Project description and planning of large-scale tests in Runehamar tunnel

Similar documents
An experimental study of the impact of tunnel suppression on tunnel ventilation

EHAMAR EHAM HAM RUNEHA UNE. Summary of Large Scale Fire Tests in the. gram gra r. ram ra. n with the UPTUN Research Progra gr. el in.

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

Large scale fire tests with fixed fire fighting system in Runehamar tunnel

The first tunnel fire. Benefits of fire

Fire Spread in Large Industrial Premises and Warehouses

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Impact of quick incident detection on safety in terms of ventilation response

Sprinklers Modeling for Tunnel Road Fire Fighting

TUNPROTEC. Active Tunnel Fire Protection

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Laboratory fire experiments with a 1/3 train carriage mockup

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Hot Issues in Fire Engineering 12 March 2013

Development of a test method for fire detection in road tunnels

Tunnel Fire Dynamics

THE EFFECT OF A WATER MIST SYSTEM ON LARGE-SCALE TUNNEL FIRES

Test One: The Uncontrolled Compartment Fire

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

First Revision No. 6-NFPA [ Section No. 2.2 ]

FIBERSHIELD EW NEW PRODUCT LOW RADIANT HEAT TRANSFER ( PARTIAL PARTIAL INSULATION ) FIRE CURTAINS. Supported by full scale fire test data

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Overview of the PRISME project Technical Description and Main Outcomes

The Worldwide Use of Fire Sprinklers

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Early Suppression Fast Response Sprinklers and Obstructions

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE

Firefighter Safety in Battery Energy Storage System Fires

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

New European Cable Testing and Classification

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

Compression of Fins pipe and simple Heat pipe Using CFD

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Gothenburg dance hall, Sweden, 1998

Characterising the smoke produced from modern materials and evaluating smoke detectors

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Real-scale dwelling fire tests with regard to tenability criteria

Large-scale fire test for interior materials of the Korean high speed train

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires Phase 1: System Design and Function Evaluation

MINISTERIO DE FOMENTO

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Plan Submittal Checklist

Considerations in the Design of Smoke Management Systems for Atriums

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Crossrail. Clare Hebden; September 2012

Mobile ventilation units in tunnels

Comparison and Review of Safety Design Guidelines for Road Tunnels

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Structure Fires in Hotels and Motels

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

Fire Dynamics During the Channel Tunnel Fires

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION:

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

CERTIFICATION BULLETIN

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way


Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

Fire & Life Safety Design Considerations for the Tugun Bypass Tunnel

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

Test Report: ICL/H18/9039 Rev 1

THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE

The Loss prevention Council. Phase 1 report

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

FAÇADE FIRE TESTS Towards a new European standard method

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

Postprint.

Summary of International Road Tunnel Fire Detection Research Project Phase II

Transcription:

Project description and planning of large-scale tests in Runehamar tunnel August 2003 Prepared by: Haukur Ingason, SP Swedish National esting and Research Institute Anders Lönnermark, SP

able of content able of content...2 1 Introduction...3 2 Partners...3 3 Importance of study...3 4 est Programme...4 4.1 Laboratory tests...4 4.2 Large scale tunnel tests...6 4.3 Measurements...9 4.4 est programme...12 5 ime table...12

