E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

Similar documents
E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

FL2011EI-HS FL2012EI-HS FL2022EI-HS

FAAST LT SET-UP AND TROUBLESHOOTING GUIDE. CONTENTS Introduction...1 Wiring up a FAAST LT unit...1. Setting the Fan speed...7

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize)

Intelligent addressable fire alarm control panel

Laptop / PC Programming Manual

LASER ASPIRATED SMOKE DETECTOR

FAAST. Fire Alarm Aspirating Sensing Technology

LASER ASPIRATED SMOKE DETECTOR

FAAST XT 9400XA Fire Alarm Aspiration Sensing Technology

Alarm Client. Installation and User Guide. NEC NEC Corporation. May 2009 NDA-30364, Revision 9

End To End Optical Beam Smoke Detector. Additional Information

FAAST 7100X INSTALLATION AND MAINTENANCE INSTRUCTIONS. Document Colour Code Key: (refer to Page 28) SPECIFICATIONS: TABLE OF CONTENTS

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

LM80031 Issue H. Installer s Handbook

FAAST XS 7100X Fire Alarm Aspiration Sensing Technology

OVEN INDUSTRIES, INC.

HOBO U14 Data Logger User Manual

FAAST. Fire Alarm Aspirating Sensing Technology

FEC400 Series. Installation Manual

User Manual. Dryer Controller M720

FIRERAY 5000 range USER GUIDE

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Ontech GSM 9040/50. Reference Manual English -1 -

D2E Duct Smoke Detector

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

Dryer Controller M720

FAAST. Fire Alarm Aspiration Sensing Technology

465 ma, All relays active, all alarm levels displayed

CSP-204 CSP-208 CSP-104 CSP-108

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

Motorised Infrared Optical Beam Smoke Detector. User Guide

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

Added password for IP setup page : Password must be in IP format!

EXTINGUISHING AGENT RELEASE MODULE

THX-DL Data Logger USER & INSTALLATION MANUAL V

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

USER MANUAL DexTempTM 1000 Temperature Monitor (P/N: IR-1001) DexTempTM 1000 USB Non-Contact Temperature Monitor. User Manual.

SCAN200E USER S MANUAL

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM

rvm4c Installation Guide Remote Video Module

Halton SAFE / 7.14 user guide and installation instructions

MODEL 6200 ANALOGUE ADDRESSABLE OPTICAL BEAM SMOKE DETECTOR

System 800 Addressable Fire Detection & Alarm System

4100U City and Relay Cards Installation Instructions

Excel-EN Conventional Fire Control Panel

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

This is to certify that the optical output of the: SENSORNET LR-DTS Temperature Sensing System: (Variants Mark 1, Mark 2a and Mark 2b)

Motorised Infrared Optical Beam Smoke Detector. User Guide

Installation, Operating and Maintenance Manual

BSR Addressable Fire Detection control panel. Installation operation manual

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Consultant Specification AGILE Wireless Fire Detection System

VAP304 PRO INSTALLATION & OPERATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

MultiSite Manager. Setup Guide

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Application, Installation, Operation & Maintenance Manual

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

Supervisor Standard Edition

BURGLAR ALARM PANEL BS-468

iminiplus PDF User Guide Version 2.0

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

POL-200-TS User Manual

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

ocbridge Plus SPECIFICATION 3. COMPONENTS Wireless sensors receiver, battery СR2032, manual, instalation CD.

Aspir A ation spir P R O D U C T S

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

SUPERINTEND VRE-08/16/32/64

PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM

Notifier by Honeywell: FAAST TM Fire Alarm Aspiration Sensing Technology

GSM RFID VOICE Alarm System

INSTALLATION AND MAINTENANCE INSTRUCTIONS TC866E Series LASER ASPIRATED SMOKE DETECTOR

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

TV2 Clean Room Monitor

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

Solution F2. Fire Alarm Control Panels one step ahead.

