TYPE APPROVAL CERTIFICATE Certificate No: TAA00001CD This is to certify: That the Programmable Controller with type designation(s) SIPLUS Series Issued to Siemens AG Fürth, Germany is found to comply with DNV GL rules for classification Ships, offshore units, and high speed and light craft Application : Product(s) approved by this certificate is/are accepted for installation on all vessels classed by DNV GL. Temperature B / D* Humidity B Vibration A EMC A* / B* Enclosure Enclosure Required protection according to DNV Rules shall be provided upon installation on board * see Application/Limitation Issued at Hamburg on 2017-11-15 This Certificate is valid until 2022-11-14. DNV GL local station: Augsburg for DNV GL Approval Engineer: Heinz Scheffler Joannis Papanuskas Head of Section This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid. The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed. Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 1 of 6 DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Product description SIPLUS S7-1200 CPU 1212C 6AG1 212- CPU 1214C 6AG1 214- CPU 1215C 6AG1 215- SM 1221 6AG1 221- SM 1222 6AG1 222- SM 1223 6AG1 223- SM 1231 6AG1 231- SM 1232 6AG1 232- SM 1234 6AG1 234- SB - Signal boards SB 1221 6AG1 221- SB 1222 6AG1 222- SB 1223 6AG1 223- SB 1231 6AG1 231- SB 1232 6AG1 232- CM - Communication Modules CB/CM 1241 6AG1 241- CM 1242 6AG1 242-5 CM 1243 6AG1 243-5 CSM 1277 6AG1 277- Power supply modules PM 1207 6AG1 332- SIPLUS S7-1200-F CPU 1214FC 6AG1 214-1AF40-5XB0 CPU 1214FC 6AG1 214-1HF40-5XB0 SIPLUS ET200MP IM - Interface Modules IM 155 6AG1 155- SIPLUS S7-1500 PM Load Power Supplies PM 6AG1 332- PM 6AG1 333- PS System Power Supplies PS 6AG1 505- PS 6AG1 507- Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 2 of 6
CPU 1511 6AG1511-... CPU 1513 6AG1513-... CPU 1516 6AG1516-... CPU 1518 6AG1518-... SM 521 6AG1521-... SM 522 6AG1522-... SM 531 6AG1531-... SM 532 6AG1532-... CM - Communication Modules CM 540 6AG1540-... CM 541 6AG1541-... CM 542 6AG1542-... TM Technology Modules TM 550 6AG1550-... TM 551 6AG1551-... SIPLUS S7-1500-F CPU 1518F 6AG1518-4FP00-4AB0 SIPLUS ET200SP IM - Interface Modules IM 155 6AG1 155- CPU 1510 6AG1 510- CPU 1512 6AG1 512- SM DI 6AG1 131- SM DO 6AG1 132- SM AI 6AG1 134- SM AO 6AG1 135- CM - Communication Modules CM 137 6AG1 137- CM 545 6AG1 545- TM Technology Modules TM 138 6AG1 138- BU/ BA Base units/ Bus adapter/ Server modules BU/ BA 6AG1 193- Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 3 of 6
SIPLUS ET200SP-F SM F-DI 6AG1136-6BA00-2CA0 SM F-DQ 6AG1136-6DB00-2CA0 SM F-RQ 6AG1136-6RA00-2BF0 PM - Power Modules PM F-PM-E 6AG1136-6PA00-2BC0 SIPLUS HMI SIPLUS Key Panel KP8 PN SIPLUS Basic Panel KTP400 Basic KTP700 Basic DP KTP700 Basic KTP900 Basic KTP1200 Basic DP KTP1200 Basic SIPLUS Comfort Panel KP/ TP700 KP/ TP900 KP/ TP1200 KP/ KTP400 KP/ KTP400 KP/ TP700 KP/ TP900 KP/ TP1200 SIPLUS Outdoor Panel TP700 Comfort Outdoor TP1500 Comfort Outdoor SIPLUS Power Supplies SIPLUS PS PSU 200M 5A 6AG1333-3BA10-7AA0 PSU 100S 6AG1334-2BA20-4AA0 PSU 200M 10A 6AG1334-3BA10-7AA0 PSU 300S 10A 6AG1434-2BA10-7AA0 PSU 300S 20A 6AG1436-2BA10-7AA0 PSU 8200 6AG1437-3BA10-7AA0 PSE 200U 3A 6AG1961-2BA31-7AA0 PSE 200U 10A 6AG1961-2BA41-7AA0 PS MODULAR 6AG1961-3BA01-7AA0 PS E202U 6AG1961-3BA21-4AX0 PS E202U 6AG1961-3BA21-7AX0 Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 4 of 6
Approval conditions The Type Approval covers hardware listed under Product description. When the hardware is used in applications to be classed by DNV, documentation for the actual application is to be submitted for approval by the manufacturer of the application system in each case. Reference is made to DNV Rules for Ships Pt.4 Ch.9 Control and Monitoring Systems. Product certificate Each delivery of the application system is to be certified according to Pt.4 Ch.9 Sec.1. The certification test is to be performed at the manufacturer of the application system according to an approved test program before the system is shipped to the yard. After the certification the clause for application software control will be put into force. Clause for application software control All changes in software are to be recorded as long as the system is in use on board. The records of all changes are to be forwarded to DNV for evaluation and approval. Major changes in the software are to be approved before being installed in the computer. Application/Limitation * Temperatur D: SIPLUS S7-1200, TP700 Comfort Outdoor; TP1500 Comfort Outdoor. * EMC Surge Immunity: External Protective circuits required for DC systems. See the current System Manual for recommendations. * EMC B: System SIPLUS S7-1200, SIPLUS S7-1500, SIPLUS ET200SP/MP, SIPLUS HMI, SIPLUS Power Supplies for use on bridge and deck zone, the power supply lines are to be protected by filter type B84113C (manufacturer by Epcos or equivalent) Tested with: I=3A, C=2x0,47uF+2x4700pF, L=4x4,7mH. Enclosure class C: SIPLUS Outdoor Panel (when mounted) front IP66 and rear IP20 Type Approval documentation Test reports: List of Test Reoprts 18-E007698-BM-A01 Documents: List of Technical datasheets/equipment manuals 18-E007698-BM-B01 Tests carried out Applicable tests according to Class Guideline DNVGL-CG-0339, November 2016. Marking of product The products to be marked with: Model name Manufacturer name Serial number Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 5 of 6
Periodical assessment The scope of the periodical assessment is to verify that the conditions stipulated for the type are complied with, and that no alterations are made to the product design or choice of systems, software versions, components and/or materials. The main elements of the assessment are: Ensure that type approved documentation is available Inspection of factory samples, selected at random from the production line (where practicable) Review of production and inspection routines, including test records from product sample tests and control routines Ensuring that systems, software versions, components and/or materials used comply with type approved documents and/or referenced system, software, component and material specifications Review of possible changes in design of systems, software versions, components, materials and/or performance, and make sure that such changes do not affect the type approval given Ensuring traceability between manufacturer s product type marking and the type approval certificate Periodical assessment is to be performed after 2 years and after 3.5 years. A renewal assessment will be performed at renewal of the certificate. END OF CERTIFICATE Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 6 of 6