1 Introduction In recent years a number of road tunnels fires have occurred throughout Europe with catastrophic outcome. Among these are the fire in the Mont Blanc tunnel with 39 deads (1999), the auern tunnel in Austria with 12 deaths (1999) and the St.Gotthard tunnel in Switzerland with 11 deaths (2001). In these fires the semi-trailer cargo played a major role in the outcome. he main reason being that the trailers contain a very high fire load and the fire could easily spread with aid of the ventilation. he rescue services also had great difficulty in reaching the fire. hese fires have prompted the European Union (EU) to fund both a tunnel network (FI-Fires in unnels) and a research project dealing with the question of methods to upgrade the fire safety in existing tunnels (UPUN-Upgrating Existing unnels). he proposed experiments are unique in that no data of this detail, investigating catastrophic tunnel fires has previously been collected. he tunnel s unique location, together with its good condition, length and accessibility present one of the few places in the world where such experiments would be feasible. he tunnel is owned by the Norwegian Road Administration and we will work closely with them in performing these tests. 2 Partners Active UPUN 1 partners in the performance of the tests will be NO in Holland and SINEF/NBL in Norway. Associated partners from USA are the Port Authority in New York, the National Association of State Fire Marshalls in USA (NASFM) and National Institute of Standards and echnology (NIS). 3 Importance of study he aim of the project is to obtain new knowledge about fire development and fire spread in semi-trailer cargos and the heat exposure to the tunnel linings in the vicinity of the fire. here is a lack of systematic studies of the fire behaviour of semi-trailer cargos. Only two largescale fire tests using semi-trailer fire loads have been performed in a tunnel. hese tests were performed in 1992 in the EUREKA 499 test program performed in Repparfjord in Norway and sponsored by European partners. One test was performed with a semi-trailer loaded with 2000 kg of furniture and a wind speed of 6 m/s in the tunnel and one test was performed with densely packed wood cribs (2212 kg) supplemented with rubber tiers and plastic materials on the top (322 kg and 310 kg, respectively) and a wind speed of 0,5 m/s in the tunnel. he latter test was a simulated semitrailer load. In the furniture test, the fire was ignited in a tractor unit (Leyland DAF 310 A) and the fire spread from the tractor unit to the semi-trailer within 10 minutes. After the fire spread from the tractor unit to the semi-trailer cargo the fire developed very rapidly resulting in peak values of 120 130 MW within 3-4 minutes, whereas the wood crib tests showed a 1 he UPUN project has 41 partners. he proposed tunnel tests in the Runehamar tunnel are closely linked to this project.

relatively slow fire development. A peak value of 15 MW was obtained 15 minutes after ignition. hese two tests show the variation in the results depending on the fuel type, fuel configuration and the wind speed in the tunnel. In 1993-1995, the Massachusetts Highway Department and Federal Highway Administration in conjunction with Bechtel/Parsons Brinckerhoff performed a test program in the Memorial unnel in West Virgina, USA, using pool fires (liquid fuel in pans) varying between 20-100 MW. he focus of the test programme was primarily on the performance of different types of ventilation systems on smoke control in tunnels as well as foam sprinkler systems on pool fires. he objective was not to study the fire development of semi-trailer cargo or the risk for fire spread between these types of vehicles. Consequently, a scientifically performed study of semi-trailer cargo fires, including systematic variation in the fuel type, fuel configuration and ventilation conditions as well as the risk for fire spread between these vehicles would provide information of great importance for tunnel authorities, tunnel designers and fire services that is presently lacking. 4 est Programme he test programme is divided in Laboratory tests and Large-scale tests. he laboratory tests have been run in SP s fire hall and the large-scale tunnel tests will be carried out with semitrailer cargos in the Runehamar tunnel in Norway. he Runehamar tunnel lies about 5 km from Åndalsnes, 40 km south of Molde, in Norway. Molde lies on the Norwegian west coast, about 400 km from Oslo. he tunnel is a two-way-asphalted road tunnel that was taken out of use about ten years ago. It is 1650 m long, 6 m high and 9 m wide, with a slope varying between 1-3 %. he tunnel s unique location, together with its good condition, length and accessibility present one of the few places in the world where such experiments would be feasible. he tunnel is owned by the Norwegian Road Administration and we will work closely with them in performing these tests. he local Road Administration in Norway will deal with the environmental aspect of the tests. 4.1 Laboratory tests Several pre-tests consisting of free burning tests under a large hood system at SP s Fire laboratory have been performed. his was carried out in order to obtain accurate knowledge about the fire behaviour (MW) and heat content (MJ) of the different commodities used in the large scale test program. he commodities we plan to use consist of four different materials, each representing a specific category of material found in the cargo of semi-trailers. hese commodities are standardised wood pallets, plastic pallets made of polyethylene (PE), standardized test commodity consisting of polystyrene cups (PS) in paper cartons and polyurethane madrasses (PUR). hese materials do not cover all type of materials found in semi-trailers but they represent basically two catergories; - cellulosic materials (wood, paper) - synthetic polymers or plastics (PE, PS, PUR).