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

Patriot Systems Limited

Dashboard for Windows V1.1.0

Danfoss gas detection units

Simplex Panel Interface Guide

MAKING MODERN LIVING POSSIBLE INT INT EFIT 550. User Guide and Installation Manual. Danfoss Heating

Please use authentic SATA hard drive, USB device and battery.

Millennium Xtra. Millennium ATMA setup and configuration guide. May Millennium Group, Inc.

ANALOGUE ADDRESSABLE FIRE PANEL MAGPRO96 INSTALLATION AND PROGRAMMING MANUAL

Danfoss gas detection unit Type GD Heavy Duty

PowerRouter application guideline

Transcription:

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration Sensing Technology (FAAST) family. FAAST is an advanced fire detection system for use where early warning and very early warning are a requirement. The system continuously draws air from the controlled environment through a series of sampling holes to monitor the environment for smoke particulate. The FL0 is the stand-alone version of the FAAST LT range and is available in different models: FL0E - Has single channel capability with one laser smoke sensor. FL0E - Has single channel capability with two laser smoke sensors in a common chamber for coincidence detection. FL0E - Has two channel capability with two laser smoke sensors in separate chambers. (One sensor for each channel). This guide provides information for mounting and basic installation using the unit s default factory settings. For more extensive information please see the FAAST LT Advanced Setup and Control Guide - reference D00-00-00. SPECIFICATIONS Electrical Characteristics Voltage Range:. -. VDC Supply Current: Channel: 0mA (typical); 0mA (max) @ VDC o C (excluding sounders) Channel: 0mA (typical); 0mA (max) @ VDC o C (excluding sounders) Configurable Input: Activation Time: s (min) Relay Contact Ratings:.0 A @ 0 VDC, 0.A @ 0 VAC Environmental Ratings Temperature: -0 C to C Relative Humidity: 0% to % (non-condensing) IP Rating: Mechanical Exterior Dimensions: See Figure Wiring: 0. mm² to mm² max Maximum Single Pipe Length: 00m (Classes A. B & C) Maximum Number of Holes: See Table A Figure : Dimensions and Knock-Outs Pipe Spec (EN-0 Compliance): to EN (Crush, Impact, Temp ) Outside Pipe Diameter: mm (nom) or mm (nom) Shipping Weight:.kg (inc sensors) PARTS LIST mm Description Quantity FAAST LT unit Mounting bracket -pin Terminal block -pin Terminal block -pin Terminal block k-ohm EOL Resistor USB Cable Front Panel Labelling Pack Installation Kit CD Quick Installation Guide mm Important Note Aspirating Smoke Detectors supplied and installed within the EU must conform to the EU Construction Products Directive (/0/EEC) and the related European Product Standard EN -0. FAAST LT has been tested and certified to ensure that it conforms to the necessary Standards, but strict adherence to this instruction guide is advised to ensure that the installation meets the requirements of the CPD Directive D00-0-00 I--0 mm

ALARM PREALARM This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations. PHYSICAL INSTALLATION Front Panel Labels The LT FL0 is shipped without the front panel labels fixed in place. This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack. Figure shows where the labels need to be placed: Figure : How to Knock Out Cable Gland Holes Mounting the LT FL0 to the Wall 0 0 INDICATES CENTRE OF ASPIRATING PIPES LEVEL LEVEL MODULE MODULE FAAST LT HANGING LUGS A FIXING HOLE USE FOR PLUMB-LINE FIXING HOLE LOW FLOW INPUT ASPIRATOR DISABLE EM / TEMPERATURE Figure : Mounting Bracket S YS T Figure : Placing the Front Panel Labels 0 mm mm When label A is in place, remove the protector from the bottom of the clear cover to stick the cover down, as shown in Figure : mm mm POSITION OF BRACKET * Figure : Remove Backing to Stick Cover Down PLUMB LINE mm Cable Access Knock out cable gland holes where required. The location of the cable gland holes is shown in Figure, represented by the icon: OUTER DIMENSION OF UNIT BASE OUTLINE * mm mm * Minimum clearance required from hinges to open door = mm. Figure : Fasten the mounting bracket to the wall D00-0-00 I--0 Pittway Tecnologica S.r.l. Via Caboto /, TRIESTE, Italy

