Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Similar documents
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Recent Advances in Energy, Environment and Economic Development

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

K.F. Fong *, C.K. Lee, T.T. Chow

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

Department of Mechanical Engineering, Mirpur University of Science and Technology, Mirpur, AJK, Pakistan

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

System Modeling of Gas Engine Driven Heat Pump

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Journal of Thermal Science and Technology

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Dynamic performance of a novel dew point air conditioning for the UK buildings

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

Enhancing the performance of the domestic refrigerator with hot gas injection to suction line

Design of solar adsorption refrigeration system with CPC and study on the heat and mass transfer performance

To investigate the surface properties for increasing efficiency of solar water heater

Experimental study of an energy efficient hybrid system for surface drying

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Effect on air quality and flow rate of fresh water production in humidification and dehumidification system

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Study on a novel variable capacity technology and control strategy for refrigerated shipping container unit

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

ANALYSIS OF DESICCANT COOLING SYSTEM

Mathematical Simulation of Longan Fruit Drying

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Modelling the Performance of a Diffusion Absorption Refrigeration System

Evaluation of moisture content in drying of grated coconut meat using grain moisture meter

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector

Characterization of Desiccant Wheels with Alternative Materials at Low. Regeneration Temperatures

Solar Heating and Cooling Systems

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

A new method for preventing air-source heat pumps and refrigerators from frosting

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

Waste Heat Recovery Analysis of CO 2 Refrigeration Systems

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

A study of Transient Performance of A Cascade Heat Pump System

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

SOLAR COOLING TECHNOLOGIES

Adsorption Chillers Energysmart Green Cooling

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Adsorption refrigeration system using waste heat

Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine

Efficient adsorption refrigerators integrated with heat pipes

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

ISSN: [Ghatol* et al., 6(12): December, 2017] Impact Factor: 4.116

Energy Recovery Ventilation

Desiccant Cooling Analysis Simulation software, energy, cost and environmental analysis of desiccant cooling system

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Performance of CO2 Cycles with a Two-Stage Compressor

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Performance investigation of Air-conditioning system using ejector as expansion device

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Trane CDQ Desiccant Dehumidification

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Transcription:

IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP Conf. Ser.: Earth Environ. Sci. 121 052037 View the article online for updates and enhancements. This content was downloaded from IP address 148.251.232.83 on 22/12/2018 at 09:44

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump Yefeng Liu 1, Deren Meng and Shen Chen School of Energy and Power Engineering, University of Shanghai for Science&Technology, Shanghai, 200093,China 1 yfliu209@163.com Abstract. In traditional desiccant wheel, air regeneration process occurs inside an open loop, and lots of energy is consumed. In this paper, an energy-saving desiccant wheel system with CO 2 heat pump and closed loop air regeneration is proposed. The general theory and features of the desiccant wheel are analysed. The main feature of the proposed system is that the air regeneration process occurs inside a closed loop, and a CO 2 heat pump is utilized inside this loop for the air regeneration process as well as supplying cooling for the process air. The simulation results show that the proposed system can save significant energy. NOMENCLATURE Subscript h enthalpy (kj kg -1 ) in inlet of a desiccant wheel on process air side T temperature ( ) out outlet of a desiccant wheel on process air side T db dry-bulb temperature ( ) reg regeneration air T dp dew point temperature ( ) T e evaporating temperature ( ) T wb wet-bulb temperature ( ) UR relative humidity (%) X humidity ratio (g kg -1 ) 1. Introduction Desiccant wheels are also known as dehumidification wheels, wheel dehumidifiers or rotary dehumidifiers in different literatures. With the requirements of energy saving and emission reduction in the world, desiccant wheels have been expanded greatly from special areas such as electronics, food, storage and pharmaceutical industries, to supermarkets, restaurants, schools, hospitals, and office buildings[1]. Most research works focus on the performance analysis of desiccant systems. Many works analyze the performance of hybrid vapor compression-desiccant wheel systems and show that this technology can save significant energy compared to the traditional systems where the vapor compression system is used for dehumidification [2-13]. The biggest advantage of hybrid vapor compression-desiccant wheels system lies in the elimination of overcooling and reheating. In the above mentioned research studies, it is reported that the air regeneration process of the desiccant wheel occurs inside an open cycle, which needs lots of energy for regeneration. Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

