Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

Similar documents
Influence of the operating time on the behavior of smoke alarms in typical office environments

SupDET 2015 Characterization of Dust and Water Steam Aerosols in False Alarm Scenarios

THE NEXT GENERATION IN VISIBILITY SENSORS OUTPERFORM BOTH TRADITIONAL TRANSMISSOMETERS AND FORWARD SCATTER SENSORS

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

UL268 7 th challenge with single infrared smoke detector

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

Research on Evaluation of Fire Detection Algorithms

Characterising the smoke produced from modern materials and evaluating smoke detectors

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment

15 th International Conference on Automatic Fire Detection PROCEEDINGS. October 14-16, 2014 Universität Duisburg-Essen Duisburg, Germany

Fact File 66. Guide to Beam Smoke Detectors

A Model of the Population of Fire Detection Equipment Based on the Geometry of the Building Stock

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

OH110, OP110, HI110. Automatic Fire Detectors. Automatic Fire Detector For collective and conventional detector lines

COMITÉ EUROPÉEN DES ASSURANCES

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Smoke Detector Testing

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

INTRODUCING SOTERIA, POWERED BY COREPROTOCOL APOLLO'S MOST ADVANCED FIRE DETECTION SYSTEM

Computer Modelling and Simulation of a Smart Water Heater

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

ALK-V PHOTOELECTRIC SMOKE SENSOR

Loss Prevention Standard

TSI AEROTRAK PORTABLE PARTICLE COUNTER MODEL 9110

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

The new detector from Rafiki

Research into multi-sensor detector capabilities and false alarm reduction

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

200 SERIES ADVANCED PHOTO/THERMAL/IR DETECTOR PRODUCT SPECIFICATION

Towards Predicting High Sensitivity Smoke Detector Operational Performance in Building Environments

Multi-Point Peripherals

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

Development of high sensitivity radon detectors

FEATURE ARTICLE. The PLCA-800 Series Inline Particle Sensor for Chemical Solutions. Yoshihito Yuhara. Abstract

DUR 40Ex Intrinsically Safe SMOKE DETECTOR

S TEM PRODUCT SPECIFICATION

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

M-20 Oil Mist Concentration Detection and Alarm Device

A GEM-based detector for detection and imaging sparks and flames G. Volpe 1 and V. Peskov 2. Abstract

Application Note. Application Note for BAYEX

Bristol Babcock Oil Content Monitor "oil in water"

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

by Richard W. Bukowski Center for Fire Research Program for Fire Detection and Control Systems National Bureau of Standards Washington,

The Compact Muon Solenoid Experiment. Conference Report. Mailing address: CMS CERN, CH-1211 GENEVA 23, Switzerland

Procedure for the Approval of New Fire Detection and Alarm Technologies

Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team

ENSC 388: Engineering Thermodynamics and Heat Transfer

optical detector multisensor detector heat detector mounting bases product guide

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

(12) Patent Application Publication (10) Pub. No.: US 2017/ A1

THEORY OR OPERATION 2 SENSOR UNIT - MECHANICAL 6 SENSOR UNIT - ELECTRICAL 8 CONTROL UNIT - MECHANICAL 9 CONTROL UNIT - ELECTRICAL 9 OPTIONS 11

The Basics: Summary. Objectives. for the experiment: teacher prep, for each table of 3-4. California Content Standards Addressed. for journal prompt:

Consultant Specification AGILE Wireless Fire Detection System

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR

Fire Sensor Data logging

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles

FCP 320/FCH 320 Conventional Automatic Fire Detectors

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Cereal Seed Health and Seed Treatment Strategies: Exploiting new seed testing technology to optimise seed health decisions for wheat.

Instruction Manual. gray Mounted Detectors. for. greenteg AG Technoparkstrasse Zürich, Switzerland T: F:

Tatsuya Yamaguchi, Hiroshi Ohno, Yu Matsumoto, Taiyo Matsumura, Yukitaka Shinoda, Takashi Ono Nihon University, Tokyo, Japan

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

Optical Measurement Techniques for LED Clusters and LED Safety

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

The performance of multi-sensors in fire and false alarm tests

EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS

Installation and Operation Manual

Conventional Detectors

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Use of MCNPX for Alpha Spectrometry Simulations of a Continuous Air Monitor

Smoke Alarm Research at NIST

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

Understanding total measurement uncertainty in power meters and detectors

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

The development of seat fire testing for EN Richard Nowell

Guidance on Video Smoke Detection Technology (VSD)

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Available online at Procedia Engineering 45 (2012 )

InstrumentationTools.com

OH110, OP110, HI110 Automatic fire detectors

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

Residential Cluster, Ahmedabad: Housing based on the traditional Pols

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

ISO INTERNATIONAL STANDARD. Coating powders Part 13: Particle size analysis by laser diffraction

Temperature dependent Components within the Pyroelectric Detector

Effect of characteristics of unsaturated soils on the stability of slopes subject to rainfall

