August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

Similar documents
PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

PIP ELIMTD00 Motor Installation Details for Class I, Division 1 Areas (Motors 600 Volts and Below, 60 hp Maximum)

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED

PIP PCTPA001 Testing of Process Analyzer Systems

MODULAR INTEGRATION OF PROCESS EQUIPMENT PACKAGES FOR OIL AND GAS FACILITIES

First Revision No. 1-NFPA [ Chapter 2 ]

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

AS/NZS :2008

PIP PNE00004 Steam Trap Guidelines

Numerical Standards Listing

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

Numerical Standards Listing

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Australian/New Zealand Standard

Numerical Standards Listing

Overview of Hazardous Locations as They Relate to Solenoid Valves

INTERNATIONAL STANDARD

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

ELECTRICAL SAFETY Information Bulletin

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals

Smoke detection in hazardous areas:

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Public Input No. 3-NFPA [ Chapter 2 ]

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

ELECTRICAL SAFETY Information Bulletin

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

BP OIL -- TOLEDO REFINERY

Fire Alarm System Accessories

Meeting NFPA standards for

ORDINANCE NO

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Meeting the Requirements of NFPA 820:

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

HOT WORK SAFETY PROGRAM:

ELECTRICAL SAFETY Information Bulletin


AS/NZS :2014. Electrical equipment for coal mines Introduction, inspection and maintenance AS/NZS :2014. Part 1: For hazardous areas

ARTICLE 25. FUEL GAS CODE

DUST EXPLOSION CODES AND STANDARDS: Ensuring Regional Compliance and Global Consistency

Fire and Gas Detection and Mitigation Systems

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

An Urgent Bulletin from CSA Group

Cross Reference Table for Area Classification Details

Understanding Hazardous Locations Concepts

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Introduction to Hazardous Electrical Location Classifications

Plant Processing and Extraction Facilities

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements

Pre-First Draft Meeting Technical Committee on Wastewater Treatment Plants On line/conference Call November 20, PM EDT

AREA CLASSIFICATION AND ELECTRICAL EQUIPMENT SPACING FOR NORTH AMERICAN APPLICATION

Dust Explosions. health & environmental sciences failure analysis & prevention

Report on Proposals June 2013 NFPA 70


Part I Extraction Process Equipment


INTRODUCTION TO DUSTS AND THEIR EXPLOSIVE PROPERTIES

EtherCAT Box Modules (EPxxxx-xxxx)

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

ISA 18.2 WG8. Purpose Definitions Status. By: Lieven Dubois, Co-chair

Compliance Guidance for non-technical managers

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

Why AC800M High Integrity is used in Burner Management System Applications?

NEC 2017 Changes and Their Effect Upon the ICT Industry

Fire protection in hazardous locations:

Drive Technology \ Drive Automation \ System Integration \ Services * _0817* Inquiry Forms for Explosion-Proof Gearmotors

CONSULTING Training Courses

AS AS Australian Standard. Industrial fuel-fired appliances. This is a free 9 page sample. Access the full version online.

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

***** 2. Rev.1 is to be uniformly implemented by IACS Members from 1 July 2004.

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

H gh-p led Combust ble Storage. Application Guide 2009 Edition

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

Fire Alarm System Accessories

Electrical Hazards and NFPA-70E: Protecting Your Employees

ATEX, NOMENCLATURE AND CODING

Is your current safety system compliant to today's safety standard?

