Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Similar documents
FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Excel-EN Conventional Fire Control Panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation, Operating and Maintenance Manual

Menvier Fire System MF9300

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

5000 INSTALLATION GUIDE

OPERATION AND INSTALLATION MANUAL

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Intelligent Security & Fire Ltd

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

Surveyor Envoy-MINI 4

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Precept Marine Control Panel Application Guide

Application, Installation, Operation & Maintenance Manual

Installation Guide for models:

Control Panel Engineering and Commissioning Instructions

Installation and user manual for the BiWire / Conventional Repeater Panel

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

GAS SUPRESSION CONTROL PANEL:

Loadstar AC/DC Systems

Installation Guide for models:

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

EXTINGUISHING AGENT RELEASE MODULE

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

Series. Access Power Controllers. Installation Guide

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

FEC400 Series. Installation Manual

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Intelligent Security & Fire Ltd

TECHNICAL DATA OBSOLETE

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

Unity DAU Voice Alarm System

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

Installation, Commissioning & Operating Manual

FireNET Plus Wiring Instructions

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

System 800 Addressable Fire Detection & Alarm System

Operation and Maintenance Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

ELECTRIC FIRE PUMP CONTROLLER

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Installation & Commissioning Manual

New Silent Alert Fire Safe System

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Commercial and Light Industrial Fire Alarm Control Panel

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

Dale Power Solutions Ltd

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

Installation and Operating Instructions

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

Functional Performance Test

ORION Mini-Rep INSTALLATION MANUAL

ISIS SAFETY SYSTEM Installation guide

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Temporary wireless battery operated fire system from Channel Safety Systems

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Premier Hazard STC Instructions

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

SOUNDER CONTROL MODULE SCM-AS4

Door Release Power Supply

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Conventional Fire Detection

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

Specification/ Data Sheet

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

DYCU-3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL

Transcription:

BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual

BCU RANGE OF 24V DC BATTERY CHARGERS MODELS: BCU24-50-4 BCU24-100-4 BCU24-200-3 Stand alone 24V battery chargers of 5, 10 and 20 amp capacities. Maximum battery size for enclosure: BCU24-50-4 24Ah BCU24-100-4 38Ah BCU24-200-3 38Ah (72Ah with additional enclosure) The constant voltage charging rate is set at 27.6 ± 0.2V DC All battery chargers are rated for fire alarm use. Should they be used for standing loads, then the output should be de-rated by 20% e.g. a 5 amp charger should not supply a standing load of more than 4 amps. When used in a fire alarm system, then to comply with the requirements of British Standard EN54 Pt.2 1998, the charger should be for the exclusive use of the fire alarm. Smoke Dispersal An auxiliary double pole relay is supplied as standard to supply the standby loads required in smoke dispersal systems (i.e. roof vents and Naco louvre window vents etc.). The majority of smoke dispersal ventilators are designed with electromagnets to hold them in the closed position. When de-energized the electromagnets allow the vents to open. To prevent overheating any standing load placed on the charger should only be 80% of the rated capacity i.e. a 5 amp charger should only supply a 4 amp constantly rated load. These smoke dispersal chargers can be controlled either from an auxiliary relay on a fire alarm panel or from a simple switch i.e. a non-resistive, break glass call point (preferably not a red one). Refer to Drawing No. 1747M for different connection scenarios. Thought should be given to providing a fail-safe signal method, preferably via a continuous 24V signal or by normally closed contact. 2

Specification Voltage: 24V DC nominal (27.8V maximum) Charging Rate: 27.6 ± 0.2V Supply Voltage: 100 264 V AC rms 47 63Hz 5, 10 & 20A Units Colour: Lid and cabinet Radon MW334E Interpon Size: 500mmH x 450mmW x 200mmD 5, 10 & 20 Amp Cabinet:: Constructed from 18 SWG mild steel folded and welded. Five mounting holes in rear face. Knockouts at the top 20mm diameter. Ventilation louvres in side walls.. Max Cont Max Fuse Fuses Fuse Load Battery Mains 24V O/P Battery BCU24-50-4 4A 24Ah 5A 5A 5A BCU24-100-4 8A 38Ah 10A 10A 10A BCU24-200-3 16A 38Ah 20A 20A 20A NB. 72Ah batteries can be used with the BCU24-200-3, but requires an additional BC200 battery cabinet. Indications and Controls External Indications: Supply Healthy - Green LED Common Fault - Yellow LED Charger Fault - Yellow LED Battery Fault - Yellow LED Silenced - Fault buzzer, Yellow silenced LED Silence Button - Mutes fault buzzer. Electronic, with auto reset Internal Indications: Battery Fault - Yellow LED Mains Fault - Yellow LED Earth Fault - Yellow LED Volts Fault - Yellow LED Battery Start - Connects battery when Mains Supply is not present 3

