rooms. Clever and flexible.

Environmentally Sound Solutions for Ventilation

Effect of Insulation on the Growth of Radish Plants- Cultivated Radish ( Raphanus sativus L.) Danielle Griggs, Meher Pandher, Avni Mehta, Meghan Royle

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Pharmaceutical Facility Design

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

Review on Waste Heat Recovery Techniques in Air Conditioning Application

11th Conference on Advanced Building Skins

Laboratory study of the effects of green roof systems on noise reduction at street levels for diffracted sound

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

Transcription:

Temperature Distribution of Rotary Heat Recovery Units Bjørn R. Sørensen, dr.ing. Narvik University College, P.O.Box 385, N-8505 Narvik, Norway Corresponding email: brs@hin.no SUMMARY This paper deals with measurements of temperature distribution of rotary heat recovery units. A special grid of thermocouples has been made to measure air temperature in equally distributed sampling points on each side of a heat recovery wheel. Air flow rates and the amount of recirculation air (leakage) were measured using a tracer gas. The results show that the temperature profile is generally dependent on both the rotational speed of the wheel and the flow rate. Measurements also show that the placement of temperature sensors in the duct can be significant, since wrong placements may lead to both faulty or non-optimized control of the units, and wrong readings of the temperature efficiency. Propitious sensor placements have been proposed. INTRODUCTION There are many types of air-to-air heat recovery units (HRU) which are in use in ventilation systems (see for instance Schild [1]). Rotary heat recovery exchangers are widely used, and the units are known for their high efficiency and trouble-free operation. Temperature efficiencies above 80% are not uncommon. For balanced ventilation systems, the recovered heat power can be at the same rate. Unfortunately these units are also infamous for transmission of polluted air from exhaust to supply. Due to the rotation of the device, there will always be a direct and indirect connection between exhaust and fresh supply air. Crosscontamination through rotary heat recovery units comes from two mechanisms; (1) Leakage, (2) Carryover. The former is dependent on the differential static pressure across the wheel, and the placement of supply and exhaust fans may affect its value significantly. The latter (carryover) occurs as a result of air being entrained within the wheel volume. Contaminated air is then carried into the other, clean air stream. The degree of carryover air is strongly dependent on whether the unit has a purge section or not. Rotor speed is normally relatively low and in a range of 3-15 rpm. The cross sectional temperature distribution on the supply or discharge side of a rotary HRU is in many cases non-uniform. This means that placement of temperature sensors for control or for calculation of energy transfer and efficiencies is crucial. SITE DESCRIPTION AND MEASUREMENT SETUP Flow and temperature measurements where performed in a laboratory test ventilation system (the heat recovery AHU part of the system is shown in figure 1). This is a ABB EC2000 unit with a non-hygroscopic rotary wheel. Flow rates where measured with a tracer gas. A tracer gas (SF 6 ) was released into the air, and concentrations upstream and downstream of the dosing points determined the flow rate and cross-contamination of the heat recovery unit (according to figure 2).

Figure 1. The AHU subsystem containing the rotary heat recovery unit Figure 2. Flow measurement setup and tracer gas sampling points, Eian/Sørensen [2] Figure 3. Temperature sampling points

The temperature measurement system (refer to figure 3) consisted of: Three grids of thermocouples on the intake and supply side (grid T1, T2 and T3), each containing 6 sample points (figure 3 and 4) Three grids of thermocouples on the exhaust and discharge side (grid A1, A2 and A3), each containing 6 sample points Temperature in the ducts T0, T4, A0 and A4. A NI1000 mean temperature sensor on the exhaust side (this sensor was not used in this study) Figure 4. Picture of a thermocouple grid in front of the rotary heat recovery unit. RESULTS AND DISCUSSION Flow rates Figure 5 shows the flow rates that were measured for different speeds of the fan and heat recovery unit. Figure 6 shows the percentage return air being recirculated to the supply side. Flow rate (m3/h) 1000 900 800 700 600 500 400 300 200 Flow rate - exhaust 100% rotary speed 50% rotary speed 0% rotary speed Cross contamination (%) 100 % 90 % 80 % 70 % 60 % 50 % 40 % 30 % 20 % 100% rotary speed 50% rotary speed 0% rotary speed 100 10 % 0 0 % 20 % 40 % 60 % 80 % 100 % Fan speed (% of max) 0 % 0 % 20 % 40 % 60 % 80 % 100 % Fan speed (% of max) Figure 5. Flow rates measured in the exhaust Figure 6. Cross contamination (%)