Figure : Sequence ( to ) to Mount the Detector on the Bracket a mm mm Pipe Hole Configuration Figure below shows the pipe holes available on the unit. Each unit has pipe holes per channel (so if installing a channel unit, holes and do not function). Use Table to locate the holes required for the installation: Figure : Pipe Holes b 0 mm 0.00 o Table : Pipe Holes Used for Each FAAST LT Model c FAAST LT MODEL INLET PIPE HOLE OUTLET PIPE HOLE FL0E &, or or FL0E &, or or FL0E Channel &, or or Channel &, or or Note : Pipe holes not used should be kept sealed. Note : Do NOT glue pipes into the pipe holes. Table a: Maximum Number of Pipe Holes Allowed Per Channel mm All figures quoted using highest (level ) sensitivity CLASS PIPE LENGTH (m) MAX NUMBER OF HOLES PER CHANNEL C 00 (0 x.mm, x mm) + mm non sensing end hole) B 00 ( x mm, x mm inc end hole) A 00 x mm (+ mm non sensing end hole) A 0 ( x mm, x mm inc end hole) d Pipe Installation 0 D00-0-00 I--0

Exhaust Pipe SAMPLING AREA SAMPLING AREA WIRING INSTALLATION Power, Alarm and Control Connections CHANNEL CHANNEL EARTH BAR MOUNT EARTH BAR (OPTIONAL) AND ALARM CONNECTIONS EARTH BAR MOUNT USB PORT Note : All wiring should comply with local requirements and regulations. Note : Panel wiring must observe the recommendations of the panel manufacturer Figure : Inside the Detector COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET D00-0-00 I--0 Pittway Tecnologica S.r.l. Via Caboto /, TRIESTE, Italy

Table : Wiring Terminal Designations (Note - Terminals marked CH will only be available on channel models) No. Function Ext Power In + Primary PSU Ext Power In - Primary PSU Aux Power In + Not used in default T Aux Power In - Not used in default NC Alarm Relay CH C Alarm Relay CH T NO Alarm Relay CH NC Alarm Relay CH C Alarm Relay CH T 0 NO Alarm Relay CH NC Fault Relay CH C Fault Relay CH T NO Fault Relay CH NC Fault Relay (AUX) CH C Fault Relay (AUX) CH T NO Fault Relay (AUX) CH Sounder Output - Sounder Output + k-ohm EOL Resistor T Sounder Output - 0 Sounder Output + k-ohm EOL Resistor T Configurable Input + (Reset) Default is active = short circuit Configurable Input - (Reset) (unsupervised) T NC Pre-Alarm Relay CH C Pre-Alarm Relay CH T NO Pre-Alarm Relay CH NC Pre-Alarm Relay CH C Pre-Alarm Relay CH T0 NO Pre-Alarm Relay CH Table : Relays RELAY ACTION: NOTES ALARM or Set ON when ALARM CONDITION is met on a channel Default condition = Level. Alarm state is latched as default. A manual RESET is necessary to deactivate LED and relay. PRE-ALARM or Set ON when PRE-ALARM CONDITION Default condition = Level. is met on channel. or When CONDITION on Ch or Ch Fault state is not latched (default) or a common occurs. Fault is also indicated when in SERVICE mode and when the unit is unpowered. or Set ON when a channel is in ALARM / PRE-ALARM. Sounder corresponds to Ch and Sounder corresponds to Ch Default condition = set on in ALARM. ING UP Using Default Settings. Connect a suitable VDC supply (complying with European Standard EN -) to pins and on terminal block T (See Table ). Check the voltage at the connector. Make sure it is within the required voltage range.. If the voltage is within the specified range, connect the power connector to the unit.. Close and secure the housing door; verify the fan starts up and air flows out of the exhaust port. The unit takes - minutes to initialise and stabilise in normal mode. Configuring Other Options To change any of the default options, it will be necessary to connect the detector to a PC/laptop with the PipeIQLT software installed; see USB connection section later in this guide for more information on this (and the FAAST LT Advanced Setup and Control Guide). EXTERNAL RESET The default setting for the configurable external input is Device Reset (terminal block T). A short circuit connection between these terminals will cause the FAAST LT unit to perform a reset. D00-0-00 I--0

