Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Similar documents
Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

Metropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Boiler Product Range

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

Quinta Pro Range. The New Remeha. Condensing Boilers REMEHA QUINTA PRO RANGE. High efficiency wall hung condensing boiler with ultra low NOx emission

pressurejetrange Buccaneer GTE, Falcon GTE, Harrier GTE, Viceroy GT, Viscount GTE, Vanguard L Pressure jet boilers kW

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Series 1000 & Storage Water Heaters

Cast Iron Boilers. G Series ( kW)

Hoval Cosmo Combination boilers. High efficiency heating combined with economic DHW generation. Boiler outputs from 100 to 1450kW.

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00

S-AF Floor Standing Condensing Boiler kW

pressurejetrange Buccaneer GTE, Falcon GTS, Harrier GTS, Viceroy GTS, Viscount GTS, Vanguard L Pressure jet boilers kW

CP+ Gas & Oil Cabinet Heater Range

Pressure Jet Boilers. Pressure Jet Range. Commercial Heating Solutions.

Technical information. Remeha P200. Pressurized boiler. Heat output: kw

Sirius FS. Working towards a cleaner future

R e m e h a P Technical Information. Remeha P 300. Pressurized boiler. Heat output: kw

Technical information. Remeha P 500. Pressurized boiler. Heat output: kw

INSTALLATION AND OPERATION MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CAST IRON ATMOSPHERIC BOILERS

IMAX XTRA EL. 715kW FLOOR STANDING CONDENSING FEATURES AND BENEFITS

STOKVIS R40 EVOLUTION RANGE. High Efficiency Fully Condensing Ultra Low NOx Wall Mounted Gas Fired Boilers

CAST IRON PREMIX HIGH EFFICIENCY GAS FIRED BOILER kw BRILEY DESIGN MANUAL

Catalogue ENGLISH h i g h h e a t t e c h n o l o g y

Hamworthy Fleet Horizontal Floor Standing. Condensing Boilers Natural Gas Outputs 40kW to 350kW 5 YEAR HEAT EXCHANGER WARRANTY

Hamworthy. Varmax. New. Fully modulating, low NOx, stainless steel, condensing boilers Natural Gas or LPG Outputs 120kW to 900kW

GHP AWO 38 Technical overview

... RHeco. High Efficiency Condensing Unit Heaters... Low NO x. ErP. ErP Lot 21 Seasonal Efficiency and NOx compliant

... RHeco. High Efficiency Condensing Unit Heaters... Low NO x. ErP. ErP Lot 21 Seasonal Efficiency and NOx compliant

CI/SfB X. RHeco Series CONDENSING GAS FIRED UNIT HEATERS

Condensing Heat Exchanger Suitable Gas Fired Ideal GT & GTE boiler ranges

VPC Gas Cabinet Heater Range

VPC Gas Cabinet Heater Range Architects of your environment. heating ventilation air conditioning

WELCOME TO REMEHA, THE EXPERT CHOICE INTRODUCING THE REMEHA GAS 110 ECO RANGE FEATURES AND BENEFITS

FEATURES AND BENEFITS. Up to 109.8% part load efficiency

RIELLO 40 GS/M SERIES

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS

... LCSA - LCSBD - LCSC Gas Fired Unit Heaters ...

Gas 220 Ace Cascade Assembly Manual

Copper-Fin GAS-FIRED WATER HEATERS

95% Hamworthy Fully Modulating, Low NOx, Stainless Steel, Condensing Modular Boilers. Wessex ModuMax mk3. New. Restyled with latest Siemens controls

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

Hamworthy. Melbury HE. High Efficiency Steel Shell Power Flame Boilers Gas, Oil, Biofuel or Dual Fuel Burners. Outputs 530kW to 10000kW

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment

Wall Hung Condensing Boilers. Working towards a cleaner future. heating specialists

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

Prextherm Rsw High efficiency steel pressurised boilers

R-SERIES kW YEAR ROUND MAXIMUM CONDENSING BOILER. burning diesel oil, kerosene, natural gas or liquid petroleum gas

Sirius WH. Working towards a cleaner future

Operating and Installation Instructions for the SR-plus hot water boiler

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

Rycroft Storage & Non-Storage Calorifiers. Installation, Operation & Maintenance Manual