Series 65 Product Guide MAN 3036

A Review of Hydronic Balancing of Cooling Water Circuit

Transcription:

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors Stephen Ellwood AW Technology Ltd, Earl Shilton, Leicestershire, United Kingdom Abstract A review on the limits to the compensation applied to smoke detectors is being carried out to enable a revision of the clauses in EN54 standards relating to the response to slowly developing fires. The effects of sensor non-linearity and maximum output are understood, but data on the effects of contamination on the sensitivity and the sensor signal were not available. The effects on optical scatter smoke sensing chambers are considered here as they are the most commonly used type. A simple general mathematical model is presented which can calculate the limit of compensation when the response value is increased by a factor of up to 1.6. Some practical tests were carried out on a typical optical scatter smoke sensor with dust applied to the inside surfaces of the chamber. These indicated that when only considering the optics of the sensor the limits may be large compared with the increase in signal to an alarm of a new detector. Keywords, Optical smoke sensor, contamination, compensation, dust Introduction Smoke detectors include algorithms that compensate for changes in the sensor output with no smoke present. The changes could be due to short term variations in temperature, long term ageing of sensor components or contamination on surfaces. The response to slowly developing fires clauses in EN54 standards are intended to limit the rate of compensation so that any correction for short term changes does not significantly delay the response to a slowly developing fire. They also limit the range of compensation so that the response value of the detector will not get significantly greater than when it was newly manufactured. The effects of sensor non-linearity and maximum sensor output are already understood.

This work is intended to quantify some effective limits for compensation when considering the effect of contamination. As a smoke sensor becomes contaminated the signal without smoke can either decrease or increase. The sensitivity to smoke can also change. A simple analysis shows that the worst case for compensation is when the signal increases, but the slope sensitivity of the sensor decreases. The compensation will increase the alarm threshold, which will then increase the overall detector response value rather than help to maintain it at a constant value. This situation could occur if an optical scatter smoke sensing chamber is contaminated with light coloured dust which increases scatter but partially blocks the optics. Aging of components could also decrease the sensitivity of the sensor, but this normally tends to decrease the signal. The aim here is to model how the sensitivity of a detector will change as the sensor becomes contaminated. Some tests will also be carried out on a typical optical scatter smoke sensor chamber in order to establish a limit for compensation in this case. General model of change of sensitivity with increasing sensor contamination A general model of the change in sensitivity with increasing contamination is proposed that could apply to any type of smoke sensor, but point optical scatter detectors are used as an example. In the following the sensor output is expressed as a voltage (V) and the smoke concentration as m value (as defined in EN54-7 [1]). Compensation for an increase in the output without smoke (V0) is assumed to result in an equivalent increase in the alarm voltage (Va), and as also shown in [2]: (Va Vanew) = (V0 V0new) V (Eq. 1) Assuming a linear response the sensor slope gain (S) is defined as the increase in sensor output divided by the smoke concentration: S = (V V0) / m V/dB/m (Eq. 2) V is the sensor output at smoke concentration m db/m. S new refers to the sensor slope gain of a new sensor. alarm is the increase in the alarm threshold scaled by the difference between the alarm threshold and sensor output with no smoke for a new detector (Vanew V0new). It is often refered to as the number of alarm thresholds. If the increase in alarm threshold since the detector was new is (Va Vanew), then: alarm = (Va Vanew) / (Vanew V0new) (Eq.3) If the slope gain decreases by the same proportion for each alarm, then this will result in an exponential decay in slope gain:

S = S new * e -( alarm /C) V/dB/m (Eq. 4) C is a constant that controls the rate of decrease of slope gain with alarm. The EN54 smoke detector standards require that compensation of Va for changes in the sensor output without smoke is limited to maintain the response value close to the new condition. This is equivalent to a decrease in slope gain by a factor of up to 1.6. At this limit S / S new = 1/1.6 = e -( alarm/c) (Eq. 5) If the rate at which the slope gain decreases as the no smoke signal increases is known, then it is possible to calculate the maximum increase in Va that will enable the detector to remain within the requirements of EN54 standards. alarm = - C * ln(1/1.6) (Eq. 6) Some examples are given in table 1 below. Table 1. Example calculation of alarm to decrease the slope gain by a factor of 1.6. Fractional loss in the slope gain for each alarm Constant C alarm to decrease the slope gain by a factor of 1.6 0.05 19.50 9.16 0.10 9.49 4.46 0.20 4.48 2.11 0.30 2.80 1.32 0.40 1.96 0.92 0.50 1.44 0.68 The above indicates that if the slope gain varies slowly with increases in Va then the compensation can increase the alarm threshold by a large alarm. But if for example slope gain decreases by a factor of 0.2 for each alarm, the compensation of Va has to be limited to 2.11 * alarm to keep the detector within the requirements of EN54 detector standards. Some examples showing how the gain decreases, with different values of the constant C, are plotted in Fig. 2 which also shows the results of practical tests. Practical tests It is difficult to predict the degree to which the slope gain will change with increases in the sensor output without smoke as the nature of contamination, and the degree of aging, will vary with the environment in which the detector is sited.