A large amount of recirculated return air was measured. The large amount of return air was mainly a result of the rotary HRU having no purge sector and an unfavorable placement of the fans in the system. This resulted in a low static pressure on the intake side of the HRU and a relative high pressure on the exhaust side, forcing air to cross to the supply side. The latter caused a 12-15% air recirculation. It was also noticed that the amount of recirculation increased significantly with increased speed of the HRU wheel. This indicates that carryover air stands for a large amount of total recirculation. Furthermore, at low fan speeds, the relative amount of recirculated air increased significantly. While the fans were running at only 20% of maximum speed, and the HRU was at full speed, there were almost no fresh outdoor air on the supply side (90% recirculation). Thus this confirms the importance of obtaining proper pressure conditions around the rotating wheel. The results also suggest that for VAV systems running on low fan speeds, the amount of return air can become very high and thus unacceptable. Measurements with the HRU not rotating show an almost constant amount of recirculated air (independent of fan speed). Hence, the increase of recirculation was mainly caused by carryover air in the rotating wheel. Furthermore, the amount of carryover air from the supply to the exhaust was quite noticeable, as can be seen in figure 5 (since flow rates on the exhaust side varied with the speed of the rotating wheel). Similar measurements were performed on the supply side of the HRU, showing that the ventilation system was very good balanced with respect to supply and exhaust flow rates. Temperature measurements Relative speed (%) 120 % 100 % 80 % 60 % 40 % 20 % 0 % Fan speed HRU w heel speed 0 20 40 60 80 100 Time (min) Figure 7: Fan and HRU wheel speeds (% of max) during temperature measurements Two measurements series were performed, each resulting in responses from altered fan speeds (0-100% of max, 20% step) and HRU wheel speeds (0%, 10%, 20%, 40%, 60% and 100% of max), see figure 7. The outdoor temperature was fairly constant around 0 C. Figure 8 shows the temperature measurements as a function of time from grid T2 (supply side, closest to the wheel) for measurement series 2. At a first glance, it is obvious that the temperature varied quite noticeable across the section/grid for a given fan and HRU wheel speed. If looking closer it is possible to see the variations in temperature due to the alternations of the wheel rotary speed. The most conspicuous temperature drops happened when the rotary HRU was shut down to 0% speed. When this occurred, the temperature on the supply side naturally dropped towards the outdoor temperature. In figure 9-12, the results have been arranged so that they correspond to the location of the actual sampling point. The two upper rows of graphs correlate to the grids on the supply side of the HRU wheel, grid T2 and T3, while the two lower rows of graphs correlate to the grids on the discharge side, grid A2 and A3. In addition, the duct temperatures (T4 and A4) are plotted on the supply and discharge graphs respectively. Since these sampling points are located away from the wheel (in the ducts), they are used as references to decide whether a