Max-3 Steel Shell Boiler

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

KDE. PRESSURIZED STAINLESS STEEL CONDENSING BOILER FROM 124 kw TO 2160 kw

WOLF GAS CONDENSING BOILERS COMFORTLINE

Steel Shell Boilers. Max-3 plus kw. Max-3 E & Max-3 condens E kw. CompactGas kw. SR-plus and SR-H plus kw

Worcester GB162 wall mounted gas-fired condensing boiler series

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

CONDOR RAPID CONDOR RAPID/V STEAM FORCED CIRCULATION. Design pressure 11,76 bar Steam production from 45 to Kg/h

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Hamworthy. Stratton Wall Hung. Stainless Steel Condensing Boilers Natural Gas or LPG Outputs 45kW to 100kW

Hamworthy. Stratton Wall Hung. Stainless Steel Condensing Boilers Natural Gas or LPG Outputs 45kW to 100kW

Hamworthy Fleet Vertical Floor Standing. Condensing Boilers Natural Gas Outputs 80kW to 1050kW 5 YEAR HEAT EXCHANGER WARRANTY

Bosch Buderus SSB255/399/512 Stainless Steel Condensing Boiler

Hamworthy. Wessex Modumax. High Efficiency, Fully Modulating Boilers Condensing & Non Condensing, Pre-mix, Gas Fired. Outputs 100kW to 750kW

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Technical Specification

MX RANGE PACKAGED STEAM BOILERS

U n i t H e at e r s

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

GB Condensing Gas Boiler

Ridge End. DA Cooks. Progressing Meeting No:2. Neptune Responses Mechanical. 2 nd November 2015

HEAT TRANSFER STORAGE CALORIFIERS EC SERIES SC SERIES BT SERIES

Ultramax R600. High output, floor standing gas fired condensing boilers with outputs from 150kW to 571kW

up to Seasonal efficienc (gross) y ErP Nat Gas 5:1 Part L LPG

Ultramax PB. Floor standing premix gas fired condensing boilers with outputs at 65, 85, 100 & 120kW BOILERS

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Bosch Uni 7000F Cast Iron Hot Water Boiler

Hamworthy. Purewell VariHeat

Baxi Megaflo System HE IE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Boiler

THW-I NTE. Description THW-I NTE. Industrial Hot Water Boiler THW-I NTE for Oil or Gasfiring. Industrial Hot Water Boiler

Biomass. Biomass solid fuel boiler range

Pressurisation units & expansion vessels

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

Light oil - kerosene burner

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Transcription:

Calder Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing Outputs 70-3500 kw Calder Model 70-1300 Calder Model 1400-3500

Calder - Steel Hot Water Boiler The Calder is a range of three pass reverse flame steel shell and tube hot water boilers. They are available in sizes ranging from 70-3500 kw, suitable for firing on natural gas, LPG and oil with a choice of burner manufacturers. Design features Manufactured to EN303 Flanged front and rear tube plates High density insulated casing Left or right hand hinged front door Ancillary boiler connections incorporated Performance features Calder Model 70-1300 High efficiency up to 92.3% (net CV) Standard outputs from 70-3500 kw Standard working pressure up to 5 bar (up to 10 bar on request) Maximum flow water temperature 100 C Minimum return water temperature 55 C General Description Calder Model 1400-3500 2 Calder boilers are designed to provide high efficiency up to 92.3% (net CV), focusing on fuel savings, low flue gas temperatures and low emissions. The boilers have a high water volume and the design reduces thermal stress and the build up of scale, which improves the longevity of the boiler. Calder boilers are generally available in outputs of up to 3500 kw, however details of outputs above this are available on request. The boilers have a standard maximum working pressure of 5 bar, with higher pressures up to 10 bar available on request. The maximum standard water flow temperature is 100 C and the minimum return water temperature is 55 C, with a maximum temperature drop across the boiler of 30k. Each boiler is supplied with a factory tested control panel. The panel is pre wired and connected to the control and safety limit thermostats and burner. Where appropriate, Calder boilers should be installed in accordance with BS 6644 and other relevant standards, codes of practice and current building regulations. Water treatment is recommended for all steel shell and tube boilers and a water treatment specialist should be consulted for advice on this matter. All Calder boilers are supplied with a set of cleaning tools.