Installation Instructions 1) Precautions: It is the responsibility of the installer to ensure suitability of this equipment for the purpose intended, to install it in compliance with EN54 Pt. 2 & 4 1988 or local authority requirements and to ensure it is correctly commissioned and maintained by a qualified person. WARNING: Always take full anti-static precautions when handling this electronic equipment. Any equipment returned to the manufacturer must be suitably protected in anti-static packing materials. ONLY apply the stated supply voltage to the input terminals marked N.E.L. supply any high voltage directly to any printed circuit boards (PCB) contained in the panel. apply greater than 50V DC to any auxiliary relay mounted on the PCB. use unsuppressed or unpolarised bells or coils. subject panel to liquids. use a megger or similar test equipment to check cables while they are connected to the Fire Detection System or any other electronic equipment. ENSURE swarf, brick dust, wire clippings etc. are not allowed to contaminate the PCB, as this can cause severe damage to the circuits. ALWAYS isolate the mains supply before connecting or disconnecting the mains supply lead. 2) Mount the cabinet securely to a wall using the four fixing holes provided. A centre key hole is provided as an additional aid. To assist installation of the cabinet, the door and (on 5, 10 & 20 Amp) the charger chassis can be removed to a safe place for storage. Ensure that any swarf or brick dust is not allowed to contaminate any of the electronic components or PCBs. 3) Knockouts are provided in the top face, but the cabinet can be drilled, with care, to accept additional cable entries. 4) Ensure all cables are routed neatly and to avoid contact with any PCBs or components. All cables should be fastened securely into the terminals provided. 5) Check all connections and wiring to ensure that the load figures quoted earlier are not exceeded or that short circuits are not inadvertently placed across the terminals. 6) Connect 2 off 12V batteries in series to give 24V and connect as shown in drawing no. 1745M. 7) Switch on mains supply and all warning LEDs will extinguish and the Supply Healthy LED should illuminate. 4

8) Test charger by: a) Disconnecting main supply. Charger Fault and Common Fault LEDs will show and the buzzer sounds. Mute buzzer by pressing Silence button. Silenced LED will show. Reconnect mains, all Yellow LEDs extinguish and the Supply Healthy will show. N.B. The Battery Charger circuit will disconnect the batteries at 19V to protect them from full discharge after the main supply has failed. When the mains are restored the relay pulls up and the batteries are reconnected, or if battery start switch is pressed if Mains supply is not present. Maintenance Apart from periodic checking of the functions as in 8 above and the charging voltage, no regular maintenance is required. We would recommend that a discharge test be carried out on the Sealed Lead Acid batteries in accordance with the manufacturers instructions. Checking the Charging Voltage Disconnect batteries and measure across charger output terminals marked Battery. Check voltage to 27.6 ± 0.2V DC. An accurate voltmeter must be used. Adjustment can be made with a potentiometer on the power supply module, refer to drawing no. 1745M or 1769M for 1.5 Amp and 3 Amp units. Earth Fault Monitoring Both positive and negative rails of the 28V supply are monitored for earth faults. If an earth fault is present, this will be indicated internally and signalled to compatible monitoring equipment i.e. Surveyor Excel Control Panel. If earth fault monitoring is not required, cut out the earth fault link L1 on the bottom left of the circuit board. 5

Connection Details All sizes of power supply unit are provided with the following terminals:- Battery + - :- 28 volt output for battery charging use only. Use suitable leads as supplied. 28v Outputs + - :- 28 volt supply outputs to power load. Separately fused at full output current. Note:- Fuses of lower value may be fitted to provide extra protection to external equipment. Aux Relay Contacts C, NC, NO :- Relay contacts for switching auxiliary loads. Note:- 20 Amp unit does not have (NC) contacts provided. An external contactor or relay will be necessary if this is required. 28v Coil + - :- Coil connections for control of Aux Relay. Polarised and suppressed may be activated by bell circuits or 24v DC from control panels. Common Fault C, NC, NO :- Volt free fault contacts for remote signalling use. CF - :- Switched negative charger fault output compatible with 2000 Series and previous panels. BF - :- Switched negative battery fault output. PSD :- Data output to Excel panels. PSC :- Clock output to Excel panels. 12v + :- Ancillary 12 volt 500 ma supply output for use on Excel panels etc. N.E.L. :- Mains supply input 230V AC 50Hz. Note:- This unit must be earthed according to I.E.E. Requirements. CAUTION :- Never connect mains supply to any other terminal other than the fused 3 way mains terminal block provided. 6

BCU24-50-4, BCU24-100-4 & BCU24-200-3, General Layout Drawing 7

BCU24-50-4, BCU24-100-4, BCU24-200-3, Connection Options Diagram 8