he burning characteristics such as smoke production, production of toxic gases and heat radiation vary greatly between these materials. Other type of common materials such as vegetables, foodstuff, and margarines are not covered by these two categories. Melted plastics can, however, result in similar fire behaviour as pool fires. he pre-burn tests were carried out under a large fire collector at SP s fire laboratory as shown in figure 1. his fire collector can measure the heat release rate (MW), smoke production (optical density, yields etc) and production of hazardous gases (CO, CO 2, HCN etc). We will also be able to measure the total heat content of the commodities used (MJ). he number of tests carried out were three: - standardised test commodity cartons with PS cups (80-85/20-15 %) - mixture of wood pallets and plastic pallets (80-85/20-15 %) - mixture of wood pallets and PUR (80-85/20-15 %) SP Fire Collector 10 MW 1200 1100 4000 2743 Figure 1 Free-burning pre-tests with standardised test commodity cartons with PS cups under a large hood at SP s fire laboratory.

In semi-trailer cargos we cannot expect to find only one category of materials, but a mixture of these materials. We also know that the configuration of the commodity may play a major role in the fire development. he semi-trailer load can consists of thousands of different variations or mixtures of materials. In order to reduce the number of parameters between each test, we will keep a constant mass ratio of cellulosic materials (80-85 %) and plastics (15-20%) throughout the test program. his ratio is expected to be a reasonably well-represented mass ratio of what can be found in semi-trailers throughout the world. Swedish statistics identify 24 different groups of commodity transported on Swedish roads. he combustible commodity can be distributed by their mass ratio into four different categories; cellulosic materials (42 % by mass), miscellaneous commodity inclusive packaging materials (28 %), food products (17%) and oil products (13 %). he two largest categories include cellulosic materials and miscellaneous commodity with packaging materials. he packaging material is usually either cartons or plastics. he statistics do not apportion the miscellaneous commodity with packaging material into cellulosic materials and plastics. Discussions with road carriers indicate that the mass ratio of 80 85 % cellulosic materials versus 15 20 % plastics is a reasonable distribution for these two categories. In order to investigate the effects of ventilation on the configuration of the commodity we plan to run some preparatory tests on paper cartons and wood pallets/cribs in order to conduct a scientific evaluation on the effect of ventilation on the large-scale behaviour of the commodity. his is an important parameter to investigate since we know from the literature that authors state that the increase in fire growth rate and peak heat release rates in tunnel fires may be as high as a factor of ten. herefore, it is importance to investigate these claims before we make a final decision about the configuration of the test commodity. 4.2 Large scale tunnel tests he heat release rate will be measured with aid of a mobile fan (Mobile Ventilation Unit MVU 125/140 from empest) positioned at one of the tunnel openings. his will provide a means of driving the fire gases in one direction and so enabling the heat release to be measured at the other end of the tunnel. Although the primary objective is to measure the heat release rate for various ventilation conditions, this will also provide important information on: - how smoke spreads in the tunnel, upstream and downstream of the fire, - the conditions under which firefighters with breathing apparatus may have to work, - smoke development from various types of loads, - gas temperatures and heat fluxes close to the fire place - the spread of fire between vehicles, - measuring heat release rates in the 50-200 MW range. We plan to run four tests with a constant longitudinal velocity of 2.5 m/s and different mixtures of materials in the semi-trailer cargo. In three tests we will use a mixture of cellulose and plastic materials with a mass ratio of approximately 80-85 % and 20-15 %,