Design & Construction The Calder is a three pass wet back reverse flame shell and tube design and comes complete with a removable stainless steel turbulator within each firetube. and robotic welding machines ensure high quality workmanship. The boiler incorporates a flanged front and rear tube plate design, which minimises thermal stresses within the boiler. casing, which is supplied fully assembled and factory fitted. Calder boilers are manufactured in accordance with European standards and are CE certified. The boiler is manufactured using high quality steel and is constructed generally in accordance with EN303. Laser cut precision components are used during manufacture The boilers are supplied complete with a high density insulated casing. The 70-1300 models have painted steel panels, which can be supplied fully factory fitted or loose for fitting on site by the purchaser. The 1400-3500 models have a circular stucco aluminium The boilers have an insulated hinged front door, which is available for left or right hand opening. However this needs to be specified at the time of order. To ensure the highest quality standards, every Calder boiler is hydraulically pressure tested in the factory. Electrical Connections and Controls A control panel is supplied with each Calder boiler. The standard control panel features include a main switch, panel live lamp, boiler thermometer, control thermostats, safety thermostat with manual reset, burner on/off switch and pump on/off switch. The standard control thermostats have an operating range from 60-90ºC, (control thermostats up to 100ºC are available on request). Additional control options are available, including volt free kits, weather compensation, optimised start/stop, cascade control, room and outdoor sensors, hours run meter, flue gas thermometer, etc. details available on request. A 230v single phase electricity supply is required to the control panel from a suitable fused isolator. For single phase burners the electrical supply can be direct from the control panel. For three phase burners a seperate three phase isolated supply direct to the burner is necessary, with a flexible connection for boiler door opening. The standard panel is supplied with the following :- main switch burner on/off switch and panel live lamp pump on/off switch boiler thermometer Fully wired and connected to burner control thermostats safety thermostat with manual reset 3

