VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

Similar documents
VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 100. for heating engineers

VIESMANN VITOLADENS 300-T Oil Unit condensing boiler 35.4 to 53.7 kw

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN VITOLADENS 300-C Oil condensing boilers 12.9 to 28.9 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Operating and service instructions VITOMAX 200-HW. for contractors

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

Baxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus. User s Operating Instructions

General safety precautions English

Operating instructions

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Operating instructions

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

User Guide. Promax SL Condensing Central Heating Boiler

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

Operating instructions Oil condensing boiler

General safety precautions English

Baxi Maxflow Combi WM

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

User manual. Logano GC 124 II. Gas boiler

Performa 24. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

USERS MANUAL FOR GAS BOILERS

USERS GUIDE. LOGIC+ Combi 24, 30, 35

Osprey 2 CFL

Baxi Combi 80Eco. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Installation Instructions VITOTRONIC 300

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

Operating instructions Page 12

ir-range 8G /03.15 Changes reserved.

Baxi Maxflow Combi FS

Logic+ Combi

Operating instructions

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE

For the owner. Operating manual. ecotec plus 937. Gas condensing storage combination boiler VUI

Operating instructions

DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors

FR 10 INSTALLATION & USER INSTRUCTIONS INTELLIGENT ROOM THERMOSTAT

Operating instructions

WHE 2.24 / WHE 2.24 FF

USER GUIDE LOGIC HEAT H

Baxi Megaflo System HE IE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Boiler

User Guide and Important Warranty Information. Suprima HE. Condensing Central Heating Boiler. Please read this document and keep it safe.

Test Unit GTL 100 for Fire Detectors

Operating instructions

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

INSTALLATION AND USER INSTRUCTIONS COUNTERTOP AND FREE STANDING FRYERS

DANESMOOR FRONT SERVICE (FS) 12-18, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

User Guide and Important Warranty Information. Suprima HE Range. Condensing Central Heating Boiler. You can rely on

Device Technology. Supply Operating voltage Implemented via the bus KNX: V DC XIB: 12 V DC (rated voltage) Voltage range: 10.

Transcription:

Installation and service instructions for contractors VIESMANN Vitotrol 300A Remote control, part no. 7438 364 VITOTROL 300A 3/2010 Please keep safe.

Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. Work on gas equipment must only be carried out by a qualified gas fitter. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Observe the following when working on this system all legal instructions regarding the prevention of accidents, all legal instructions regarding environmental protection, the Code of Practice of relevant trade associations, all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards, Gas Safety (Installation & Use) Regulations the appropriate Building Regulation either the Building regulations, the Building Regulation (Scotland), Building Regulations (Northern Ireland), the Water Fittings Regulation or Water Bylaws in Scotland, the current I.E.E. Wiring Regulations. If you smell gas Danger Escaping gas can lead to explosions which may result in serious injury. Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appliances ON or OFF. Close the gas shut-off valve. Open windows and doors. Remove all people from the danger zone. Notify your gas or electricity supplier from outside the building. Shut off the electricity supply to the building from a safe place (outside the building). 2

Safety instructions Safety instructions (cont.) If you smell flue gas Danger Flue gas can lead to life-threatening poisoning. Shut down the heating system. Ventilate the boiler room. Close all doors leading to the living space. Working on the system When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening. Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolator. Safeguard the system against unauthorised reconnection. Ancillary components, spare and wearing parts Please note! Spare and wearing parts which have not been tested together with the heating system can compromise its function. Installing non-authorised components and non-approved modifications/conversion can compromise safety and may invalidate our warranty. For replacements, use only original spare parts from Viessmann or those which are approved by Viessmann.! Please note Electronic modules can be damaged by electro-static discharges. Touch earthed objects, such as heating or water pipes, to discharge static loads. Repair work! Please note Repairing components which fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. 3

Index Index Installation instructions Installation sequence Installation location... 5 Installing and connecting the Vitotrol 300A... 6 Connecting several remote control units... 7 Fitting the programming unit... 9 Removing the programming unit (if required)... 10 Service instructions Commissioning Configuring the remote control... 11 Specification... 12 Parts list... 13 4

