DVPVC Multi-Position, Variable-Speed Air Handler Comfortnet - Compatible ECM-based Inverter-tuned Internal TXV Contents Air Handler Nomenclature... Heater Kit Nomenclature... Product Specifications...3 Dimensions...4 Airflow Data...5 Heat Kit Data...7 Wiring Diagram...9 Accessories... Product Features Internal factory-installed, invertertuned thermal expansion valve for cooling and heat pump applications Variable-speed ECM blower motor ComfortNet Communicating System compatible Auto configuration of the airflow and tonnage in communicating mode Provides constant CFM over a wide range of static pressure conditions independent of duct system CFM indicator Fault recall of six most recent faults Provides adjustable low CFM for efficient fan-only operation Improved humidity and comfort control Built-in compatibility with multi-stage heat pump and cooling applications All-aluminum evaporator coil AHRI certified; ETL listed Cabinet air leakage less than.0% at.0 inch HO when tested in accordance with ASHRAE standard 93 Cabinet air leakage less than.4% at 0.5 inch HO when tested in accordance with ASHRAE standard 93 3 kw 5 kw electric heater kits Horizontal or vertical configuration capabilities depth for easier attic access DecaBDE-free thermoplastic drain pan with secondary drain connections Screw-less sides and back helps to reduce condensation when installed in humid locations Foil-faced insulation covers the internal casing to reduce cabinet condensation Galvanized, leather grain-embossed finish Glue-less cabinet insulation retention Tool-less filter access * Complete warranty details available from your local dealer or at www.daikincomfort.com. To receive the 6-Year Unit Replacement Limited Warranty and -Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Additional requirements for annual maintenance are required for the Unit Replacement Limited Warranty. Online registration and some of the additional requirements are not required in California or Quebec. SS-DVPVC www.daikincomfort.com 5/5 Supersedes 3/6
Nomenclature D V 4 P V C B 4 AA 3,4 5 6 7 8 9 0, Brand Engineering * D - Daikin Single- Piece Major/ Minor Revisions Air Handler *Not used for inventory management Unit Application Refrigerant Compatability V - Multi- Position 4 = R- 40A Variable- Speed Motor Electrical Nominal Capacity Range - 08/40 V, Phase, 60 Hz 5 - Tons 59-4 Tons 37-3 Tons 6-5 Tons Cabinet Width B = 7½" C = " Cabinet Finish D = 4½" P - Painted Communications Expansion Device C - ComfortNet Compatible E - Electronic Expansion Valve T - Expansion Valve V - Inverter- Tuned Expansion Valve HKS X 03 X A AA 3 4 5 6,7 Unit Type Revisions HKS Heat Kit for Engineering Revisions Air Handlers Phase Circuit Breaker A Single Phase 08 V E Three Phase 40 V X No circuit breaker B Single Phase 40 V F Three Phase 08/40 V C Circuit Breaker C Single Phase 08/40 V G Three Phase 460 V D Three Phase 08 V Heating Capacity @ 40 Volts 03 3.0 kw 5 4.4 kw Cabinet Size (MAX) 05 4.5 kw 9 9. kw wth 50F limit C C Cabinet 06 6.0 kw 0 9. kw with 70F limit D D Cabinet 08 8.0 kw 5 5.0 kw X All Cabinet Sizes 0 9.6 kw www.daikincomfort.com SS-DVPVC