TEMPERATURE / INPUT FRONT PANEL The front panel will be different depending on which of the FL0 models is being installed, and each is shown below. The following information is displayed: Detector Status: Normal, Alarm, Fault or Isolate Alarm Level; Alarm, Pre-Alarm Particulate Levels; - Flow Level Test, Reset and Disable Buttons 0 ALARM PREALARM Figure 0: Front Panel Display LEVEL ALARM PREALARM 0 LOW FLOW ASPIRATOR DRIFT COMPENSATION TEMPERATURE / INPUT DISABLE / SYSTEM LEVEL 0b: FL0E Channel Detector ( Sensors) ALARM LOW FLOW ASPIRATOR DRIFT COMPENSATION DISABLE / SYSTEM 0 PREALARM 0 0a: FL0E Channel Detector ( Sensor) LEVEL LEVEL LOW FLOW ASPIRATOR DRIFT COMPENSATION TEMPERATURE / INPUT DISABLE / SYSTEM 0c: FL0E Channel Detector D00-0-00 I--0 Pittway Tecnologica S.r.l. Via Caboto /, TRIESTE, Italy

Table : Front Panel Indicators and Fault Descriptions INDICATOR ACTION WARNING OR TROUBLE COMMENT / ACTION CHANNEL / ALARM ON Red, Channel is in alarm (relay is No delay with default settings set) BLINK Green, when sensor is polled Not in alarm CHANNEL / PRE- ALARM ON Channel is in pre-alarm (relay is set) LEVEL ON Led number indicates sensor Only numbers used alarm level reached ON FAAST LT is in initialization ON Common or multiple faults BLINK Fault delay Default = 0s. ON FAAST LT is powered ON Low power alert / high power fault Check the power supply voltage. CHANNEL FLOW INDICATORS / ON The LED indicates the air flow for a channel: - Centre = normal flow - Left = flow low; (-0% at extreme) - Right = flow high; (+0% at extreme) On channel unit: Upper row = Ch Lower row = Ch LOW FLOW ON Low flow fault Check filter; check pipe network for blockages. BLINK Sensor initialization fault Try to restart device. Replace faulty sensor. BLINKS Sensor communication fault Check sensor addresses and installation; replace sensor. ASPIRATOR ON Air flow sensor fault Try to restart device. BLINK Flow initialization fault Check filter; check pipe network for blockages. Try to restart the device. BLINKS Fan fault Try to restart device. DRIFT COMPENSATION BLINK Drift compensation, st alert Clean sensor BLINKS Drift compensation, nd alert Clean sensor BLINKS Drift compensation limit warning Sensor needs urgent maintenance TEMPERATURE BLINK Low temperature alert Check the air flow temperature BLINKS High temperature alert Check the air flow temperature INPUT BLINK External input fault Not used with default settings DISABLE BLINK Alarms, faults & alerts not reported Returns to Maintenance then Normal operation after 0min (default) SYSTEM BLINK Wrong configuration Flashes all LEDs. Try to restart device. BLINKS EEPROM fault Check power supply voltage. Try to restart device BLINKS Real time clock fault RTC is corrupted or time reading failed. BLINK Sounder fault Check the sounder circuit and the EOL BLINK Filter alert at set date No date set as default ON High flow fault Check pipe network for breaks or leaks. In case of simultaneous alerts/faults on the same LED, priority order is: ON (Highest), blink, blinks, blinks (Lowest) Front Panel Buttons The front panel has user buttons: TEST, RESET and DISABLE. These buttons are used to enter the pass-code which then allows the user to carry out simple test functions. Note: In Remote Maintenance and Service Mode, these buttons are always disabled. Figure : User Interface Buttons D00-0-00 I--0

