Control System THETA. Operating Instructions. Room control unit RSC and RSC-OT

Similar documents
BrainQ RSC/2 USER MANUAL. BrainQ RSC/2 Thermostat 8G /10.05

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Operating instructions

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1

User Instructions For TopTronic RS-30

Condensing Boiler RS100 Controller Training Program

Heating Controller SDC Remote Heating Controller DHC

Operating constructions

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

BM Programming Module. For the heating engineer Installation instructions

Operation manual FR EN NL DE IT. intended for professionals and end users. To be saved for future consultation

Operating instructions

Modulating clock thermostat

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

USERS GUIDE. Electronic Timer, 7 day. LOGIC+ Combi, LOGIC Combi & LOGIC Combi E 24, 30, 35

Operating instruction. Remote control station WCM-FS /

RF ELECTRONIC PROGRAMMABLE ROOM THERMOSTAT, 7 DAY

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

Operating instructions. For the operator. Operating instructions VRT 350. Room temperature-controlled controller GB, IE

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

G a

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Operating Instructions

danfoss Heating Solutions 5

Vokèra OpenTherm 711 without external sensor connected

Vokèra OpenTherm 711 with external sensor connected

- Data Brochure tekmarnet 4 Thermostat 542e

Installation & User s Instructions

Installation and Operating Manual. Merlin 5064 V3. System Manager

RVL47. Heating Controller. Installations Instructions. Installation

R. Room temperature controller with solar control FR 120. Operating instructions for the user (2012/02)

Type UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button

RF Programmable Room Thermostat User Instructions

RVL481. Heating Controller. including d.h.w. heating

QAW70. Room Unit. Building Technologies. for use with heating controllers

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Heating Controller SDC Remote Heating Controller DHC

Basic Plus2 Room Thermostats Floor Heating

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

4 Wiring Brochure Wiring and

User Guide for EHE & EHE Programmable Room Thermostat

GreenCon On/Off Room Thermostat

GreenCon On/Off Room Thermostat

For the operator/for the heating engineer. Operating and Installation Manual VRC 430. Weather compensator VRC 430

Installation and servicing instructions

Heating and D.h.w. Controller RVL482 Basic Documentation

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Heating Controller SDC District Heating Controller DHC 43 SERVICE MANUAL

Control solutions Biofloor

3 Channel Multi-Purpose Programmer User Instructions

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVP310. Heating Controller. Building Technologies HVAC Products

Smile SDC heating and district heating controller

multimatic Operating instructions AT, BE (de), CH (de), DE VRC 700f/4

ES-LCD User Control SD Card Location

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Heating Controller SDC Remote Heating Controller DHC

Roth Touchline. German quality since Quick and easy user manual 1/10

Cooling kit UTW-KCL*D. Installation instructions FR NL EN DE IT. (Compatible with high-flow circulation pump, code UTW-PHF*D)

On initial power up the thermostat will guide you through set up procedure for the following:

REA22 Room Temperature Controller

multimatic Operating instructions Operating instructions For the operator AT, BE (de), CH (de), DE VRC 700f/4 Publisher/manufacturer Vaillant GmbH

Roth Touchline. German quality since User manual quick and easy guide 1/10

Operating Instructions

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

Operating Instructions

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

For the owner and the heating engineer. Operating and Installation Manual. timeswitch 140. Two-channel 5/2 or 7-day full programmer

Boiler controller S-Tronic Plus

ECL Comfort 210 / 296 / 310

Operating your heating system with the Prefect PRE5701 Programable Thermostat

Operation manual. Daikin Altherma Low temperature split EHBH04CBV EHBH08CBV EHBH11CBV EHBH16CBV

Operating and Installation Manual VRC 430f. Weather compensator controller with radio transmission. For the operator / for the heating engineer

Operating instructions

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

MAKING MODERN LIVING POSSIBLE. TP7001 Range Electronic 7 Day Programmable Room Thermostat. User Guide. Danfoss Heating

ProCon Boiler Controller Commissioning Quick Reference Guide

Climapro 2. User manual. wireless room thermostat without receiver. To be left with the user.

MAKING MODERN LIVING POSSIBLE. CP715Si. Electronic 2-Channel Common Timebase Programmer for Heating and Hot Water. User Guide.

