FT080 Fire terminal (Touch) Mounting Installation 06-0-08 Control Products and Systems
Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Division International Headquarters Gubelstrasse CH-630 Zug Tel. + 7- www.siemens.com/buildingtechnologies Edition: 06-0-08 Document ID: Siemens Switzerland Ltd, 05
Table of contents Setup of fire terminal (Touch) FT080... 5 Installation in 9" pedestal housing of the FC080... 7 3 Installation in housing (standard)... 0 Installation in rear panel (FT080) FHA039... 5 Installation in desktop housing (FT080) FHA00... 6 6 Technical data... 3
Setup of fire terminal (Touch) FT080 Setup of fire terminal (Touch) FT080 3 6 6 5 Figure : Rear panel fire terminal (Touch) FT080 Support plate Front indicator (Touch) FTO00 3 PMI & mainboard FCM07 x mounting holes in the operating unit 5 Shield plate above carrier (CPU) 6 Hinges for wall housing 5
Setup of fire terminal (Touch) FT080 Arrangement of components Figure : Components on the fire terminal (Touch) FT080, without cover cap Front indicator (Touch) FTO00 Main network module (SAFEDLINK) on X3, optional 3 License key, optional Slot [SER_OPT] for the first serial module at X, optional 5 Slot [SER_OPT] for the second serial module at X9, optional 6 Degraded mode network module (SAFEDLINK) on X, optional 7 CPU module (CORVUS) FCC009 8 Carrier for CPU modules FTO0 9 CPU module (MPC88) FCC006 0 PMI & mainboard FCM07 Slot X for serial module. Not required for FT080 Both slots X and X9 can hold the RS3 or RS85 serial module. 6
Installation in 9" pedestal housing of the FC080 Installation in 9" pedestal housing of the FC080 The installation instructions described below apply to all operating units. Before an operating terminal is installed, the following components must first be mounted on the operating unit. Network module (SAFEDLINK) FN00-A with ES, for connecting to the FC080 Adapter and connection cable for the power supply Supplied with processor unit (9", FC080) FCC00-A Preparing the operating unit The network module (SAFEDLINK) FN00-A must be installed on connector X3 of the operating unit (main module slot). 6 3 5 8 7 Figure 3: Installing the required components, taking operating unit FCM08-A as an example Operating unit Flange with threaded holes for securing the module 3 Connector strip X3 for network module Network module (SAFEDLINK) FN00-A with ES 7
Installation in 9" pedestal housing of the FC080 5 x fixing screw 6 PMI & mainboard FCM07 7 Adapter for power supply (including ribbon cable) 8 Connector strip X3 peripheral data bus connection. Plug the network module (SAFEDLINK) () into connector X3 (3) of the operating unit ().. Secure the module to mounting flange () with both screws (5). Ensure that it is secured correctly to avoid interrupts. 3. Plug the adapter (7) into connector X3 (8) of the PMI & mainboard (6) so inscription 'TOP' is at the top. Installing operating unit 3 5 Figure : Mounting operating terminal in door, taking operating unit FCM08-A as an example Inside of door Opening for operating unit 3 x welded threaded bolts x mounting holes in the operating unit 5 x fixing screws. Remove the cover plate () by removing the four nuts (5).. Place the mounting holes () of the operating unit on the four threaded bolts (3) and screw the operating unit down with the four nuts (5). 3. The operating add-ons in the bottom window openings are installed in the same way.. Wire up the operating unit and operating add-ons according to the following wiring instructions. 8
Installation in 9" pedestal housing of the FC080 Wiring the fire terminal (Touch) 3 5 Figure 5: Wiring the fire terminal (Touch) with FC080 Ribbon cable for FC080 system supply to card cage (CPU) X30 FCnet connection to card cage (CPU) X/X 3 X3 connection to network module (SAFEDLINK) to PMI & mainboard FCM07 Inside of door (section view) 5 Fire terminal (Touch) FT080 6 Adapter for flat cable of the supply 6 FCnet FCnet FC080 Door FCC003 * FCM0xx A B A B A B A B A B A B 3 3 3 X X X3 FN00 FN00 FN00 Figure 6: Example of FCnet wiring of X3 on PMI & mainboard FCM07 of the fire terminal (Touch) * The FCnet connection from X to X on the card cage (CPU) FCC003 is wired up in advance at the factory. 9