respectively, and in one test we plan to use a real commodity consisting of furniture. Below we find a list of the proposed est Commodity: - est Commodity 1 600 corrugated paper cartons with interiors (600 mm x 400 mm x 500 mm ; L x W x H) and 15 % of total mass of unexpanded polystyrene cups and 40 wood pallets (total weight 2650 kg), - est Commodity 2 236 wood pallets and 240 PUR madrasses measuring 1000 x 1000 x 150 mm (total weight 6125 kg). - est Commodity 3-360 wood pallets measuring 1200 x 800 x 150 mm, 20 wood pallets measuring 1200 x 1000 x 150 mm and 75 PE plastic pallets measuring 1200 x 800 x 150 mm (total weight 9917 kg) - est Commodity 4 Furniture (total weight 8400 kg) Drawings showing the est Commodity (C) 1 3 are presented in figures A1 A3 in the Appendix A. In test 4 we will use furniture similar to that used in the EUREKA 499 test series. he reason for using furniture is that the test carried out in EUREKA 499 was carried out with a very high ventilation rate (6 m/s at the start of the test). herefore, it is of interest to run one such test for comparison with est Commodity 2, which has similar materials as in upholstered furniture s. he longitudinal velocity of 2.5 m/s is what is required in order to avoid long backlayering of smoke upstream the fireplace (test site). 2600mm protected Promatect boards 6000mm tarpulin 1220mm 3300mm 100 mm gravel - 100 m long protection of asphalt asphalt gravel 7300mm 9000mm Figure 3 he fire load of the semi-trailer will be located at the centre of one lane of the tunnel.

he fire will be located 560 m from west entrance and the smoke will be blown from east to west. his means that 560 m of the tunnel will be smoke filled. he test commodity will be placed on a simulated semi-trailer up stand (see figure 5) measuring 10700 mm by 2600 mm. he total height will be 4500 mm. We will not use any real trucks as we are focusing on the fire development of semi-trailer cargos and the additional heat release from the hauler unit is expected to be less that 5% of the total heat release. he height of the platform floor will be 1200 mm and the width 2600 mm. he simulated semi-trailer platform will be located at the centre of the left hand lane. he cross-section of the tunnel at the fireplace is shown in figure 3. he test commodity will be covered by polyethene tarpaulin in all tests. Ignition will take place at the upstream side of the test commodity. It will consist of pieces of fibre board soaked with heptane. At a distance of 15 m from the downstream side of the test commodity there will be a target consisting of the first row of the same test commodity as used in actual test, see figure 6. We will have video cameras in order to determine the time to ignition of the second vehicle. East entrance West entrance Side view Åndalsnes 2 km 1000 fire place 500 target 563m op view 1600m Figure 4 Location of the fire and target. he fire will be located 560 m from the west entrance and the fan will be at the east entrance.

Figure 5 he rack storage system used to create the platform for the fire load. 4.3 Measurements In this test program SP will measure the gas temperatures, visibility in the smoke, the heat radiation and the toxic gases in the fire gases. here will be other UPUN partners (NO in Holland and SINEF in Norway) making complementary measurements. In order to carry out the measurements, SP will use a data acquisition system based on radio links to provide wireless broadband communication between the instrument stations and the logging computer. he system has worked very well in other large-scale tunnel tests. he benefits are that we will avoid the need to run long cables in the tunnel. his also provides considerable flexibility in carrying out the work. here will be three main measuring stations: one located 100 m from the downstream tunnel entrances, one in the vicinity of the fire site, and one 100 m upstream of the fire. In the area between 100 400 m from the west (downstream) entrance there will be some measurements on temperatures. he measuring station at the downstream entrance is the one where most of the fire gases will be transported, see figure 6. he upstream measurement station will only be useful when we run a test without any longitudinal ventilation. he results from the entrance stations will be used to calculate the heat release rate with the assistance of the consumption calorimetry technique. he transportation time of the fire gases from the fire site to the measuring location will be corrected afterwards. here are not only practical reasons to locate these measuring station far away from the fire. We should also expect a quite uniform flow on the downstream side and the temperature is