Service Instructions for use by heating contractor

RVL480. Heating Controller

Boiler controller Lambdatronic S 3200

Planet Super4F.S. User Instructions

Quickheat 30 weather compensated boiler control

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

COMF RT SYSTEM. T-32-TS Touchscreen Thermostat. User Manual

Transcription:

Control System THETA Operating Instructions Room control unit RSC and RSC-OT

Table of contents Page 2 USER LEVEL Operating instruments........................................................................................4 Operation start-up - language selection - device identification - standard display...........................................5-6 Temperature settings required daytime temperature, required reduced temperature, required hot water temperature................7 Operational mode selection for heating and hot water (summary)..............................................8 Function of operational modes holiday, absence, party, automatic, summer, permanent heating, permanent reduced heating, standby.....9 Quick operational mode selection (automatic, party, absence, hot-water reloading).......................................10 Heating characteristics (heating curve)...........................................................................11 Plant information........................................................................................ 12-133

PROGRAMMING LEVEL LEVEL SUMMARY schematic block diagram............................................................14-15 Level TIME PROGRAMS Programming, copying, reloading of standard programs, table for individual programs............16-22 Level TIME-DATE Time, calender year, calender month, calender day, automatic summer-/wintertime reset.............23 Level SYSTEM Language selection, clearing of time programs, control mode, summer switching-off...............22-26 Level DOMESTIC HOT WATER Economic temperature, legionella protection................................................27 Level UNMIXED CIRCUIT Reduced mode, heating system.......................................................28-29 Error messages......................................................................................................30 Notes...............................................................................................................31 Technical specification.................................................................................................32 Page 3

General operation Operating instruments Page 4 LCD-display Heating and set back programs Setting heating characteristic Displaying heating plant information Setting daytime temperature Setting reduced temperature Setting domestic hot water temperature Rotary-push button

Operation Symbolism used in this manual: Turn: select parameters, change values Press once: confirm, store The center-positioned rotary-push button and the labeled keys guarantee a simple and easy operation. It is however recommended to read this manual attentively to be informed about the repeating steps. Each value in the display appears flashing and can be modified with the rotary-push button. A flashing display is appropriately marked in this manual. Turn to the right (+): Increase values Turn to the left (-): Decrease values Press once: Acceptance of the selected and indicated value, store. Keep pressed: Entry into the programming level (level selection), The last operation step will be stored automatically after approx. 60 seconds if it was not stored by means of the rotary-push button. 20 0 2 4 6 10 12 18 22 8 14 16 24 f f f f f f f f f f f f ¾ À Á Ä KWh KWh min min f f f f f% % ff:f f Display test Start-up In case of initiation of the plant or after every power failure a display test of the large display is carried out with automatic error diagnosis. At that all available segments and symbols will be displayed. SPjACHWAHL D Language selection Country code Language selection In case of first initiation the desired language can be chosen after the display test. The languages D (German), GB (English), F (French) and I (Italian) can be selected. Note: This display appears after every restart on day of first initiation until midnight. After that the language can only be changed in the level SYSTEM - parameter LANGUAGE. Page 5

OT RSC V2 1 Device identification Interface and software version Device identification Page 6 After the display test and/or the language selection the device identification momentary appears with device type, interface and the corresponding number of software version. 0 2 4 6 10 12 18 20 22 MO 22 AUG ;05 ë 16:32 8 14 16 24 62 5 Heating cycles Standard display Actual boiler temperature resp. room temperature Basic display Provided that there is not any error message, the basic display indicates the date, time, heating mode (ë = daytime temperature, ì = reduced set back temperature ) as well as the current boiler temperature or, if released, the room temperature. Response time program. The cursor below ( - ) indicates the current operating mode (see function of operating modes). The upper time bar shows the heating periods and the corresponding operating times of the current weekday. 0 2 4 6 10 12 18 20 22 MO 22 AUG ;05 À 16:32 8 14 16 24 22 5 Standard display Summer switching-off activated An activated summer switch-off is represented in the basic display by a sunshade symbol ( À ). The heating mode symbols ë or ì will be suppressed during an activated summer switch-off. 0 2 4 6 10 12 18 20 22 MO 22 AUG ;05 Á 16:32 8 14 16 24 22 5 Standard display Frost protection activated With acting frost protection function an ice crystal symbol appears in the basic display ( Á ).

