Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Similar documents
PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL INSTALLATION MANUAL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

Unity DAU Voice Alarm System

CFDAU30 Voice Alarm System

USER MANUAL & MAINTENANCE GUIDE OG OO

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions PANEL 1.84 & LOOP 3.70

Excel-EN Conventional Fire Control Panel

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

5000 INSTALLATION GUIDE

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation, Operating and Maintenance Manual

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

Intelligent Security & Fire Ltd

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

FEC400 Series. Installation Manual

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

EXTINGUISHING AGENT RELEASE MODULE

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Control Panel Engineering and Commissioning Instructions

16 Zone Voice Evacuation VA & PA Sound System

Intelligent Security & Fire Ltd

Product Data Sheet. Remote Terminals. Features:

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Vocia VACIE. Reference Guide

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

VACIE REFERENCE GUIDE REVISION 1.2.6

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

Operation and Maintenance Manual

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

DIVA8MG2. Compact PAVA System Master Unit. DIVA8 System

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

System 800 Addressable Fire Detection & Alarm System

Precept Marine Control Panel Application Guide

35(0,(56; ),5($/$50 &21752/3$1(/ 86(50$18$/ 0$,17(1$1&(*8,'( /2*%22.

SIMPLICITY MICRO INSTRUCTION MANUAL ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTRUCTION MANUAL

July 14, 1999 DF C-100.

Silent Alert Fire Safe System

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9

VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

New Silent Alert Fire Safe System

LOG BOOK & CERTIFICATES

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

FIRE ALARM CONTROL PANEL FVC01-08

Surveyor Envoy-MINI 4

June 10, 2002 DF C S2424

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply Display Module PSDM. Installation and Operation Manual

VSN PLUS VSN 4 PLUS ; VSN 8 PLUS ; VSN 12 PLUS

Fire detection and alarm

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Entero Voice Alarm system. User guide

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

APPLICATION DATA SHEET

Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) User Operational & Maintenance Manual

Promatrix 6000 I EN de I 1. ISO7240 PAVIRO. Installer checklist

Intelligent Security & Fire Ltd

PREMIER AD INSTALLATION MANUAL. Software:31/3/04 & LC6 CONTENTS

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

ZFP Networkable Analogue Addressable Fire Alarm Control Panel

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

SP40S-D. Kingfisher Company, inc. Features: Description:

Entero Voice Alarm system.

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

OmniCare EVC System. Installation & Commissioning Manual

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Public Safety DAS Annunciator Panel

ECC-50/100C. Emergency Command Center

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Transcription:

Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1

INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation information... 5 Battery information... 5 Product disposal at the end of its working life... 6 Locating the Voice Alarm panel... 7 Fixing the back box to the wall... 7 Recommended cable types and their limitations... 8 Mains wiring recommendations... 8 Mounting the fire alarm control panel... 8 Planning cable entry... 9 Display & Controls... 10 Display... 10 Controls... 11 Speaker Circuits... 11 Wiring the Speakers... 11 Configuring the Voice Messages, and Trigger Inputs... 12 Speaker Circuits... 14 Wiring the Speakers... 14 Methods of Operating the Premier Evacs 16... 15 Resetting from a Voice Alarm Condition... 15 Fault display & fault-finding... 16 Fault Finding... 16 Power Supply fault... 16 Speaker Circuit Fault... 17 Earth Fault... 17 Amp Fault... 17 System Fault... 17 Specifications... 18 Electrical Specifications... 18 Enclosure Specifications... 18 Fuse Ratings... 18 Approved Document No: GLT.MAN-141 PAGE 2