expected to be low. he drawback is the transportation time but this can be corrected afterwards with the help of CFD calculations and simple mass transport equations. -100-70 0 m +20 +100-25 +70 +40-40 -15 +10 +150 +200 +250 Sheated 0.25 mm thermocouple 0.3 m under ceiling and platethermometer at the ceiling Sheated 0.25 mm thermocouple 0.3 m under ceiling +350 See 300 m instr 0.25 mm thermocouple 0.3 m under ceiling and measurement station 2 (see separate figure) +463 0.25 mm thermocouple 0.3 m under ceiling 0.25 mm thermocouple 0.3 m under ceiling and 1.8 m above the floor Sheated 0.25 mm thermocouple 0.3 m under ceiling, platethermometer at the ceiling, and plate thermometeer 1.6 m above the road Figure 6 600 500 400 he layout of the instrumentation along the tunnel. 300 200 100 0 m he measuring station in the vicinity of the fire is more complicated due to the enormous heat. At this site we will only measure gas temperatures and heat fluxes. In figure 8, a proposal for measurements at the fire site is shown. Between 100 m upstream and 463 m downstream of the fire the gas temperature near the ceiling will be measured. At some positions the temperature at a lower level will also be measured (see Figure 6). At 463 m (100 m from the entrance) SP will have the instrumentation as shown in figure 7. he thermocouples will be type K with 0.25 mm diameter. At some locations near the fire we will measure the temperatures with the Plate hermometer. he velocity will be measured with aid of bi-directional probes. he gas analysis will be on dry basis and the optical density will be measured with aid of a laser system. he radiation gage will be of Schmidt-Boelter type.

6000mm H 0.12H 0.19H 0.19H 0.19H 0.19H 0.12H, u,o2,co2,co, u, u,o2,co2,co, OD, u, u,o2 7300mm 9000mm Figure 7 he measurement station 100 m from the downstream entrance. =gastemperature, u=gasvelocity, O2=oxygen, CO2=carbon dioxide, CO=carbon monoxide, OD=visibility, H=tunnel height at measuring location. 5700mm 10000mm 10000mm 10000mm, P, P, P arget R R 10000mm 15000mm Figure 8 he detailed instrumentation in the vicinity of the fireplace. =gas temperature, P=Plate hermometer, R=heat flux gage he measurement station 100 m upstream of the fire will be very similar to the one shown in Figure 7, but with fewer velocity measurement and gas analyses.

4.4 est programme he preliminary test program is as follows: est nr est Commodity Estimated heat content (GJ) 1 C 2 wood pallets + PUR 2 C 3 wood pallets + Longitudinal ventilation (m/s) Mass ratio cellulosic/plastic 113 2.5 82/18 207 2.5 82/18 PE pallets 3 C 4 IKEA furniture s - 2.5 82/18 4 C 1 carton+ps 52 2.5 81/19 5 C 1 52 1.5 81/19 6 C 1 52 0 81/19 5 ime table he laboratory tests have been carried out and the preparation of the tunnel will be carried out in August 2003. he tests will be run in September 2003 according to the present test plan. he project is expected to be finalised at end of 2004. he major financial support comes from the Swedish Rescue Service Agency (SRV), the Swedish Road Administration, the Swedish Rail Administration, the Swedish Research Board (BRANDFORSK) and from the European Commission through the UPUN project. Industrial sponsors are Promat International N.V. in Belgium, Gerco Beveiligingen B.V. in the Netherlands and B I G Brandschutz Innovationen (EMPES) in Germany.

Appendix A - Large scale test commodity Figure A1 - est Commodity 1 consists of 600 corrugated paper cartons (600 mm x 400 mm x 500 mm) with interiors and 15 % of total mass of unexpanded polystyrene cups and 40 wood pallets. Figure A2 - est Commodity 2 consists of 200 wood pallets and 200 PUR madrasses measuring 1200 x 1000 x 150 mm.

Figure A3 - est Commodity 3 consists of 320 wood pallets measuring 1200 x 1000 x 145 mm and 80 PE plastic pallets measuring 1200 x 800 x 150 mm.