Temperature settings Required daytime room temperature Required set back room temperature Domestic hot water temperature This button is used to set the required daytime room temperature T This button is used to set the required set back room temperature set temperature joom-day 20 0 Setting range: 5.0...30 Factorypreset: 20 accept joom-night 16 0 Setting range: 5.0...30 Factory preset: 16 DHW DAY 50 0 Setting range: 10...80 Factory preset: 50 This button is used to set the required domestic hot water temperature Adjustment (standard display mode only): After pressing the button for the required temperature the current value appears flashing and can be adjusted directly with the rotary pushbutton. Re-entry into the standard display is done by pressing the rotary-push button or the corresponding temperature button or automatically after approx. 60 seconds. Page 7

Operational mode selection for heating and hot water Select: With this button the required operational mode is selected. It appears in plaintext on the display, simultanously a cursor at the lower edge of the display points to the appertaining program symbol. Pressing the button, the previously selected operational mode appears flashing. The other operational modes can be selected and activated with the rotary-push button according to the following scheme. Page 8 HOLIDAY TIL 27 08 ABSENT TIL 19: 45 Entry into the previously selected heating operation mode Select required operational mode PAjTY TIL AUTOMATIC SUMMEj HEATING jed HEATING 02: 30 DHW STANDBY æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí accept, activate HOLIDAY TIL 15:30 27 08 ABSENT TIL 15:30 19: 45 PAjTY TIL 15:30 02: 30 set date or time Note: This mode is skipped in case of separate selection (see»function of operating modes«and»level SYSTEM - parameter CONTROL MODE«) activate, re-entry to standard display Plant off during holiday Interrupt heating operation Extend heating operation Heating operation via timer Domestic hot water only Permanent heating operation Permanent red. heating operation Plant off frost protection

Functions of operational modes Plant off during holiday Interrupt heating operation Extend heating operation Heating operation via timer Domestic hot water only Permanent heating operation Permanent red. heating operation Plant off frost protection HOLIDAY TIL ABSENT TIL PAjTY TIL MO 22 AUG ;05 SUMMER HEATING jed HEATING STANDBY 19:27 24 09 10:27 19 30 19:27 02 27 19:27 56 5 10:27 24 0 19:27 72 0 19:27 45 0 19:27 19 0 æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí æçèéêëìí Setting range: Setting range Setting range: Operating times: Operating times: Permanent heating Permanent reduced Heating and hot heating and water plant com- Actual date...actual P1: P1: (see level TIME PRO- (see level TIME PRO- and reduced hot date + 250 days Heating operation is Heating operation is GRAMS) GRAMS) water operation reduced hot water pletly switched off Return to the previously selected ope- switching-on time of switching-on time of Heating and dome- Only hot water ope- according to the the clock according protection mode. interrupted until next continued until next round the clock operation round except for frost rational mode at current operating time current operating time stic hot water operation automatically settings of hot water room temperature back temperature ration according to settings of daytime to the settings of set 0.00 o clock of the program (see level program (see level set return date. TIME PROGRAMS) TIME PROGRAMS) according to settings temperature (see and domestic hot (see Temperature of temperature values (see Temperature and selected opera- (see Temperature heating mode (see Temperature settings) water temperature settings), reduced Hot water operation is set to frost 0.5...24h: 0.5...24h: Heating operation Heating operation settings) and selected ting times program. settings) level UNMIXED protection temperature of 5. The heating operati- is interrupted until is continued until operating times program. water economic CIRCUIT) and hot set time of return. end of party. on is interrupted and temperature (see Earlier termination: Earlier termination: Earlier termination: frost protected. level DHW). Press button, Press button, Press button, Programming of individual operating times vidual operating times Programming of indi- select required operational mode with rational mode with rational mode with select required ope- select required ope- see level TIME PRO- see level TIME PROrotary-push button rotary-push button rotary-push button GRAMS). GRAMS). and press again to and press again to and press again to activate. activate. activate. Page 9