In this paper, a new desiccant wheel system with closed-loop air regeneration is introduced and analyzed. In a transcritical CO 2 cycle heat pump, the cooling process in the supercritical region is a gas cooling process, which is particularly suitable for the regenerative heating of air. The regeneration air can be heated to the desired temperatures, and no auxiliary heater is needed. Therefore, a CO 2 transcritical cycle heat pump is utilized in the proposed system. In addition, the air regeneration process occurs inside a closed loop. The CO 2 transcritical cycle heat pump is utilized to not only regenerate the recycled air, but also to cool the supply air. The aim of this work is to study the performance of the proposed system, as well as explore the energy saving potential. 2. Methodologies In order to provide universality for the air dehumidification process, only fresh air processing is considered in the simulation, and the fresh air is from the ambient. Figure 1 illustrates the schematic of a traditional desiccant wheel-cooling system. In the further analysis, this system is named System 1. As shown in Figure 1, the desiccant wheel is divided into two sections for the process air and the regeneration air. Water vapor is adsorbed by the desiccant when the moist air stream passes through the process air side. The wheel rotates then exposes the moisture-laden desiccant to the regeneration air stream, which is heated up by an electric heater before entering the desiccant wheel. Water is desorbed from the desiccant and the desiccant material is regenerated. The hot and humid regeneration air leaving the desiccant wheel is then discharged to the ambient. Significant heat energy is required for the regeneration process. After the process air leaves the desiccant wheel at Point B, it is cooled in Evaporator I of a vapor compression cycle, obtaining supply air with the required temperature and humidity ratio at Point C[2]. Figure 1. Schematic of conventional desiccant wheel-cooling system (baseline system / System 1). Figure 2 illustrates an advanced high temperature heat pump coupled to desiccant wheel-cooling system. In the further analysis, this system is named System 2. Compared to System 1, the difference is only on the regeneration air side: the airstream from the ambient is first pre-heated through the heat rejected from the condenser before being further heated to the desired temperature by an electric heater[2]. 2

Figure 2. Schematic of advanced high temperature heat pump coupled to desiccant wheel-cooling system (System 2). Figure 3. Schematic of proposed desiccant wheel system with closed loop air regeneration (System 3). 3

Figure 4. CO 2 heat pump cycle for System 3: (a) cycle in a pressure-enthalpy diagram (b) cycle in a temperature-entropy diagram. A schematic of the proposed system, the new desiccant wheel system with closed loop air regeneration, is illustrated schematically in Figure 3. In the further analysis, this system is named System 3. The air regeneration process occurs inside a closed loop. A transcritical CO 2 heat pump is utilized for the recycled air regeneration including dehumidification, cooling and heating process. In addition, the CO 2 heat pump supplies cooling for the supply air. In the CO2 heat pump, there are two evaporators: Evaporator I is utilized to cool the supply air, and Evaporator II is utilized for cooling and dehumidification of the recycled air in the closed loop. The pressure-enthalpy diagram and temperature-entropy diagram of the CO 2 heat pump cycle are shown in Figure 4. 3. Mathematical model of desiccant wheels According to Beccali et al.[9-10], the outlet humidity ratio (X out ) and temperature (T out ) of the process air in a desiccant wheel can be calculated by the following expressions: X out = e0.053t out (0.9428 UR reg + 0.0572 UR in ) - 1.7976 / 18.671 (1) (UR out e 0.053 T out - 1.7976) / 1867.0 = (h out - 1.006 T out ) / (2501-1.805 T out ) (2) UR out = (0.9428 UR reg + 0.0572 UR in ) (3) A desiccant wheel type-i (Silica Gel) is selected for the three systems. The air enthalpy leaving the desiccant wheel, hout, is calculated by the following expression: h out = (0.1312 h reg + 0.8688 h in ) (4) The enthalpy (h reg ) is a function of humidity ratio X reg and the regeneration temperature T reg. It can be expressed by the following well-established equation: Where C p is the specific heat of the moisture. h reg = 1.01 T reg + (2500 + C p T reg ) X reg / 1000 (5) For the calculation of relative humidity URreg, the following empirical relation has been developed: UR reg = (18.6715 X reg + 1.7976) e (-0.053Treg) (6) The desiccant wheel runs with identical volume air-flows on the air process side and the regeneration air side. The ranges of available field data for the given model are as follows: X reg = 10-16 g kg-1,t reg = 40-80,T in = 20-34,X in = 8-15 g kg-1. 4