temperature value is too low or too high in the grids. Each graph has been numbered in accordance with the setup given by figure 3. The direction of the HRU is also shown. Figure 9 and 10 show steady state temperature levels (according to the variations in fan speed and wheel speed defined by figure 7) for each sampling point at 20% respectively 100% fan speed, as a function of the relative HRU wheel speed. Likewise, figure 11 and 12 show temperature levels for each sampling point at 20% respectively 100% HRU speed, as a function of the relative fan speed. Temperature ( C) 25 20 15 10 5 0 Grid T2 0 20 40 60 80 100 Time (min) Figure 8. Temperature measurements, grid T2 (supply side, close to wheel). From figure 9 and 10 it can be seen that the HRU speed is of minor importance as long as it is above 20% (in this case, 20% speed corresponds to an absolute speed of 2.25 rpm). Furthermore, while the fans run on low speed (20% of max) the cross sectional stratification bedding is small on the supply side, and the temperature distribution is fairly uniform. As the HRU speed is increased, temperatures on the supply side decrease slightly. Most likely this is caused by the large increase of recirculation air (refer to the flow measurements discussed earlier). However, in a system with an efficient purge sector this tendency will not show. On the discharge side, the distributions are more scattered, with highest values near the center line of the wheel. When the fan speed is increased (figure 10), the cross sectional temperatures on both the supply and discharge sides of the wheel become increasingly scattered, and a cross sectional stratification is revealed. In this situation, the air is warmest near the center line of the wheel. From the next two figures (figure 11 and 12) it can be seen that the fan speed of course affect the temperature levels significantly. While the fans run on low speed (20% of max) the cross sectional stratification bedding is small on the supply side, and the temperature distribution is fairly uniform. There is however a tendency of high temperatures near the center of the unit and low temperature around the edges. On the discharge side, the warmest air is near the edge of the wheel, close to the center line. Table 1 shows a simple summary of the temperature levels from figure 9-12, as a color map of grid T2 and A2. Levels are shown as +/- differences from the duct levels T4 and A4, which are believed to be more representative for the actual air temperature. Table 1. Map of temperatures ( C) close to HRU wheel (supply and discharge side). Fig. 9, fan 20% Fig. 10, fan 100% Fig. 11, HRU 20% Fig 12, HRU 100% Varying HRU Varying HRU Varying fan Varying fan +1 0-1 +1-2 -1 +1-2 -1 0-1 -1 Supply 0 0-1 +1 +2-1 +1 +2-1 0 +1-3 +2 0 +2 +6 +2 +8 +6 +2 +8 +5 +2 +8 Discharge 0-2 0 +6-3 0 +6-3 0 +3-2 +1 T2-1 T2-2 T2-3 T2-4 T2-5 T2-6

Figure 9. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of HRU rotational speed at 20% fan speed (HRU view from intake side). Figure 10. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of HRU rotational speed at 100% fan speed (HRU view from intake side).

Figure 11. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of relative fan speed at 20% HRU rotational speed (HRU view from intake side). Figure 12. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of relative fan speed at 100% HRU rotational speed (HRU view from intake side).

Placement of temperature sensors in the duct The ideal placement of a temperature sensor used for Supply control or efficiency calculations is away from the wheel so it is not affected by stratified air nor by radiation from the wheel media. However, this is rarely convenient or possible, so the compromise must be to find a spot near the wheel (on all sides) that approximately resembles the actual air temperature as if it was measured away and shielded from the device. From table 1, an assessment of sensor placement is possible. For this actual HRU wheel Discharge it seems most appropriate to place the supply side and Figure 13. Placement of sensors discharge side sensors as shown by the yellow spots in figure 13. It should also be mentioned that the temperatures on the exhaust and intake side of the wheel were fairly uniform, but small variations can be expected due to radiation from the wheel and in cases with leakage. A similar assessment may be required here. Possible sources of error Measurements should be carried out on several different heat recovery units. Also, the number of repeated measurements series are low, and it is thus not possible to establish a basis for categorical conclusions. Nevertheless, the results serve to pinpoint typical tendencies. CONCLUSIONS The flow rate measurements results suggest that for ventilation systems running on low fan speeds (VAV), the amount of recirculation of air from the exhaust to the supply can, due to carryover, become very high and thus unacceptable. The rotational speed of the heat recovery unit has shown to be of minor importance as long as the wheel is rotating. For this particular case, above 20% of maximum speed. The ideal placement of a temperature sensor used for control or efficiency calculations is away from the wheel so it is not affected by cross-sectional stratification bedding, nor by radiation from the wheel media. For the particular HRU in question, measurement results suggest that the sensors on the supply and discharge side should be placed approximately in the middle of the AHU duct, or displaced to the sides. FURTHER WORK This work represents the first report in a project on air-to-air heat recovery devices carried out at Narvik University College. Future work will address temperature and energy efficiency, transient conditions, control, modelling and simulation. REFERENCES 1. Schild P G. 2004. Air-to-Air Heat Recovery in Ventilation Systems. AIVC Ventilation Information Paper no 6. 2. Eian P. K., Sørensen B. R. 1996, Bestemmelse av ventilasjonens effektivitet med sporgassanalyse. Report (in Norwegian), Narvik University College, ISBN 82-7823-000-5.