Quick operational mode selection modify if required Automatic mode MO 22 AUG ;05 16:32 activate 3 sec 62 5 Party mode Absence mode Manual hot water loading PAjTY TIL 3 sec 3 sec 3 sec ABSENT TIL 1 TIME DHW 0 0 02:50 19:45 min Setting range: 0...240 min Factory preset: 0.0 min Page 10 Short-time operational modes Frequently used operating modes such as PARTY or ABSENT or reloading the hot water tank during set back mode can be selected quickly according to the left scheme. Direct automatic mode Pressing button for approx. 3 seconds activates the automatic mode via timer inevitably. Functions and setting range see Operational mode selection for heating and hot water - Function of operational modes. Manual hot water loading To activate manual hot water loading outdoor of operation times the button has to be pressed for about 3 seconds. This turns on hot water preparation at any time for a period which may to be adjusted with the rotary pushbutton between 0...240 minutes. Pushing the rotary pushbutton activates loading. Afterwards the controller returns to program operation. At adjustment 0.0 the loading is independent of any time period. The tank will be loaded up to the set DHW-temperature value once.

Setting the heating characteristics (heating curve) Modify Slope HEAT CURVE HC 1 50 Store modification Note: The heating slope should be modified only in small steps and left for a while until steady condition can be obtained. Changes to the slope should be made in intervalls of 0.1 every 1 or 2 days. Setting range: OFF (heating circuit eliminated) 0,20...3,50 Factory preset: 1,50 This button regulates the heating characteristics of the heating circuit in relation to outdoor temperature. The adjustment is dependent of the plant installation and shows the relation between outdoor temperature and heat generator (boiler) temperature. The slope sets the change of the supply temperature, if the outdoor temperature changes for 1 K. Diagram of heating curves Heat generator temperature () 100 90 80 70 60 50 40 30 2.00 1.75 1.50 (factory preset) 1.25 1.00 0.75 0.50 0.20 20 20 16 12 8 4 0-4 -8-12 -16-20 Outdoor temp.() Re-entry into the standard display is done be pressing the button again or automatically after approx. 60 seconds. Page 11

Plant information Entry into information level Page 12 Inquire anti-clockwise heat circuit information one after the other Examples: AUTO-P1 DAY HC ON AUTO-P1 DAY DHW HEAT GENEj ON STAjTS 1245 OFF Direct heating circuit (unmixed) Domestic hot water circuit Heat generator (boiler) Heat generator starts (number of starts) OUTSIDE 13 5 Outdoor temperature Inquire clockwise temperatures, consumption datas one after the other Examples: Outdoor temperatur Minimum-maximum value between 0.00h and 24.00h Heat generator temperature (boiler temperature) Return flow temperature (only with return flow sensor) Flue gas temperature (only with flue gas sensor) OUT MIN/MAX 8 0 14 5 HEAT GENEj 65 0 jetujn FLOW EXHAUST 45 0 135 0 This button displays all plant temperatures and states of all circuits. The information can be requested according to the direction with the rotary-push button. Turning rotary-push button clockwise displays from all plant-specific temperatures the actual values and the nominal values (pressing rotary-push button) meter readings such as consumption data etc. Turning rotary-push button anti-clockwise displays from direct heating circuit resp. DHW circuit operational mode (holiday, absence, party, auto etc.) timer programm P1( P2 and P3 only when released) heating mode (daytime-, reduced-, ECO-mode) identification (direct circuit HC, hot water circuit DHW) status of heating- and DHW charging pump (on, off)

OPER HOURS 258 THEjMOSTAT HC OFF ROOMTEMP HC 21 0 Heat generator run time number of service hours Room thermostat function 2) room max. temp. delimitation Room temperature 2) Direct heating circuit Hydraulic pressure 1) (only it pressure sensor is present) Hot-water temperature (electronically controlled) Hot-water thermostat 1) (mechanically controlled) HYDRAU PRESS 1 4 DHW DHW resp. 52 0 THEjMOSTAT OFF shows operating status (on, off) number of service hours number of starts of heat generator, boiler etc. shows room thermostat function (heating on, off) current room temperature if room sensor is activated shows water pressure if pressure sensor is present 1) display dependent on the type of heat generator 2 will be displayed only if the room sensor was activated before Page13