Summary The Premier Evacs 16 is a 16 zone (or channel) voice alarm system which has 15 Watts per Zone Output. It has 2 pre-recorded messages, which can be altered with the Voice alarm software, and USB connection. The pre-recorded messages can be initiated either via the unit`s keypad, or via one of the 18 remote input triggers. The triggers may be provided by the outputs of a fire alarm control panel / control & indicating equipment (CIE). It has an emergency (or fireman s) microphone which can be used to broadcast live messages The system itself uses 4 quad amplifiers to provide the 16 zones. This configuration allows mixed messaged to be played on different zones. The Evacs 16 is available in 4 versions: Model No EVAC16/4 EVAC16/8 EVAC16/12 EVAC16/16 Part No 180-100 180-101 180-102 180-103 No of Zones 4 8 12 16 Output / Zone 15 Watts 15 Watts 15 Watts 15 Watts Total Power 60 Watts 120 Watts 180 Watts 240 Watts Approved Document No: GLT.MAN-141 PAGE 3

12V Sealed Lead Acid Batteries (Max Capacity 12Ah) Approved Document No: GLT.MAN-141 PAGE 4

Safety information & use of this manual WARNING: Read this section completely before operating this equipment. Installation information THIS VOICE ALARM CONTROL & INDICATING EQUIPMENT (VACIE) IS CLASS 1 EQUIPMENT AND MUST BE EARTHED. This equipment must be installed and maintained by a qualified and technically experienced person. This VACIE. must be wired to a fused spur rated at 3A. It must NOT be connected via a removable plug, or be connected through an RCD device. Prior to commencing installation of the control panel, ensure that adequate precautions are taken to prevent damage to the sensitive electronic components on the display board and the control board due to electrostatic discharge. You should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe. You should repeat the process at regular intervals during the installation process, especially if you are required to walk over carpets. The panel must be located in a clean, dry position, which is not subject to excessive shock or vibration and at least 2 metres away from pager systems or any other radio transmitting equipment. The only items which are designed to be removed from the enclosure, are the cable connectors. Ensure that all electrical power is removed from the equipment before removing, inserting or connecting cables to these connectors. Battery information This VACIE. uses 2 x 12V Sealed Lead Acid (SLA) batteries with a maximum capacity of 12Ah. CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO BATTERY MANUFACTURERS INSTRUCTIONS. IMPORTANT NOTES ON BATTERIES: DANGER: Batteries are electrically live at all times. NEVER short circuit the battery terminals. WARNING: Batteries are often heavy. Take great care when lifting and transporting batteries. DANGER: Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery. Electrolyte is a highly corrosive substance, and presents Approved Document No: GLT.MAN-141 PAGE 5

significant danger to yourself and to anything else it touches. In case of accidental skin or eye contact, flush the affected area with plenty of clean, fresh water and seek immediate medical attention. Valve Regulated Lead Acid (VRLA) batteries are low maintenance, requiring no electrolyte top-up or measurement of specific gravity. Product disposal at the end of its working life Like all electronic equipment, at the end of its working life this unit should not be disposed of in a refuse bin. It should be taken to a local reprocessing site as per the guidelines of the WEEE directive, for correct disposal. Approved Document No: GLT.MAN-141 PAGE 6

Locating the Voice Alarm panel The control panel should be installed in accordance with the following recommendations:- The panel should be close to the main entrance of the building, so that it can be viewed by any fire-fighting personnel entering the building. It should be fitted to a sturdy wall that will not flex unnecessarily. It should be mounted at eye level, in order for it to be viewed without need of a ladder. It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight. It should be easily accessible, so that the responsible person can perform their regular fire alarm checks. Fixing the back box to the wall Plan view inside the enclosure without PCBs. Side view for surface installation. (Dimensions: mm) Fix the enclosure to the wall using the four mounting holes provided. Check the build & condition of the wall to decide a suitable screw fixing. The mounting holes are designed for No 8 roundhead or countersunk woodscrews (or similar). Remove any debris from the enclosure. Approved Document No: GLT.MAN-141 PAGE 7