3 Installation in housing (standard) 3 Installation in housing (standard) Figure 7: Installation of fire terminal in the housing (standard) FH00 Mains connection terminals Power supply unit (70 W) FP05 3 Rear panel (standard) Fire terminal board FTI00 5 Wiring FCnet/SAFEDLINK 6 Network module (SAFEDLINK) FN00 7 Fire terminal (Touch) FT080 X3 Ribbon cable connection from the fire terminal (Touch) to the fire terminal board X Supply input for fire terminal board You will find detailed information on wiring the 'fire terminal board FTI00' and the 'network module (SAFEDLINK) FN00' in document Product Data 008837. 0
Installation in rear panel (FT080) FHA039 Installation in rear panel (FT080) FHA039 The rear panel (FT080) can be used for installation in a desk or installation in a third-party housing. Installing the rear panel (FT080) in a third-party housing guarantees the required EMC protection. The installation sequence is as follows, due to the restricted space: Installing the fire terminal board FTI00 Wiring the fire terminal (Touch) Installing the fire terminal (Touch) Installing the rear panel (FT080) in a desktop View of rear panel (FT080) FHA039 3 Figure 8: Rear panel (FT080) FHA039 Rear panel (FT080) FHA039 50 V EMC filter, 3 A with plug-in contacts 3 Clamping bracket with screw for ground connection
Installation in rear panel (FT080) FHA039 Installing fire terminal board FTI00 3 5 Figure 9: Installing the fire terminal board in the rear cover (FT080) Rear panel (FT080) FHA039 Fire terminal board FTI00 3 x fixing screws x mounting holes 5 Threaded press-in sleeves in rear cover (FT080). Position the fire terminal board () in the rear panel () as shown.. Use the four fixing screws (3) to screw the fire terminal board () in the rear panel () firmly onto the threaded press-in sleeves (5).
Installation in rear panel (FT080) FHA039 Wiring the fire terminal (Touch) When installing in a desktop that is thicker than 33 mm, the cables must be routed through the rectangular openings of the rear panel (FT080), and not through the round cable breakthroughs. Figure 0: Wiring view of the fire terminal (Touch) in the rear cover (FT080) Fire terminal (Touch) FT080 Network module (FCnet/SAFEDLINK) FN00 3 FCnet connection cable Prefabricated cable for supply connection to X7 5 EMC filter 6 Input for DC V system supply to EMC filter 7 Fire terminal board FTI00. Wire up the flat cable from the fire terminal board X3 to the PMI & mainboard X3.. Wire up the prefabricated cable of the supply from the EMC filter to the fire terminal board X7. 3. Wire up the external cables of the supply, the FCnet and the Ethernet cable through the cut-out in the desktop and the cable lead-throughs in the rear panel. 3
Installation in rear panel (FT080) FHA039 Installing the fire terminal (Touch) 3 5 6 7 8 9 Figure : Installing the fire terminal (Touch) in the rear panel (Touch) Fire terminal (Touch) FT080 x fixing screws 3 x mounting holes in the fire terminal (Touch) Cable lead-through in the rear panel 5 x threaded holes in the rear cover (FT080) 6 Lateral cable lead-throughs 7 Rear panel (FT080) FHA039 8 Cut-out in the desktop 9 Desktop. Position the wired-up fire terminal (Touch) () on the rear panel (7) as shown.. Screw the four fixing screws () through the holes (3) to secure the fire terminal (Touch) () into the threaded holes (5) in the rear panel.
Installation in rear panel (FT080) FHA039 Installing the rear cover (FT080) in a desktop 3 5 7 6 Figure : Installing the rear cover (FT080) in a desktop Rear panel (FT080) FHA039 Mounted fire terminal (Touch) FT080 3 x fixing screws Mounting holes in the flanges of the rear panel (FT080) 5 Bores in the desktop 6 Desktop 7 Cutout for rear panel (FT080) min. 30 x 68 mm. Place the rear panel () in the cut-out of the desktop (6) as shown. Ensure that the cables are not pinched.. Use the four fixing screws (3) to screw the rear panel () into the bores (5) of the desktop at the flanges (). 5
5 Installation in desktop housing (FT080) FHA00 5 Installation in desktop housing (FT080) FHA00 3 6 5 7 0 9 8 Figure 3: View of desktop housing (FT080) Top of desktop housing Tilting bracket for top of housing 3 Base of desktop housing Mx0 pan head screw (scope of delivery) 5 Clamping bracket for ground cable (scope of delivery) 6 50 V EMC filter, 3 A with plug-in contacts (mounted) 7 Fixing screw by customer 8 Washer 5/5 mm (scope of delivery) 9 x rubber grommets (scope of delivery) 0 Spacer sleeves (scope of delivery) Ethernet coupling 6