The established model consists of ten variables and six equations. Therefore, the values of four variables have to be given. Usually, the parameters h in, UR in, and X out are known based on the given operating conditions. In addition, the value of X reg can be calculated when the evaporating temperature of the CO 2 heat pump (i.e.,t e ) and the heat transfer temperature difference are given. In addition, the performance of CO 2 heat pump (System 3) is: COP=(h 2 -h 5 )/(h 2 -h 1 ) 4. Performance simulation and results The performance and energy savings analysis are based on the supply air conditions: the dew point of the supply air is between 5 and 0, and the dry-bulb temperature is 20. In addition, the fresh air conditions from the ambient are based on ARI standard rating conditions and typical ambient conditions. The operating conditions of four typical case studies are listed in Table 1. The dew point of the supply air in Case 1 is the same as the one in Case 2 with different fresh air conditions. The mass flow rate of process air and regeneration air streams are both assumed as 1kg s -1. The variations of the regeneration temperature, Treg, of System 3 as a function of the evaporating temperature, Te, for the four cases are shown in Figure 5. It can be seen that T reg increases with an increase of T e for all cases. No. Point A: Fresh air Case 1 Table 1. Operating conditions in four typical case studies. Point B: Dew point of air after the desiccant wheel on process air side ARI standard rating condition: T db = 26.7, X in =11.23 g kg -1 T dp = 5 (i.e., X out = 5.46 g kg -1 ) Case 2 T dp = 5 Case 3 Typical outdoor air condition: T db = 20, X in = 8.8 g kg -1 (i.e., X out = 5.46 g kg -1 ) T dp = 3 (i.e., X out = 4.7 g kg -1 ) Case 4 T dp = 0 (i.e., X out = 3.8 g kg -1 ) Point C:Supply air T dp = 5 T db = 20 T dp = 5 T db = 20 T dp = 3 T db = 20 T dp = 0 T db = 20 Figure 5. Variations of required regeneration temperature Treg with evaporating temperature Te in System 3 in the four cases. 5

The variations of the COP and the discharge pressure, P, of the CO 2 heat pump of System 3 as a function of the evaporating temperature, T e, for all Cases are shown in Figure 6. It can be found that the COP increases and then decreases with an increase of the evaporating temperature, T e, in every case. Thus, there is an optimal COP when T e varies from 1 to 15. Figure 6. Variations of COP of the CO 2 heat pump with evaporating temperature Te in System 3. An energy saving comparison for Case 1 is listed in Table 2. According to the total cooling load and COP, the compressor power is calculated. Electric heater supplies supplementary heat in System 2. The energy saving rates of System 3 for all cases are listed in Table 3. It can be found that System 3 can save significant energy. Table 2. Energy savings analysis for Case 1. Items System 1 System 2 System 3 Point A: Fresh air from ambient T in = 26.7, T wb,in = 19.4 Point B: Air at the outlet of desiccant wheel on air T out = 47.8, X out = 5.46 g kg -1 T out =46.3, X out =5.46 g kg -1 process side Point D: Regeneration air T reg = 68.4, X reg = 11.23 g kg -1 T reg = 63.5, X reg = 9.57 g kg-1 Cooling load of evaporator I, (kw) 28.3 26.8 Cooling load of evaporator II, (kw) 33.0 Heating load for regeneration, (kw ) 43.0 50.7 COP 5.2 4.1 6.3 Power of compressor,(kw) 5.4 6.9 9.5 Heating capacity from condenser/gas 35.2 50.7 coolers, (kw) Power of the electric heater, (kw) 43.0 7.8 Total energy consumption, (kw) 48.4 14.7 9.5 Energy-saving rate compared to System 1 70% 80% Energy-saving rate compared to System 2-230% 35% Table 3. Energy-saving rates of System 3 in all cases. Items Case 1 Case 2 Case 3 Case 4 Compared to System 1, energy-saving rate 80% 84% 84% 84% Compared to System 2, energy-saving rate 35% 70% 66% 68% 6