Recommended cable types and their limitations All wiring must be installed to meet BS5839: Pt1: 2002 + A2:2008 and BS 7671:2008 (IEE Wiring Regulations) standards. Other National standards of fire alarm system installation should be adhered to where applicable. Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC compatibility. The two categories of cable according to BS5839: Pt1: 2002 + A2:2008, Clause 26 Fire Detection and Alarm Systems for Buildings (Code of Practice for System Design, Installation and Servicing) are: Standard fire resisting cable to PH30 classification of EN 50200 (including the 30 min survival time of Annex E) Enhanced fire resisting cable to PH120 classification of EN 50200 (including the 120 min survival time of BS 8434-2) (Note that all cables should be at least 1mm 2 cross section On the Premier Evacs16 Panel the general recommendation would be to use standard fire resistant cable, such as GLT Exports Fire Defence Cable, Firetuff, FP200 or an equivalent. These cables are screened, and will provide good EMC shielding when properly grounded at the panel. Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact. Depending on the environment, the cables may need mechanical protection (such as a conduit). Mains wiring recommendations The Mains supply to the VACIE is fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), fed from an isolating double pole switch fused spur, fused at 3A. IT SHOULD NOT BE CONNECTED THROUGH AN RCD. This should be secure from unauthorised operation and be marked FIRE ALARM: DO NOT SWITCH OFF. The supply must be exclusive to the Fire Panel. MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED Mounting the fire alarm control panel The Premier Evacs16 comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the panel door is removed to avoid accidental damage. Also, the back plate which holds the loop cards and power supply should be removed and stored in a safe place. This would also help while fixing the back box to the wall. Approved Document No: GLT.MAN-141 PAGE 8

Planning cable entry The figure below shows the location of the cable entries to facilitate planning of wiring to be brought to the panel. The grommets can be easily removed by a push from inside the control panel box. If a grommet is removed, fill the hole with a brass cable gland. If any knockout is removed, but subsequently not used, it should be covered up. The 230Va.c. Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box. This cable must be connected to the mains EMI filter. The terminals on the EMI filter are labelled N G L (Neutral Ground/Earth Live). Take care not to damage the VACIE during installation. EMI FILTER Approved Document No: GLT.MAN-141 PAGE 9

Display & Controls Here is the fascia for the Premier Evacs16. Display The Premier EVACS16 has the following LED indicators:- LED COLOUR MEANING POWER ON GREEN The system has mains and/or battery backup present. The panel showing this LED only is the normal condition SYSTEM FAULT YELLOW The system may have developed a serious problem. Contact your local dealer POWER FAULT YELLOW The System s PSU is reporting a problem EARTH FAULT YELLOW The system has detected a wiring fault shorting to earth AMP FAULT YELLOW There is problem with one of the systems amplifiers COMMON FAULT YELLOW There is a fault on the system. Check specific LED for further information. COMMON ALARM RED The system is playing the pre-recorded evacuate message. COMMON ALERT RED The system is playing the pre-recorded alert message. MIC ACTIVE RED The panel`s live emergency microphone is being used to REMOTE MIC ACTIVE ALARM / ALERT ZONE 1 16 FAULT/DISABLE ZONE 1-16 RED RED YELLOW broadcast a message. The panel`s remote microphone is being used to broadcast a message The indicated zone(s) are playing the Alarm or Alert message (as indicated by the common Alarm/Alert LEDS) The indicated zone (s) have a fault, or are in the disabled condition. Approved Document No: GLT.MAN-141 PAGE 10

Controls The Premier Evacs 16 has the following controls:- LABEL USE TEST Reserved for future use ALARM Used to initiate manual playback of the Evac / Alarm Message ALERT Used to initiate manual playback of the Alert Message DISABLE Used to disable one or more of the speaker channels SILENCE Used to silence the panels fault buzzer RESET Used to reset the system from the voice alarm condition STOP / START Used to Manually start playback of a selected message, or to stop an existing message. 1-16 Select buttons for channels 1 to 16 Speaker Circuits Wiring the Speakers The Premier Evacs 16 checks for line integrity by using a 10K End of Line Resistor on each speaker circuit. SND+ SND- SOUNDER + + - - SOUNDER + + - - SOUNDER + + - - SOUNDER + + - - 10K End of Line Resistor When the circuits have been connected if the panel reports a zone fault, check that the EOL resistor is securely connected and is the correct value. Approved Document No: GLT.MAN-141 PAGE 11