0 2 4 6 8 10 12 14 16 18 20 22 24 Standard display (Example: Operational mode AUTOMATIC) MO 22 AUG ;05 19:45 58 5 Programming level - Level summary Schematic block diagram Page 14 Entry into the level selection 3sec press knob for approx. 5 seconds Select Level TIME-DATE TIMEPROGRAMS SYSTEM DOMESTIC HOT WATER (DHW) UNMIXED HEATING CIRCUIT Entry: TIME SELECT CIRCUIT HC (Heating) DHW (Hot water) LANGUAGE D GB F I ECO-Temperature reduced nominal DHW-value REDUCED HEATING ECO/Reduction back forward back forward back forward back forward YEAR WEEKDAY (Mo-Su) Heating cycle (1...3) Copying function TIME PROGRAM P1 P1-P3 LEGIONELLA PROTECTION Day 1-7) HEATING SYSTEM m-value Underfl./rad./conv. back forward back forward back forward back forward

back DAY-MONTH CHANGEOVER Summer-Wintertime back forward forward HEATING START selected cycle HEATING END selected cycle TEMPERATURE selected cycle OPERATING MODE common (1) separate (2) back back SUMMER switching off PARAM.-RESET Reset to factory preset forward forward Selection and modification of parameters and setting values Entering into the programming level, principally the operating times level (TIME PROGRAMS) appears at first. All other levels, such as - SYSTEM - DHW - UNMIXED CIRCUIT - DATE-TIME can be selected directly via rotary-push button By pressing the rotary-push button, the selected flashing level is activated; the first value resp. parameter appears flashing. If necessary, it can be modified via the rotary-push button and accepted by pressing again. If necessary, the following parameters can be treated in the same way. back forward Re-entry into the level selection is done via the info button, reentry into the standard display via the program-selection button or automatically after approx. 60 seconds. Page 15

Programming of operating times Page 16 Standard display Press for approx. 3 seconds Enter operating times level MO 22 AUG ;05 15:30 62 5 3sec TIMEPjOGjAMS With this mode of operation individual programs, other than standard programs for heating and hotwater mode can be set up. For this purpose after selecting the heating- resp. hot-water circuit the factory preset standard program (P1) is called an can be overwritten individually. For programming the operation times, for each week day maximum three heating cycles with one switch-on and switch-off time each are available. Further more, the heating- resp. hot-water cycle can be combined with a required room temperature resp. hot-water temperature for the duration of the cycle. accept Select heating circuit For example unmixed heating circuit HC accept TIMEPjOGjAMS HC TIMEPjOGjAMS DHW select program P1...P3, if released

Select day and cycle For example Tuesday - heating cycle 1 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 MO-1 20 0 MO-2 8 14 16 22 24 -- ----- -- 0 2 4 6 10 12 18 20 TU-1 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 20 0 0 2 4 6 8 10 12 14 16 18 20 22 24 0 2 4 6 8 10 12 14 16 18 20 22 -- ----- -- -- ----- -- - Wed - Thu - Fri - Sa t - Sun - TU-2 SU-2 -- - -- - -- - Modify accept switching-on time 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 TU-1 20 0 Setting range 0.00...24.00 h Note: The 3 rd heating cycle is skipped if the 2 nd heating cycle does not include any operating times. accept Modify - Exit : Modify switching-off time 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 TU-1 20 0 Setting range: 0.00...24.00 h Confirm the selected flashing value by pressing the rotary-push button. Then set the new required value and take over by pressing the rotary-push button again. Modify accept temperature accept 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 TU-1 20 0 For heating circuit: Room temperatur Setting range: 5.0...30.0 For hot-water circuit: Hot-water temperature Setting range: 10.0...80.0 (resp. DHW-max) Re-entry into the former step in done by pressing the button, exit into the standard display via the button or automatically after approx. 60 seconds. Page 17