Some test equipment has been proposed [3] which simulates the exposure of the complete detector to dust that can cause false alarms [4]. This paper is mainly concerned with the direct response of the optics to long term exposure to dust so it was directly applied over internal surfaces of the sensing chamber. Some practical contamination tests were carried out by the author. These were intended to test the model and to establish some realistic values for the constant C. The tests were carried out on a typical single wavelength, single angle, optical scatter smoke sensing chamber as this is the most common type in use. The chamber was taken from a production example of a smoke detector complete with the LED emitter and photodiode receiver. This was connected to a test circuit with a simple voltage output so that any effects of algorithms within the detectors are not included in the response. Contamination was applied by exposing sensor chambers to dust deposited evenly over the inside surfaces, including the surfaces of the emitter and receiver. This was applied using a soft brush. The dust was collected from the offices of AW technology, and the distribution of the dust was checked using a microscope. This technique is not intended to simulate a particular environment as the dust is applied directly, but has been shown to be a useful development tool for comparative measures of the effect of contamination on smoke sensor chambers. It is a method that could be used for determining realistic values of the constant C, and thereby the limit that can be placed on the alarm threshold compensation to remain within the requirements of the EN54 standards. The sensitivity tests were carried out in an AW Technology 1800 smoke / heat detector test tunnel, which conforms to the test requirements of EN54-7. The output voltage of the test circuit was measured in clean air and then at increasing aerosol concentration in 0.1dB/m steps. The slope gain in a clean condition (Snew) and with dust applied (S) could then be calculated from these measurements using Eq. 2. The calculation of alarm was made using a simple alarm threshold of 0.15dB/m when the chamber was clean. The dust on the chamber surface is shown in Fig.1. It incudes a lot of fibrous material and small particles of mineral grit. It is a very high level of contamintation, greater than would be expected inside a smoke sensing chamber even after 10 years in a normal environment. Fig. 2 shows the values of S / Snew plotted against alarm for the optical scatter chamber tested, together with calculated values using different values of the constant C. Of the three values plotted the data is a best fit to C = 9.49, which corresponds to a decrease in gain of 10 % for each alarm.

A decrease to a S / Snew of 1/1.6 would then occur on average at a alarm of 4.46, which could be used as a limit of compensation when considering the effects of contamnination by dust. Fig. 1. Dust on surface of smoke sensing chamber at a alarm of 4.4. Fig. 2. Results of tunnel tests on smoke chamber after contamination with dust. Comments The model used was intended to provide a stimulus for discussion in the consideration of the limits to the compensation. It was not intended to accurately model to optics of the sensor, but to enable discussion

about the limits to compensation in terms of the number of alarm thresholds ( alarm). It helps to answer the question about the increase in response value by a factor of 1.6, if the reduction in slope gain is XX% per alarm threshold. It is recognised that different types of smoke sensor will have different laws controlling the change in sensitivity with increasing contamination. The main conclusion from this work is that a typical optical scatter smoke sensor can be highly contaminated by dust before the sensitivity change will cause an increase in the response value by more than a factor of 1.6. In practice it will be very hard to achieve this level of contamination inside a smoke sensive chamber without the entrance to the smoke sensor or insect screen becoming partially blocked, which would also increase in the response value when measured in a smoke tunnel. It is also possible that in very dusty environments false alarms could occur while dust particles are still air-borne within the chamber. In the calculation of the limit of compensation of Va for changes in V0 several factors need to be considered together. The decrease in slope sensitivity due to increasing contamination is only one consideration and is discussed in this paper as it was thought to be the least understood. This work is being used by a group that has been tasked by CEN TC72 to review and revise the Response to slowly developing fires clauses within EN54 detector standards. The author is a member of this task group and the contribution from the chairman and other members is acknowledged. It is intended that the results presented here will be a contribution to the work of the task group as this data was not previously available. References [1] EN54 part 7, Fire detection and fire alarm systems Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionization, English version EN 54-7:2000. [2] F Daniault, Drift compensation and detection of slowly developing requirements and assessment in EN 54 - Part 1: Introduction, EUSAS February7-8, 2017, Berlin, Germany. [3] W. Krüll, T. Schultze, R. Tobera, I. Willms, Apparatus for the test of fire detectors in dusty environments, 15th International Conference on Automatic Fire Detection, AUBE '14, Duisburg, Germany, October 2014. [4] W. Krüll, T. Schultze, R. Tobera, I. Willms, Characterization of dust aerosols in false alarm scenarios, 15th International Conference on Automatic Fire Detection, AUBE '14, Duisburg, Germany, October 2014.