Configuring the Voice Messages, and Trigger Inputs On the Premier Evacs 16, the Voice messages can not be recorded at the panel. We have decided that this is not a suitable method of recording, as background noise, and probable poor acoustics would mean a poor quality message. Instead any suitable Audio file can be uploaded. The file format is *.wav format, 16 bit, 1 channel, uncompressed 16,000 samples/sec (256kbps) A custom message can be recorded on a PC, or in a sound studio if the best sound clarity is required. Alternatively, you can use one of the sample messages provided with the PC Configuration Software. The Evacs 16 has 18 trigger inputs. There are inputs to play the Evacuate / Alarm message on all zones, the Alert message on all zones, and an individual input for each zone, which can be configured via the PC Configuration Software. Sample configurations are:- Play alarm message on selected zone, Play alarm message on selected zone, and alert message on all other zones Play alarm message on selected zone, and alert on floor above & floor below. For Details on configuring these options via a PC, please refer to PREMIER EVACS 16 PC CONFIGURATION MANUAL (GLT.MAN-142). Approved Document No: GLT.MAN-141 PAGE 12

PC Configuration Software This PC-based software package includes the following options: 1. Select alert message 2. Select alarm / evacuate message 3. Select the sign-on and sign-off tones for the emergency microphone message 4. Move sliders to adjust speaker volume 5. Choose which message should be played on each channel For full details on configuring these options via a PC, please refer to PREMIER EVACS 16 PC CONFIGURATION MANUAL (GLT.MAN-142). Approved Document No: GLT.MAN-141 PAGE 13

Speaker Circuits Wiring the Speakers The Premier Evacs 16 checks for line integrity by measuring the impedance of the speaker line. It does not need an end of line element. SND+ SND- SOUNDER + + - - SOUNDER + + - - SOUNDER + + - - SOUNDER + + - - 10K End of Line Resistor When the circuits have been connected the panel will report circuit faults. Press the Calibrate button on the rear of the display PCB to store the new line impedance settings. Approved Document No: GLT.MAN-141 PAGE 14

Methods of Operating the Premier Evacs 16 The Premier Evacs 16 can operate in any one of the following ways:- 1. LIVE BROADCAST The microphone is used to broadcast information about the alarm, and the responsible person would direct occupants what to do next. The Microphone broadcasts to all non-disabled channels. 2. PRE-RECORDED MESSAGE (MANUAL) The Operator can select to play the pre recorded Evacuation or alert message to individual speaker channels. The message(s) are only played to the selected channels. 3. PRE-RECORDED MESSAGE (AUTOMATIC) Some or all of the Premier Evac 16`s remote trigger inputs will be connected to I/O units in a fire panel. The panel will operate the I/O relays to link the relevant trigger to 0V. There are inputs for Evac on all channels, Alert on all channels, and an individual input for each channel, which can be configured via the PC Software. Sample configurations are:- Play evac / alarm on selected channel, Play evac / alarm on selected channel, and alert on all other channels Play evac / alarmon selected channel, and alert on floor above & floor below As shown above, the number of channels operated will depend on the configuration of the remote inputs. Resetting from a Voice Alarm Condition The Evacs 16 can be reset in various ways, depending on how the Voice alarm condition was initiated. If the microphone is used for a live broadcast, simply releasing the microphone will return the Evacs 16 to it`s normal condition. If a pre-recorded message was started manually, it will need to be reset from the Voice Alarm Panel. Press Start/Stop to stop playing the message, then press reset to return the Evacs 16 to it`s normal condition. If a pre-recorded message was started automatically by a fire alarm panel, resetting the fire alarm panel will reset the Voice alarm panel automatically. Alternatively, the message can be stopped by pressing Stop/Start on the Voice alarm Panel. (Note if reset is then pressed, and the triggering signal is still active, the Evacs 16 will return to the voice alarm condition. Approved Document No: GLT.MAN-141 PAGE 15