0 PREALARM 0 LEVEL LEVEL Table : Front Panel Buttons BUTTON NORMAL Mode MAINTENANCE Mode RESET When pressed for s, starts PASSWORD PROCEDURE to enter Maintenance mode. DISABLE TEST LEVEL Used to increment Password digits in PASSWORD PROCEDURE Used to confirm password in PASSWORD PROCEDURE. Default Password = When pressed for s latched alarms, faults and sounders (relays) are reset In DISABLE Mode, if pressed for s unit will exit from DISABLE Mode but remains in MAINTENANCE Mode When pressed for s, device enters DISABLE Mode for 0 minutes (default). (Alarms, alerts and faults not reported). (To exit DISABLE Mode see RESET) When pressed for s and released, both sensor will simulate alarm When pressed for s and released, sensor # will simulate alarm DRIFT COMPENSATION LOW FLOW TEMPERATURE / INPUT DISABLE / SYSTEM ASPIRATOR DRIFT COMPENSATION TEMPERATURE / INPUT COMBINATIONS RESET + DISABLE DISABLE / SYSTEM When pressed for s and released, sensor # will simulate alarm When pressed for s, shows fan speed (on smoke level scales) for a preset time. When pressed for s, shows fan speed (on smoke level scales) for preset time. RESET + TEST No action When pressed for s, turns off sounders RESET + TEST + DISABLE No action When pressed for s, unit exits from MAINTENANCE Mode Password Sequence to Enter Maintenance Mode Press and hold RESET; Left flow indicator will turn yellow, then green. Release RESET and indicator will switch on green. The left flow indicator will blink green indicating the device is ready for the first digit. Press DISABLE to increment the LEDs ; press TEST to select a digit. The flashing airflow segment will turn solid green and the next segment will begin to flash indicating set the next digit. When the th digit is selected, all airflow segments are turned off. If the password is accepted the indicator will remain green and the unit enters Maintenance mode. If the password is incorrect the indicator flashes yellow and the unit remains in Normal mode. The Default password in. If no button is pressed for 0s during the password sequence, the unit returns to Normal mode. If there is no activity in Maintenance mode for minutes (default), the indicator blinks green for s and then the unit returns to the Normal state. TESTING Magnet Test The alarm signalling can be tested for functionality by placing a test magnet in the position shown in Figure (displayed earlier in the guide). This method does not test the air flow in the pipe-work. Smoke Testing The system alarm response can be tested for functionality using smoke. The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the duration of the test. Smoke pellets or matches can be used close to the sampling point to introduce smoke particulates into the system. It is recommended that smoke with a particulate life cycle of greater than 0s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems. Fault Testing Simulate a fault on the detector (for example, block the outlet pipe) and check that a fault is signalled on both the front panel of the unit and at the CIE (Fire Panel). SERVICE WARNING Isolate the aspirating detector from the fire alarm system to prevent any unwanted alarms when opening the front door of the unit. Make sure all power is removed from the system before removing any covers. Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode. The LEDs will blink, the unit will switch off power to the fans and the fault relay will indicate a fault. When the cabinet door is closed, the unit restarts automatically. Filters Periodic cleaning or replacement of the filters will be required. The filters are located inside the cabinet at the top of the unit (see Figure displayed earlier in the guide) and are removed as shown in the sequence below: F i lters Either replace the filter assembly or carefully brush off the accumulated dust. Refit the filter, close and secure the cabinet door. The unit will initialise and re FOAM GASKET D00-0-00 I--0 Pittway Tecnologica S.r.l. Via Caboto /, TRIESTE, Italy