Copy operating times Standard display Push for approx. 3 seconds MO 22 AUG ;05 15:30 3sec 62 5 Page 18 Programming of operating times includes a extensive copying function which allows to copy any day of the week to other days (Mo..Su) resp. to the whole week (1-7) or parts of a week such as workdays (1-5) or weekends (6-7). Enter operating times level TIMEPjOGjAMS accept Select heating circuit For example unmixed heating circuit HC accept TIMEPjOGjAMS HC TIMEPjOGjAMS DHW select program P1...P3, if available Select copy function COPY DAY 8 14 16 20 24 06 00-22 00 0 2 4 6 10 12 18 22 MO-1 20 0

Select source Example: Monday accept Select first destination Example: Monday to Friday Copy COPY FjOM COPY TO MO MO 1-5 Setting range: Monday (MO)...Sunday (SU) Setting range: Days (MO...SU), whole week (1-7), Working days (1-5), weekend (6-7) Modify - Exit : Confirm the selected flashing value by pressing the rotary-push button. Then set the new required value and take over by pressing the rotary-push button again. Re-entry into the former step in done by pressing the button, exit into the standard display via the button or automatically after approx. 60 seconds. Confirmation COPY DAY OK Source and destination are identical Select Example: Saterday and Sunday next destination COPY TO etc.. MO 6-7 If necessary select and takte over further destinations in the same way. Page 19

Reloading of standard time programs - deleting of individual time programs Page 20 Standard display Push for approx. 3 seconds Enter operating times level MO 22 AUG ;05 15:30 62 5 3sec TIMEPjOGjAMS The standard programs do not get lost by overwriting with individual programs. Individual programs however are cancelled at a later call of the corresponding standard programs and have to be set up again. For this purpose individual switching-on and switching-off times should always be noted (see level TIME PROGRAMS - table for individual programs). Select default time accept DEFAULT-TIME accept TIMEPjOGjAMS HC Modify - Exit : Confirm the selected flashing value by pressing the rotary-push button. Then set the new required value and take over by pressing the rotary-push button again. Re-entry into the former step in done by pressing the button, exit into the standard display via the button or automatically after approx. 60 seconds. Select heating circuit For example unmixed heating circuit HC DEFAULT-TIME HC DEFAULT-TIME DHW DEFAULT-TIME ALL

accept jeset HC select program P1...P3, if released 1) Reset 3sec press approx. 3 seconds! jeset OK Standard program was reloaded Individual Program was deleted! 1) see level SYSTEM - parameter PROGRAM Standard time programs Standard operating-times program P1 Circuit Day Heating from...to Unmixed heating circuit (HC) Domestic hot water (DHW) Mo-Su Mo-Su 06.00-22.00 h 05.00-22.00 h Standard operating-times program P1 1) Circuit Day Heating from...to Mo-Th 06.00-08.00 16.00-22.00h Unmixed heating circuit (HC) Fr 06.00-08.00 13.00-22.00h Sa-Su 07.00-23.00h Mo-Th 05.00-08.00 15.30-22.00h Domestic hot water (DHW) Fr 05.00-08.00 12.30-22.00h Sa-Su 06.00-23.00h Standard operating-times program P3 1) Circuit Day Heating from...to Unmixed Mo-Fr 07.00-18.00 h heating circuit (HC) Sa-Su reduced heating Domestic Mo-Fr 06.00-18.00 h hot water (DHW) Sa-Su reduced heating Page 21

Table for individual operating times and programs Page 22 Unmixed heating circuit (HC) Day Mon Tue Wed Thu Fri Sat Sun 1 st cycle From till Operating times program P1 Operating times program P2 Operating times program P3 2 nd cycle! 3 rd cycle 1 st cycle 2 nd cycle! 3 nd cycle 1 st cycle 2 nd cycle! 3 rd cycle Domestic hot-water circuit (DHW) Day Mon Tue Wed Thu Fri Sat Sun 1 st cycle 2 nd cycle 2! 3 rd cycle 1 st cycle 2 nd cycle! 3 rd cycle 1 st cycle 2 nd cycle! 3 rd cycle