5. Results and discussion In order to reduce the energy consumption and greenhouse gas emissions of desiccant wheel systems, an energy-saving desiccant wheel system with closed loop air regeneration is proposed and analyzed. A transcritical CO 2 heat pump is recommended as a high temperature heat pump in the proposed system. The mathematical model of the system is developed, and the operating performance of the systems are simulated and analyzed. The results show that the proposed system can save 35%-84% energy than conventional systems and advanced high temperature heat pump systems. Accurate control system is the key point for this kind of system. Acknowledgement This work is sponsored by Shanghai Pujiang Program (Project NO. 17PJ1407200). References [1] La D, Dai Y J, Li Y, Wang R Z and Ge T S 2010 Technical development of rotary desiccant dehumidification and air conditioning: A review Renewable and Sustainable Energy Reviews 14 130-147 [2] Jia C X, Dai Y J, Wu J Y and Wang R Z 2006 Analysis on a hybrid desiccant air-conditioning system Applied Thermal Engineering 26 2393-2400 [3] Li Y, Sumathy K, Dai Y J, Zhong J H and Wang R Z 2006 Experimental study on a hybrid desiccant dehumidification and air conditioning system Journal of Solar Energy Engineering 128 77 82 [4] Yong Li, Sumathyk K, Dai Y J and Wang R Z 2006 Experimental study on a hybrid desiccant dehumidification and air conditioning system Journal of Solar Energy Engineering 128 77-82 [5] Zhang L Z 2006 Energy performance of independent air dehumidification systems with energy recovery measures Energy 31 1228-1242 [6] Bourdoukan P, Wurtz E and Joubert P 2010 Comparison between the conventional and recirculation modes in desiccant cooling cycles and deriving critical efficiencies components Energy 35 1057-1067 [7] Panaras G, Mathioulakis E and Belessiotis V 2011 Solid desiccant air conditioning systems design parameters Energy 36 2399-2406 [8] Liu W, Lian Z, Radermacher R and Yao Y 2007 Energy consumption analysis on a dedicated outdoor air system with rotary desiccant wheel Energy 32 1749-1760 [9] Beccali M, Adhikari R S, Butera F and Franzitta V 2004 Update on desiccant wheel model International Journal of Energy Research 28 1043-1049 [10] Beccali M, Butera F, Guanella R and Adhikari R S 2003 Simplified models for the performance evaluation of desiccant wheel dehumidification International Journal of Energy Research 27 17-29 [11] Mandegari, M A, S Farzad and H Pahlavanzadeh 2015 Exergy performance analysis and opt Jani, DB, M Mishra, and PK Sahoo 2016 Solid desiccant air conditioning A state of the art review Renewable and Sustainable Energy Reviews 60 1451 1469 [12] Jani D B, M Mishra and P K Sahoo 2015 Performance studies of hybrid solid desiccant - vapor compression air-conditioning system for hot and humid climates Energy and Buildings 102 284-292 [13] Alili A A, Y Hwang and R Radermacher 2015 Performance of a desiccant wheel cycle utilizing new zeolite material: experimental investigation Energy 81 137-145 7