Product Specifications DV4PVC C4A* DV36PVC D4A* DV48PVC D4A* DV60PVC D4A* Nominal Ratings Cooling (BTU/h) 4,000 36,000 48,000 60,000 Blower Diameter 0⅝" 0⅝" 0⅝" ⅝" Width 8 0⅝" 0⅝" 0⅝" Coil Connections Liquid ⅜" ⅜" ⅜" ⅜" Suction ⅞" ⅞" ⅞" ⅞" Coil Drain Connection (FPT) ¾" ¾ ¾ ¾ Electrical Data Voltage 08/40 08/40 08/40 08/40 Min Circuit Ampacity 4.9/4.9 6.5/6.5 6.5/6.5 8.6/8.6 Max. Overcurrent Device (Amps) 5/5 5/5 5/5 5/5 Minimum VAC 97 97 97 97 Maximum VAC 53 53 53 53 Blower Motor Full Load Amps (FLA) 3.9 5. 5. 6.9 Horsepower (HP) ½ ¾ ¾ Ship Weight (Lbs.) 8 55 67 67 Note Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed. SS-DVPVC www.daikincomfort.com 3
Dimensions 3.08" (7.8 cm).63" (4.3 cm).45" (3.68 cm) " 4.50" (.43 cm).9" (7.39 cm).93" (7.44 cm) 7.5" (9. cm) 5." (3.3 cm) 9." DRAIN PORT DETAIL.55" (.40 cm) C B.55" (.40 cm) 3." (7.9 cm).4" (3.6 cm).3" (8.70 cm).55" (.40 cm) PLASTIC BREAKER COVER.8" (4.6 cm) LOGO LOCATION.7" (5.5cm) SUCTION TUBE LIQUID LINE A G INLET TUBE SEE DRAIN PORT DETAIL H E D.73" (4.39 cm) F INLET (FRONT VIEW).73" (4.39 cm) " (.54 cm) 9.5" (49.5 cm) INLET (RIGHT SIDE VIEW).55" (.40 cm) Model A B C D E F G H DV4PVCC4 49 0 0 7 7¾ 0½ ⅜ DV36PVCD4 58 3⅜ 4½ 8¾ 5¾ ¼ ⅜ ⅜ DV48PVCD4 58 3⅜ 4½ 8¾ 5¾ ¼ ⅜ ⅜ DV60PVCD4 58 3⅜ 4½ 8¾ 5¾ ¼ ⅜ ⅜ 4 www.daikincomfort.com SS-DVPVC
Airflow Data Model Rated Air flow CFM 0. 0. 0.3 0.4 0.5 0.6 0.7 0.8 0.9 DV4PVCC4A* 700 690 690 685 680 670 665 660 655 DV36PVCD4A* 90 70 65 60 45 30 0 05 00 DV48PVCD4A* 445 440 430 45 405 390 380 375 370 DV60PVCD4A* 645 640 640 635 630 65 60 60 65 Model Maximum Air flow CFM 0. 0. 0.3 0.4 0.5 0.6 0.7 0.8 0.9 DV4PVCC4A* 770 760 760 755 750 735 730 75 70 DV36PVCD4A* 30 85 80 75 60 45 30 5 0 DV48PVCD4A* 590 585 575 560 545 530 50 55 505 DV60PVCD4A* 80 805 805 800 790 785 780 780 775 Notes The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. Use the CFM adjustment factors of.98 for horizontal left,.95 for horizontal right &.96 for downflow orientations. Airflow data indicated is at 30V without air filter in place. Electric Heat Airflow HTR kw Dip Switch Settings 9 0 DV4PVC C4 DV36PVC D4 DV48PVC D4 DV60PVC D4 3 ON ON ON 730 850** NR NR 5 ON ON OFF 780 50 50 50 6 ON OFF ON 850 300 300 300 8 ON OFF OFF 950 500 500 500 0 OFF ON ON 05 550 550 550 5 OFF ON OFF NR 70 70 780 0 OFF OFF ON NR 800 85 850 or 5* OFF OFF OFF OFF NR 850 850 * Within thermostat user menu, CTK0* communicating thermostat will display 0kW for OFF- OFF- ON