TIME-DATE Entry: set time TIME-DATE TIME 18:45 Current time Setting range: 0.00... 24.00 h Entry: see» Programming level - Level summary «. Exit: via button or automatically after 60 seconds Modify: Confirm selected flashing parameter by pressing the rotary-push button. Then set the new required value via and accept by pressing the rotarypush button again. If necessary, correct the following parameters in the same way. set year set day & month YEAj DAY-MONTH MO 2005 22 08 Calender year Setting range: 2001... 2099 Calender day-month-weekday Setting range: 01.01... 31.12. Weekday is set automatically The values to the left are factory presets and normally need not be updated. If in some exceptional cases corrections should be necessary, the values can be adapted to the real conditions. The internal pre-programmed calender provides an automatic time changeover at the yearly repeating summer-wintertime dates. If required, the automatic time changeover can be switched off (manual reset). set changeover CHANGE SU-WI AUTO Time changeover mode Setting range: Automatic: last Sunday in March & Oct. Manual: no time reset Page 23

SYSTEM SYSTEM SYST SYST Entry: LANGUAGE PjOGjAM SYST GB next parameter P1 next parameter This level includes general delimiting parameters and options referring to the corresponding heating system Language Setting range: D = GERMAN GB = ENGLISH F = FRENCH I = ITALIAN Factory preset: D All information appearing on the display are available in the languages German, English, French and Italian. After entry as first parameter appears the language selection. The required language can be selected and accepted according to the above assignment. Operating times program Setting range: P1, P1-P3 Factory preset: P1 This parameter specifies the number of the released time programs. With setting P1 only one operating-times program is available, with setting P1-P3 all three programs are released and can be selected for programming operating times. Application: Page 24 Entry: see» Programming level - Level summary «. Exit: via button or automatically after 60 seconds Modify: Confirm selected flashing parameter by pressing the rotary-push button. Then set the new required value via and accept by pressing the rotarypush button again. If necessary, correct the following parameters in the same way. Use of the instrument at the corresponding language area. Application: Shift work, different programs for summer, transition period, winter etc.

CONTjOL MODE SYST next parameter 1 Control mode Setting range: 1 = common mode Factory preset: 1 2 = separated mode Common control mode: The selected operational mode (via button for Holiday, Absence, Party, Automatic etc.) applies to the heating circuit and to the hot-water circuit together. Separated control mode: The heating- and hot-water circuit can be assigned with own operational mode. Application: Objects with uniform seizure character (Onefamily houses etc). Application: Objects with different use of heating and hotwater (for example heating operation in Holiday mode, hot-water permanently in reduced mode). Operational mode Select Circuit OP MODE HC Unmixed circuit (HC), hot-water circuit (DHW) accept further operation see»operational mode selection for heating and hot water«and»temperature settings«page 25

SOMMER SYST 20 0 next parameter Summer switch-off Setting range: OFF, 10.0 to 30,0 Factory preset: 20.0 This parameter specifies the heating delimiting value regarding the average resp. current outdoor temperature and puts the heating plant automatically out of service as soon as the outdoor temperature exceeds the set heating delimiting value. During summer switch-off the pump of the heating circuit is activated each day for approx. 10 seconds to protect it against corrosion. With setting OFF the summer switch-off is not effective. Hot water preparation is not affected by summer switch-off. Page 26 Note: The active summer switch-off appears on the standard display with a sunshade symbol. MO 22 AUG ;05 À 16:32 63 5 Summer switch-off activated Application: All objects which do not require a heating operation during summertime jeset SYST Parameter-reset This function resets all individually entered values in the programming level to factory preset. Exception: Time-date, operating times jeset SYST SET Reset: Press rotary-push button for approx. 5 sec. while indication SET is flashing, until standard display appears. Important: Reset may only be executed if all individually entered values shall be replaced by the factory! preset values!

DOMESTIC HOT WATER DHW DHW DHW NIGHT Entry: 40 0 next parameter This level includes the necessary parameters for programming the hot-water circuit except the hot-water operating-times. Hot-water economic temperature Setting range: 10.0 up to the required hot water temperature Factory preset: 40.0 This parameter determines the amount of the reduced hot-water temperature outside the hot-water operating times (between the hot-water cycles) as well as in the operational mode ABSENCE for the duration of absence. Entry: see» Programming level - Level summary «. Exit: via button or automatically after 60 seconds Modify: Confirm selected flashing parameter by pressing the rotary-push button. Then set the new required value via and accept by pressing the rotarypush button again. If necessary, correct the following parameters in the same way. Application: Base temperature inside the hot-water tank in order to avoid a cooling down of the tank. Note: This parameter is skipped if a hot-water thermostat is used instead of an electronic hot-water sensor. LEGION PjOT DAY OFF Legionella protection (day) Setting range: OFF, MO...SU, ALL Factory preset: OFF The legionella protection serves to avoid a legionella infestation inside the hot-water tank and is activated on the selected weekday (Mon to Sun) or every day at 2.00 o clock. If the hot-water temperature should drop below 65, the tank is reloaded. With setting OFF this function is not effective. Note: Other legionella protection times can be regulated exclusively by the heating plant specialist. Important: Danger of scalding! Use thermostatic mixing valve on DHW outlet. Page 27