Installation sequence Installation location Weather-compensated mode Installation in any room. Operation with room temperaturedependent control On an internal wall in the living space, at a height of approx. 1.5 m from the floor Not near windows and doors Not above radiators Not near heat sources (direct sunlight, fireplace, TV set etc.) Do not install further controllers in this room. Open any thermostatic radiator valves fully. Note If the remote control cannot be installed in a suitable location, connect the room temperature sensor, part no. 7438 537, available as an accessory. Installation 5

Installation sequence Installing and connecting the Vitotrol 300A! Please note Electronic modules can be damaged by electrostatic discharges. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads. Connection Two-core cable with a cross-section of at least 0.75 mm; cores may be interchanged. Cable length up to 50 m. Note Never route the cable to the remote control immediately next to 230/400 V cables. 6

Installing and connecting the Vitotrol 300A (cont.) Installation sequence A D 4 3 2 1 13c 9 145 B Installation X4 7 6 5 4 X3 3 2 1 C A Vitotrol 300A B 2 or 3-pole plug avg (to the control unit or the KM BUS distributor) C Weather-compensated control unit with terminals X3 D Separate room temperature sensor (accessory) Connecting several remote control units Up to 2 remote control units can be connected to a boiler control unit, incl. a Vitotrol 200A and a Vitotrol 300A. Vitotrol 200A installation instructions 7

Installation sequence Connecting several remote control units (cont.) Version 1 4 3 2 1 4 3 2 1 B B 15 m 15 m A C A To the control unit or to the KM BUS distributor (see connection diagram on page 7) On-site connection via socket: Connect in accordance with the diagram B Vitotrol C Socket (on site) Limit the total length of all KM BUS cables to 50 m. Version 2 15 m 4 3 2 1 4 3 2 1 B 15 m B A D C A To the control unit or to the KM BUS distributor (see connection diagram on page 7) If several remote control units and additional KM BUS users are connected, make the connections via an onsite socket as shown in the diagram. 8 B Vitotrol C Socket (on site) D Further BUS subscribers Limit the total length of all KM BUS cables to 50 m.

Installation sequence Fitting the programming unit! Please note The remote control is supplied with power by the control unit. Do not insert batteries into the battery compartment. 3. 2. Installation 1. 9

Installation sequence Removing the programming unit (if required) 1. 2. 10

Commissioning Configuring the remote control Up to 3 heating circuits can be operated with one Vitotrol 300A; alternatively one Vitotrol 300A can be employed for each heating circuit in a single heating system. Up to 2 remote controls may be connected to the boiler control unit. 1. Switch ON the power supply on the control unit. The operating state of the heating system is transferred. A running bar appears in the display. 2. With / select the language. 3. OK as confirmation. 4. With / select the heating circuits and (if installed) the room temperature sensor to be controlled. 5. With / select "Save with OK". 8. OK as confirmation. The operating state of the heating system is transferred. A running bar appears in the display. This process may take several minutes. Note Whilst the bar is shown, pressing can display the configured heating circuits. Configuration has completed when the bar disappears. Note To return to configuration, press and simultaneously for approx. 4 s. If the heating circuit allocation is later cancelled, reset coding address A0 for this heating circuit to 0 (fault message bc, bd, be). 6. OK as confirmation. 7. With / select "Save Yes". Service 11

Specification Specification Power supply via KM BUS Power consumption 0.5 W Protection class III IP rating IP 30 to EN 60529; ensure through appropriate design and installation Permissible ambient temperature during operation 0 to +40 C during storage and 20 to +65 C transport Set room temperature range 3 to 37 C 12

Parts list Parts list When ordering spare parts Quote part no. 7438 364 and the pos. no. of the part (as per this parts list). Obtain standard parts from your local supplier. Parts not shown 080 Installation and service instructions 081 Operating instructions Parts 017 Wall mounting base 018 Programming unit 019 Cover, wiring chamber 017 018 019 Service 13

14

15

Printed on environmentally friendly, chlorine-free bleached paper 16 Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com Subject to technical modifications.