Technical Data & Dimensions Calder Model 70 to 1300 Calder Model 70 80 90 100 120 150 200 250 300 350 400 500 620 750 850 950 1000 1200 1300 Output (kw) 70 80 90 100 120 150 200 250 300 350 400 500 620 750 850 950 1000 1200 1300 Dimensions & Weight A 1030 1030 1030 1030 1030 1080 1080 1080 1180 1180 1190 1380 1380 1510 1510 1510 1660 1660 1660 B 750 750 750 750 750 800 800 800 900 900 940 1160 1160 1290 1290 1290 1440 1440 1440 C 994 994 1119 1119 1119 1364 1364 1614 1614 1864 1872 1946 2235 2247 2247 2497 2477 2477 2477 D 855 855 855 855 855 905 905 905 1005 1005 1015 1205 1205 1335 1335 1335 1485 1485 1485 E 700 700 700 700 700 750 750 750 850 850 890 1110 1110 1240 1240 1240 1390 1390 1390 F 630 630 755 755 755 1000 1000 1250 1250 1500 1502 1502 1792 1753 1753 2003 2003 2003 2003 G 413 413 513 513 513 513 513 513 523 523 600 663 663 704 704 704 703 703 703 H 240 240 265 265 265 475 475 725 700 980 850 850 1150 1100 1100 1200 1200 1200 1200 J 911 911 911 911 911 961 961 961 1061 1061 1095 1285 1285 1417 1417 1417 1568 1568 1568 K 415 415 415 415 415 440 440 440 490 490 500 610 610 675 675 675 750 750 750 L 415 415 415 415 415 440 440 440 490 490 500 610 610 675 675 675 750 750 750 M 54.5 54.5 54.5 54.5 54.5 54.5 54.5 54.5 50 60 60 60 60 60 60 60 60 60 60 Approx. dry weight (kg) 216 216 258 258 258 346 346 431 475 542 584 853 963 1205 1205 1417 1843 1843 1843 Efficiency based on net CV Efficiency (%) @ 100% load * 92.1 91.9 91.8 91.7 91.6 92.0 91.7 91.9 92.3 92.1 92.3 92.2 92.2 92.2 92.2 92.2 92.2 92.2 92.2 Efficiency (%) @ 30% load * 90.2 90.2 90.3 90.4 90.4 91.1 91.3 90.4 90.6 90.6 90.8 90.7 90.7 90.6 90.7 90.7 90.6 90.6 90.6 Combustion and flue data Gas flow rate G20 (m³/h) 8.1 9.2 10.4 11.5 13.9 17.2 23.1 28.8 34.4 40.2 45.8 57.4 71.1 86.0 97.5 109.0 117.1 137.7 149.1 Oil flow rate (l/h) 7.9 9.0 10.2 11.3 13.6 17.0 22.6 28.3 33.9 39.6 45.2 56.5 70.1 84.8 96.1 107.3 113.0 135.6 146.9 Flue Gas Volume (m³/min) 3.0 3.4 3.9 4.3 5.1 6.5 8.7 10.8 13.0 15.2 17.3 21.7 26.9 32.5 36.9 41.2 43.4 52.1 56.4 Approx Flue Gas Temp. (ºC) 188 192 194 197 200 190 197 193 184 188 182 185 185 185 184 185 186 185 185 Comb. Chamber Resistance (mbar) 0.8 1.0 0.8 1.0 1.1 1.2 1.9 2.0 2.0 2.9 4.1 4.2 6.4 5.2 7.2 5.2 4.0 5.5 6.5 Water system Hydraulic Resistance (11k) (mbar) 10.7 10.7 11.9 14.3 15.5 16.7 17.9 17.9 19.0 21.4 23.8 26.2 32,1 29.8 32.1 38.0 30.9 35.7 38.1 Hydraulic Resistance (20k) (mbar) 3.2 3.2 3.6 4.3 4.7 5.0 5.4 5.4 5.8 6.5 7.2 7.9 9.7 9.0 9.7 11.5 9.4 10.8 11.5 Minimum flow rate (11k) (l/s) 0.38 0.43 0.49 0.54 0.65 0.81 1.08 1.35 1.62 1.90 2.16 2.71 3.36 4.10 4.60 5.14 5.41 6.50 7.03 Minimum flow rate (20k) (l/s) 0.21 0.24 0.27 0.30 0.36 0.45 0.60 0.74 0.89 1.04 1.19 1.49 1.85 2.23 2.53 2.83 3.0 3.57 3.87 Water content (l) 105 105 123 123 123 172 172 220 300 356 360 540 645 855 855 950 1200 1200 1200 Connections Flue gas spigot dia. (mm) 200 200 200 200 200 250 250 250 250 250 250 300 300 350 350 350 400 400 400 Flow & Return Flanged PN16 50 50 50 50 50 50 50 50 65 65 80 80 80 100 100 100 125 125 125 Drain Male thread 1 1 1 1 1 1 1 1 1 1 1 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 Safety Valve Female thread - - - - - - - - - - 1.1/4 1.1/4 1.1/4 1.1/2 1.1/2 1.1/2 1.1/2 1.1/2 1.1/2 For models 350 and below a seperate safety valve connection is not provided, as the safety valve is connected to the 1 instrument connection *Based on 80-60ºC flow & return temperatures All dimensions in (mm) unless stated otherwise 4