Unmixed heating circuit (direct circuit) UNMIXED CIRC HC jed HEATING HC Entry: ECO next parameter This level includes the parameters required for programming the heating circuit with the exception of the related operatingtimes programs. Reduced heating mode Setting range: ECO, ABS Factory preset: ECO During the reduced operation the following modes can be selected: ECO mode: At oudoor temperatures above the set plant frost protection the heating circuit is switched off completely. At temperatures below frost protection the heating circuit is controlled with reduced heating characteristic according to the required reduced temperature (see»temperature setting«). RED mode: During the reduced mode the heating circuit pump remains activated. The heating circuit is controlled according to the reduced heating characteristic, the temperature does not drop below the set minimum temperature value. Page 28 Entry: see» Programming level - Level summary «. Exit: via button or automatically after 60 seconds Modify: Confirm selected flashing parameter by pressing the rotary-push button. Then set the new required value via and accept by pressing the rotarypush button again. If necessary, correct the following parameters in the same way. Application: Objects with high insulation values Application: Objects with low insulation values

HEAT SYSTEM HC 1 30 Adaptation to the heating system Setting range: 1,00 to 10.0 Factory preset: 1,30 This parameter refers to the type of the heating system inside the heating circuit and has to be adapted to the exponents of the corresponding consumer (underfloorradiator-convector). The setting value specifies the curvature of the heating curve of the weather dependent heating circuit and compensates the system-related efficiency losses at the lower temperature range by a progressive heating curve in conformity with the adjustment. Applications: The following setting values are recommended for the belowmentioned applications Setting value 1.00... 1.10 1.30... 2.20 Application Heating curve for underfloor heating systems or other static heating surfaces Normal standard heating curves for radiators 3.00... 4.00 4.00... 10.0 Heating curves for convectors Special heating curves for ventilators with high starting temperatures Page 29

Error messages Page 30 OUTSIDE EjjOR HEAT GEN EjjOR DHW EjjOR 10-0 30-n 50-4 Example for error message»sensor«(short or open circuit) Error code 10...20 Example for error message»heat generator«(flue gas temperature exceeded) Error code 30...40... 1) Example for logical error messages (control functions) Error code 50...60 The instrument is equipped with an extensive error diagnostic features. The error displayed takes priority over other displays and varies dependent on the model in question. For error messages from burner control (ERROR Xn:m) the error codes in the corresponding installation manuals have to be considered. Note: Error messages only appear alternating with the standard display.! In case of error messages the heating specialist always has to be informed! BUS EjjOR 70-n Example for error message»data bus«(address error) Error code 70 1) For these error messages the error codes of the heat generator in the corresponding installation manuals have to be considered.

Personal notes Seite 31

Technical specification Supply voltage: Via data bus (DC-safety voltage by EN 60730) Power consumption: 300 mw Bus interface: T2B or OpenTherm according to model Ambient temperature: 0...60 Storage temperature: -25...60 Protection type acc. to EN 60529: IP 30 Protection class acc. to EN 60730: III Approval according to: VDE 60730 Casing dimensions (BxHxD): 90 x 138 x 28 mm Casing material: ABS, antistatic Electrical connections: 2-wire mode with plugable connection Recommended cable: J-Y(St)Y 2 x 2 x 0.6 mm 2 Max. length of cable: 50 m Data and timer back up: Min. 5 years from date of delivery Accuracy of the internal clock ± 2s/day Weight: Approx. 150 g Subject to change Art. 0450017010-0528-21