Fault display & fault-finding The Premier Evacs 16 panel monitor for the following faults:- Power Supply Fault Speaker Channel open circuit wiring fault Speaker Channel short circuit wiring fault Earth Fault Amplifier Fault System Fault The Premier Evacs 16 Voice Alarm panel also has a General Fault LED that will light when any fault is present. Most of these faults will need to be checked by an engineer. All faults in the Premier Evacs 16 are NON-LATCHING. IE they can not be reset with the reset button. They will clear automatically when the fault has been fixed. Fault Finding Power Supply fault A power supply fault is indicative of one or more of the following faults: - Loss of Mains power Check that 230V AC is present at the mains terminal block Check mains fuse Check charger fuse FS1. Loss of Battery power Loss of Charger Check that 2 X 12V batteries are fitted in series to give 24V backup Check battery fuse Check that battery connections are secure. Check that the batteries are not over 5 years old The Power supply will monitor the charger circuit. In the rare event of a component failure that affects the charger, the PSU will bring up a fault. Loss of Battery Capacity The Power supply will monitor the Battery condition. If it detects a high internal resistance, which usually means a loss of capacity in the battery, it will bring up a fault. Approved Document No: GLT.MAN-141 PAGE 16

Speaker Circuit Fault A Speaker Circuit Fault is indicative of one or more of the following faults:- Speaker Circuit Open Circuit fault. Check that there are no breaks in the cable, and that all screw connections are secure. As a panel check, disconnect the circuit indicating the fault, and press the calibrate button. If the fault clears, the panel is working correctly. Speaker Circuit Short Circuit Fault Speaker Failure Check that all speakers are fitted the correct way round. Check than no other devices have been connected to the speaker circuit. Check for shorts to the cable screen. As a panel check, disconnect the circuit indicating the fault, and press the calibrate button. If the fault clears, the panel is working correctly. Because the Premier Evacs 16 monitors the speaker circuits for a change in impedance, the system can usually detect a broken speaker. For example a broken wire to the drive cone will not effect the speaker line`s continuity, but it will effect its impedance. Presently, the only way to check for this is by verifying sound output at each speaker on the speaker circuit reporting the fault. Earth Fault The Premier Evacs 16 monitors it`s cabling for short circuits to earth. In the event of an earth fault, disconnect the speaker circuits one at a time to locate the one giving a problem. Amp Fault The Premier Evacs 16 monitors Amplifiers for correct operation. If one of it`s power amps reports a fault, the Evacs 16 will report it. Try resetting the panel to clear the fault. If the fault persists, contact your dealer. System Fault The Premier Evacs 16 monitors its internal software for correct operation. If it detects a possible problem, the Evacs 16 will report it. Try resetting the panel to clear the fault. If the fault persists, contact your dealer. Approved Document No: GLT.MAN-141 PAGE 17

Specifications Electrical Specifications ELECTRICAL DESCRIPTION MAINS VOLTAGE BATTERY VOLTAGE CHARGER SIZE SPEAKER LINE VOLTAGE SPEAKER LINE CIRCUITS FAULT OUTPUT PANEL INPUTS CHARGER VOLTAGE MAINS FAILED CURRENT (BUZZER ON) MAINS FAILED CURRENT (BUZZER OFF) VALUE 230V AC +/- 10% @ 50/60 Hz 24V DC (2 X 12V SLA BATTERY) 920mA 100V 16 x 15 Watt 1 x RELAY SELV (1A MAX) 1 X COMMON EVACUATE 1 X COMMON ALERT 16 X PROGRAMMABLE 27.6V DC (NO BATTERY CONNECTED) 210mA 150mA Enclosure Specifications DESCRIPTION ENCLOSURE SIZE TOP CABLE ENTRIES BOTTOM CABLE ENTRIES VALUE 485 x 732 x 147 mm 36 x 19mm DIA GROMMETED ENTRIES 6 x 19mm KNOCKOUT ENTRIES Fuse Ratings FUSE NO DESCRIPTION RATING FS1 Charger Fuse 1.6A time delay 5 x 20mm glass FS2 Battery Fuse 1.6A time delay 5 x 20mm glass FS3 Sounder circuit) 800mA time delay 5 x 20mm glass INLET FUSE Mains Protection Fuse 2A Quick Blow HBC 5 x 20mm ceramic Approved Document No: GLT.MAN-141 PAGE 18