dipswitch selection, kw for OFF-OFF-OFF dipswitch selection. For match up with a ton outdoor unit: Heater kit application shall not exceed 0 kw. Airflow for 5 kw up to 0 kw heater kits shall be set to 850 cfm speed tap of ON-ON-ON. For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 5 kw. Airflow for 5 kw up to 5 kw heater kits shall be set to 300 cfm speed tap of ON-OFF-ON. For match up with a 3.5 ton outdoor unit: Heater kit application shall not exceed 0 kw. Airflow for 5 kw up to 0 kw heater kits shall be set to 500 cfm speed tap of ON-OFF-OFF. ** 3 kw heater kit is not applicable for this indoor application. NR - Not rated Notes Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation Within thermostat user menu CTK04 communicating thermostat will display 0KW for OFF- OFF- ON dip switch selection, kw for OFF-OFF-OFF dip switch selection. SS-DVPVC www.daikincomfort.com 5
Heat Kit Data Circuit Circuit Single-Point Kit Models Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP² DV4PVCC4AA 0.0/0.0 4.9/4.9 5/5 --- --- --- --- --- HKS*03XC* 0.8/.5 8/ 0/5 --- --- --- --- --- HKS*05XC* 7.3/0.0 7/30 30/30 --- --- --- --- --- HKS*06XC*.7/5.0 3/36 35/40 --- --- --- --- --- HKS*08XC* 8.9/33.3 4/47 45/50 --- --- --- --- --- HKS*0XC* 34.7/40.0 48/55 50/60 --- --- --- --- --- DV36PVCD4AB 0.0/0.0 6.5/6.5 5/5 --- --- --- --- --- HKS*03XC* 0.8/.5 0/ 0/5 --- --- --- --- --- HKS*05XC* 7.3/0.0 8/3 30/35 --- --- --- --- --- HKS*06XC*.7/5.0 34/38 35/40 --- --- --- --- --- HKS*08XC* 8.9/33.3 43/48 45/50 --- --- --- --- --- HKS*0XC* 34.7/40.0 50/57 50/60 --- --- --- --- --- HKSC5*#* 34.7/40.0 50/57 50/60 7.3/0.0 /5 5/5 7/8 80/90 HKSC0D#* 34.7/40.0 50/57 50/60 34.7/40 43/50 45/50 93/07 00/0 HKSC5XF* 0.0/0.0 6.5/6.5 5/5 30.0/34.6 38/43 40/45 --- --- HKSC0XF* 0.0/0.0 6.5/6.5 5/5 37.5/43.3 47/54 50/60 --- --- DV48PVCD4AB 0.0/0.0 6.5/6.5 5/5 --- --- --- --- --- HKS*03XC* 0.8/.5 0/ 0/5 --- --- --- --- --- HKS*05XC* 7.3/0.0 8/3 30/35 --- --- --- --- --- HKS*06XC*.7/5.0 34/38 35/40 --- --- --- --- --- HKS*08XC* 8.9/33.3 43/48 45/50 --- --- --- --- --- HKS*0XC* 34.7/40.0 50/57 50/60 --- --- --- --- --- HKSC5*#* 34.7/40.0 50/57 50/60 7.3/0.0 /5 5/5 7/8 80/90 HKSC0D#* 34.7/40.0 50/57 50/60 34.7/40 43/50 45/50 93/07 00/0 HKSC5XF* 0.0/0.0 6.5/6.5 5/5 30.0/34.6 38/43 40/45 --- --- HKSC0XF* 0.0/0.0 6.5/6.5 5/5 37.5/43.3 47/54 50/60 --- --- HKSC5DC* 5.0/60.0 74/84 80/90 34.7/40.0 43/50 45/50 7/34 5/50 DV60PVCD4AC 0.0/0.0 8.6/8.6 5/5 --- --- --- --- --- HKS*03XC* 0.8/.5 /4 5/5 --- --- --- --- --- HKS*05XC* 7.3/0.0 30/34 35/35 --- --- --- --- --- HKS*06XC*.7/5.0 36/40 40/40 --- --- --- --- --- HKS*08XC* 8.9/33.3 45/50 45/60 --- --- --- --- --- HKS*0XC* 34.7/40.0 5/59 60/60 --- --- --- --- --- HKSC5*#* 34.7/40.0 5/59 60/60 7.3/0 /5 5/5 74/84 80/90 HKSC0D#* 34.7/40.0 