Technical Data & Dimensions Calder Model 1400 to 3500 Calder Model 1400 1600 1800 2000 2400 3000 3500 Output (kw) 1400 1600 1800 2000 2400 3000 3500 Dimensions & weight A 1746 1746 1746 1876 1876 2146 2146 B 1470 1470 1470 1600 1600 1870 1870 C 2886 2886 3096 3220 3480 3480 3225 D 1630 1630 1630 1760 1760 2030 2030 E 1270 1270 1270 1400 1400 1670 1670 F 2300 2300 2510 2510 2770 2770 3935 G 831 831 771 903 903 903 903 H 1300 1300 1850 1550 1950 2050 2050 J 880 880 880 945 945 1080 1080 K 880 880 880 945 945 1080 1080 L 150 150 150 150 150 150 150 Approx. dry weight (kg) 2600 2600 2750 3650 3900 5200 5700 Efficiency based on net CV Efficiency (%) @ 100% load * 92.3 92.3 92.3 92.3 92.3 92.3 92.3 Efficiency (%) @ 30% load * 91.7 91.8 91.8 91.7 91.8 91.8 91.7 Combustion and flue data Gas flow rate G20 (m³/h) 160.5 183.4 206.4 229.3 275.2 343.9 401.3 Oil flow rate (l/h) 166.6 190.4 214.2 238.0 285.6 357 416.5 Flue Gas Volume (m³/min) 60.8 69.6 78.3 87.0 104.4 130.5 152.2 Approx Flue Gas Temp. (ºC) 184 183 184 184 184 184 184 Comb. Chamber Resistance (mbar) 6.0 6.5 7.0 6.0 7.5 8.0 9.0 Water system Hydraulic Resistance (11k) (mbar ) 33 32 37 35 40 49 60 Hydraulic Resistance (20k) (mbar ) 10 10 11 11 12 15 18 Minimum flow rate (11k) (l/s) 7.6 8.7 9.7 10.8 13.0 16.2 18.9 Minimum flow rate (20k) (l/s) 4.2 4.8 5.4 6.0 7.1 8.9 10.4 Water content (l) 1500 1500 1650 2000 2300 3150 3650 Connections Flue gas spigot dia. (mm) 400 400 400 500 500 550 550 Flow & Return Flanged PN16 150 150 150 200 200 200 200 Drain Male thread 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 Safety valve Female thread 1.1/2 1.1/2 1.1/2 2 2 2 2 * Based on 80-60ºC flow & return temperatures. All dimensions in (mm) unless stated otherwise 5

Installation Clearances Calder boilers should be installed and positioned so that there is adequate access to the flue and pipework connections. Consideration should also be given to the position and projection of the burner with the boiler door in the open position. All boilers should also be installed so that there is enough room at the front for cleaning of the tubes and combustion chamber and for removal of the turbulators. Burners A burner is normally supplied and matched to the boiler to give either on/off, high/low or fully modulating operation, which ensures optimum operating efficiency to suit specific requirements. The burner is bolted to the boiler front door and pre-wired to the control panel. Ancillary items A pressure gauge, safety valves and drain valve are supplied loose for connection to the boiler on site by the purchaser. For models 70-350 the safety valve and pressure gauge can be connected to a 1" instrument connection provided on the top of the boiler. Alternatively the purchaser may connect the pressure gauge and safety valve directly to the system flow pipework between the boiler and the isolation valve. For model 400 a safety valve connection is provided on the boiler and on models 500 and above, two safety valve connections are provided on the top of the boiler as standard. Boiler base Calder boilers should be located on a surface capable of supporting the fully flooded weight of the boiler and burner and it should be smooth, level and constructed from a non flammable material. Delivery Delivery to site can be arranged. Commissioning Commissioning of the boiler/burner can be arranged. Dual Boiler Options Calder boilers can be supplied in a special dual formation, for mounting either side by side or one on top of the other. Flow and return headers and special control panels are also available, for these arrangements. Dual boilers can be supplied with a total output of up to 2600 kw. Details of these boiler configurations are available on request. Ormandy Group Associated Products The Ormandy group has an extensive range of boilerhouse products, which compliment the Ormandy Hartley & Sugden boiler range. All Ormandy products can be skid mounted to specific requirements. Detailed information on all Ormandy products is available on request. Additional products include: Pressurisation units Storage and Non Storage Calorifiers Plate heat exchangers Package plant rooms which can be designed to incorporate any of the above equipment Please visit www.ormandyltd.com to access comprehensive information on Ormandy Hartley & Sugden products and services. Issue 1 April 2011 The Ormandy Group: Ormandy Offsite / Ormandy Rycroft / Ormandy Electric Ormandy Hartley & Sugden / Ormandy Newade / Ormandy Dreh / Ormandy Aquatherm For full information on the Ormandy Group and all its products and services, please visit www.ormandyltd.com Tel +44 (0)1422 350111 Ormandy Hartley & Sugden, Atlas Works, Gibbet Street, Halifax, HX1 4DB England Tel +44 (0)1422 355651 Email sales@hartleyandsugden.co.uk Ormandy Group follows a policy of continuous improvement in the design and performance of its products. Therefore we reserve the right to make changes and improvements to our products without notice which may affect the accuracy of the descriptions and illustrations contained in this brochure. 6