Either replace the filter assembly or carefully brush off the accumulated dust. Note: If replacing the filter, remove the foam gasket from the old filter and place onto the new filter. When placing the new filter into the slot, ensure that the gasket is correctly aligned. Refit the filter, close and secure the cabinet door. The unit will initialise and restart. Smoke Sensors The smoke sensors are located under the sensor cover (see Figure displayed earlier in the guide). To access the sensors, follow the sequence below: PipeIQ LT QUICK START INSTRUCTIONS Overview of PipeIQLT The PipeIQLT software program is a convenient and powerful Windows based application that can be used to quickly and accurately design pipe networks, generate configuration parameters for correct set-up and operation, and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices. PipeIQLT provides a graphical interface on a PC to: Develop and verify the performance of pipe network solutions. Configure the design parameters to suit local fire codes and standards. Generate Pipe Layouts, BoMs, Configuration and Event Log Reports. Control, Test and Monitor FAAST LT devices. There is a comprehensive Help Menu to guide the user through the different windows and options. The contents have a detailed index and a versatile search facility to locate relevant topics. Minimum System Requirements Microsoft Windows XP SP or Windows GB of RAM. Graphics hardware with MB of memory and support for OpenGL.0 or later. GB of free hard disc space Installing PipeIQLT PipeIQLT is supplied on a mass storage device with each FAAST LT unit, or it can be accessed as a download from www. systemsensoreurope.com. To install from the mass storage device Insert and view the removable storage device. Click on PipeIQLT Setup: Do NOT interchange the devices and do NOT alter the rotary address switch settings on the sensors. If replacing a sensor, ensure that the address set on the new sensor is the same as on the sensor being replaced. LASER SAFETY INFORMATION The detector contains a Class laser product. Radiation emitted inside the smoke sensor is completely contained within its housings and protective covers during all phases of operation. USB CONNECTION PC connectivity is provided by an on board USB B socket located centrally between the filter and the sensor (see Figure displayed earlier in the guide). The USB interface allows access to a range of additional options, via the PipeIQLT application software, when connected to a PC. The USB connecting cable should be removed during normal operation. Click OK and follow the instructions (see: PipeIQLT Setup and Installation Wizard section below). To install from the website Click on the link to PipeIQLT at www.systemsensoreurope.com. Click on PipeIQLT download. The download security warning will appear. Select Save, then click OK. When the download completes, click Run to display the above dialog box. Click OK and follow the instructions (see: PipeIQLT Setup and Installation Wizard section below). PipeIQLT Setup and Installation Wizard When the below dialog box appears, click Setup to start the wizard: D00-0-00 I--0

Quitting Exiting the program closes the application completely. To quit the PipeIQLT application, click X in the upper-right corner of the window. Or click Exit from the File menu. PipeIQLT can be uninstalled from the computer in the normal way for your operating system. Click Next and follow the on-screen instructions. Unless changed, the install wizard will create and store files at the following locations: When installation is complete, the wizard will automatically create a shortcut icon on the PC desktop. It will be necessary to re-boot the PC in order to run PipeIQLT. Launching To launch the PipeIQLT application, double click the PipeIQLT icon on the desktop. Or click Start (bottom left corner of the Windows screen) and then select PipeIQLT from the programs list. When the application opens, it is possible to start a new project, or to monitor or modify an existing project. Use the File menu to select New or Open. Choose from the Pipe Design, Configuration or Monitoring tabs to enter the required mode. Set the detector to Maintenance mode. To communicate with a FAAST LT detector, connect the USB port to a PC with an appropriate cable. 0 FL0E: 0-CPD-0 FL0E: 0-CPD- FL0E: 0-CPD- EN-0 : 00 Class A B & C Aspirating Smoke Detectors Pittway Tecnologica S.r.l. Via Caboto /, Trieste, Italy D00-0-00 0 I--0 Pittway Tecnologica S.r.l. Via Caboto /, TRIESTE, Italy