Installation in desktop housing (FT080) FHA00 5. Remove the top of housing () by pushing the two tilting brackets () on the left and right inwards until you can lift off the top of housing.. Connect the ground connection as shown with clamping bracket (5) and M pan head screw (). 3. Place the spacer sleeves (0) from below over the rubber feet (9).. Position the housing (3). 5. Place the washers (8) onto the rubber feet (9) inside the housing. 6. Screw the housing (3) tight with a screw (7) suitable for the substructure. Installing fire terminal board FTI00 3 Figure : Installing fire terminal board in desktop housing Base of desktop housing Fire terminal board FTI00 3 6x fixing screws (scope of delivery) Spacer with thread in rear panel. Position the fire terminal board () in the housing () as shown.. Screw the fire terminal board () firmly onto the spacers () in the housing () using the four fixing screws (3). 7
5 Installation in desktop housing (FT080) FHA00 Installing fire terminal (Touch) FT080 3 3 5 Figure 5: Mounting in top of housing Tilting brackets on left and right for fixing the top of the housing x fixing screws for tilting brackets and fire terminal 3 x fixing screws for fire terminal Fire terminal (Touch) FT080 5 Top of desktop housing (FT080) FHA00. Place the fire terminal () in the top (5) of the desktop housing as shown.. Screw the tilting brackets () into the top of the housing on the left and right as shown, through the top holes in the fire terminal (). 3. Due to the restricted space available, connect the Ethernet cable to plug X5 before mounting the fire terminal (Touch).. Use the two other screws to screw the fire terminal () into the top of the housing through the bottom holes. 8
Installation in desktop housing (FT080) FHA00 5 Assembly of desktop housing (FT080) 3 5 5 6 Figure 6: Assembly of desktop housing Fire terminal (Touch) FT080 Top of desktop housing (FT080) FHA00 3 Tilting brackets on left and right for fixing the top of the housing Guide cams on left and right for tilting brackets 5 x threaded holes for fixing the top of the housing 6 Base of desktop housing 7 Fire terminal board FTI00. Move the top of the housing () with the installed fire terminal () to the position shown.. Gently press the two tilting brackets (3) inwards and lift the top of the housing () into the two guide cams (). a The top of the housing is fixed in the open position and the tilting brackets act like hinges. 9
5 Installation in desktop housing (FT080) FHA00 3 Figure 7: Securing the top of the desktop housing Securing cap (scope of delivery) Opening for fixing screw 3 Top of the desktop housing (Touch) Fixing screw with securing device. To close the housing, tilt the top of the housing (3) onto the housing and secure the top to the housing using both screws ().. Close the openings for the fixing screws () using both securing caps () 0
Installation in desktop housing (FT080) FHA00 5 Fire terminal wiring Figure 8: Wiring view of the fire terminal in the desktop housing Fire terminal (Touch) FT080 Network module (FCnet/SAFEDLINK) FN00 3 Fire terminal board FTI00 Prefabricated cable for supply connection to X7 fire terminal board 5 FCnet connection cable 6 EMC filter 7 Input for DC V system supply to EMC filter 8 Internal cable RJ5 for Ethernet connection, L=0 mm
6 Technical data 6 Technical data Supply input Voltage DC 0 30 V Quiescent current (display illumination dimmed 5%) Maximum current (display illumination 00% and lamp test active) 390 ma 700 ma Display Screen size " Resolution 80 x 800 pixels Interfaces x slots for serial modules RS3 module for event printer RS85 module for ESPA-.. interface, FAT, FBF, UGA or remote EVAC-NL operation x slots for network modules (SAFEDLINK) x Ethernet connection RJ5 x connection for peripheral data bus Full functionality incl. degraded mode function Degraded mode function only 0/00 Mbit/s X00 Ambient conditions Operating temperature -8 + C Storage temperature -0 +60 C Moisture, condensation not permitted Protection category (IEC6059) Max. 95 % rel. IP30 Mechanical data Dimensions (W x H x D) 7 x 00 x 5 mm Weight without options FT080-A:.5 kg Color Standards and approvals VdS G50 Foil: RAL900 Pure white, RAL9006 White aluminum FT080-A / FT080-C FT080 - Control and Indicating Terminal for use in fire detection and fire alarm systems installed in buildings. Siemens Switzerland Ltd; Gubelstrasse CH-630 Zug Technical data: see doc. 008836 0/30/EU (EMC): EN 5030- / EN 6000-6-3 ; 0/35/EU (LVD): EN 60950- ; 0/65/EU (RoHS): EN 5058 The declared conformity can be seen in the EU Declaration of Conformity (DoC), which is obtainable via the Customer Support Center: Tel. +9 89 9-8000 or http://siemens.com/bt/download DoC No.: CED-FT080
Technical data 6 3