5/59 60/60 34.7/40.0 43/50 45/50 95/09 00/0 HKSC5XF* 0.0/0.0 8.6/8.6 5/5 30.0/34.6 38/43 40/45 --- --- HKSC0XF* 0.0/0.0 8.6/8.6 5/5 37.5/43.3 47/54 50/60 --- --- HKSC5DC* 5.0/60.0 74/84 80/90 35/40 43/50 45/50 7/34 5/50 ¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X.5 ² Maximum Overcurrent Protection =.5 X Motor Amps + Heater Amps ^ Circuit : Single-phase for Air Handlers Circuit : Three-phase for HKR3 Heater Kits * Revision level that may or may not be designated C = Circuit Breaker Option --- indicates Not Required HKA meets the new UL995 requirements for 5 and 0KW heaters 6 www.daikincomfort.com SS-DVPVC
Wiring Diagram PL PL 3 3 40 VA TRANSFORMER, SEE NOTE 30 VAC 08 VAC 3 4 VAC GN L L 6 6 5 5 4 4 7 7 8 8 9 9 SEE NOTE 7 BL GY COM WH BR BL 4 3 4 CIRCUIT HEATER CONNECTOR SEE NOTE 5 FAULT RECALL 4 3 C 4 CIRCUIT MOTOR CONNECTOR SEE NOTE 6 ECM MOTOR HARNESS W W CFM LED AF SELECT STATUS LED TRIM % COOL AF PROFILE BL LEARN SEE NOTE 6 DIP SWITCHES CONT FAN COM CAS SEE NOTE 8 7 SEGMENT DIAGNOSTIC DEHUM DISPLAY DEHUM ENABLE TRIM ENABLE TWO-STAGE INTEGRATED CONTROL MODULE CIRCULATOR BLOWER 3 4 5 TH 4 V 3 A FUSE SEE NOTE 6 RX LED HTR KIT(KW) S S S3 S4 S5 S6 S7 S8 S9 S0 S S S3 4 3 O Y Y W W GN G C R BL TR 4 V THERMOSTAT CONNECTIONS 4V THERMOSTAT CONNECTIONS R W W Y Y O DISCONNECT DEHUM C L FUSE 3 A TO MICRO INDOOR AIR CIRCULATOR BLWR 08/30 VAC L 40 VA TH TRANSFORMER 4 VAC W () HEAT COIL/R W () HEAT COIL/ R CAS () CONDENSATE SWITCH CAS () +VDC () RX () INDOOR AIR CIRCULATOR BLWR (4) TR COM INTEGRATED CONTROL MODULE INTEGRATED CONTROL NOTES:. PLACE RED WIRES ON TRANSFORMER TERMINAL FOR 08 VAC OPERATION.. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 05 C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES. 5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS) 6. RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK. 7. DISCA CONNECTOR PL WHEN INSTALLING OPTIONAL HEAT KIT. 8. THE CONDENSATE ALARM SWITCH (CAS) TERMINALS CAN ONLY BE UTILIZED WITH COMMUNICATING MODE SETUPS AND MUST BE ENABLED WITH A COMMUNICATING THERMOSTAT. THIS FEATURE IS NOT OPERATIONAL WITH LEGACY SYSTEMS. USE N.E.C CLASS WIRE. LOW VOLTAGE (4V) LOW VOLTAGE FIELD HI VOLTAGE (30V) HI VOLTAGE FIELD JUNCTION TERMINAL INTERNAL TO EQUIPMENT FIELD FIELD SPLICE RESISTOR OVERCURRENT PROT. DEVICE PLUG CONNECTION COLOR CODES: PK ---- PINK BR ---- BROWN WH ---- WHITE BL ---- BLUE GY ---- GRAY ---- RED YL ---- YELLOW OR ---- ORANGE PU ---- PURPLE GN ---- GREEN ---- BLACK 040A0044-B Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. SS-DVPVC www.daikincomfort.com 7
Notes Our continuing commitment to quality products may mean a change in specifications without notice. 06 daikin manufacturing company, l.p. Houston, Texas Printed in the USA. 8 www.daikincomfort.com SS-DVPVC