INTERNATIONAL STANDARD

AGENDA. NEC Code-Making Panel 14. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA

SEMICONDUCTOR FABRICATION FACILITIES

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016. Part 3: Installation site

TECHNICAL SPECIFICATION

SECTION SECURITY TESTING AND COMMISSIONING

INTERNATIONAL STANDARD

THE USE OF COMBUSTIBLE GAS DETECTION IN HAZARDOUS LOCATIONS

NCS/SAS IAS/PES Chapter Seminar January 25-27, Hazardous Locations. OBIEC Consulting George Morlidge Fluor Canada

Electrical Safety Requirements

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529

Transcription:

Electrical Engineering Guide for Determining Electrical Area Classification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time by the responsible Function Team and will be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn. Information on whether this Practice has been revised may be found at www.pip.org. (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. PIP will not consider requests for interpretations (inquiries) for this Practice. Not printed with State funds

Electrical Engineering Guide for Determining Electrical Area Classification Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1 Codes and Standards... 2 2.2 Technical Reference Material... 3 3. Definitions...3 4. General...3 4.1 Selection of Project-Specific Reference Materials... 4 4.2 Data Requirements... 5 4.3 Materials and Properties... 5 4.4 Release Sources... 5 5. Class I Materials...6 6. Class II Materials...7 7. Classification Alternatives... 7 7.1 General... 7 7.2 Pressurization... 7 7.3 Equipment Location... 8 7.4 Vapor Tight Walls and Barriers... 8 7.5 Ventilation... 8 7.6 Gas Detection... 8 7.7 Dust Source Control... 9 8. Unclassified Locations... 9 9. Documentation... 9 Appendix 1 Class I Hazardous Area Assessment Process... 14 Appendix 2 Class II Hazardous Area Assessment Process... 17 Page 1 of 18

Engineering Guide for Determining Electrical Area Classification August 2002 1. Introduction 1.1 Purpose This Process Industry Practice (Practice) provides a work process for applying industry codes and standards to determine electrical area classification. 1.2 Scope 2. References This Practice provides an engineering work process for gathering the necessary information and applying the applicable codes and standards to develop a welldocumented area classification. It addresses the classification of areas containing flammable liquids, gases, or vapors and combustible dust, but does not address ignitable fibers and flyings. This Practice applies to petroleum and chemical process facilities and other related industries that fall within the scope of the standards being used for the assessment of the area classification. This Practice is not a stand-alone document for determining area classification. It should be used with petroleum and chemical industry codes and standards that define the basis for area classification. This Practice may be used for new or existing facilities. Applicable requirements in the latest edition (or the edition indicated) of the following industry codes and standards shall be considered an integral part of this Practice. Short titles will be used herein when appropriate. 2.1 Codes and Standards American Petroleum Institute (API) API RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2 API RP 505 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, Zone 1, and Zone 2 The Instrumentation, Systems, and Automation Society (ISA) ISA-12.10 Area Classification in Hazardous (Classified) Dust Locations ANSI/ISA-12.01.01 Definitions and Information Pertaining to Electrical Instruments in Hazardous (Classified) Locations ANSI/ISA-TR12.24.01 (IEC 60079-10 Mod) Recommended Practice for Classification of Locations for Electrical Installations Classified as Class I, Zone 0, Zone 1, or Zone 2 Page 2 of 18

Engineering Guide for Determining Electrical Area Classification National Fire Protection Association (NFPA) NFPA 30 Flammable and Combustible Liquids Code NFPA 45 Standard on Fire Protection for Laboratories Using Chemicals NFPA 70 National Electrical Code (NEC) NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment NFPA 497 Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas NFPA 499 Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas 2.2 Technical Reference Material 3. Definitions Bishop, D.N., D.M. Jagger, and J.E. Propst, New Area Classification Guidelines, IEEE Industry Applications Society Magazine, Vol. 6, Issue 1, Jan-Feb 2000. PCIC 98-2. Propst, J.E., Volatility and Mists Area Classifications Important Variables, IEEE Industry Applications Society Transactions, Vol. 36, Issue 2, March-April 2000. PCIC 98-25. Comment: For more inclusive listings of codes, guides, and standards pertaining to area classification, see API RP 500, Section 2; API RP 505, Section 2; NFPA 497, Appendix C; NFPA 499, Chapter 4; ISA--TR12.24.01, Section 1.2; and ISA-12.01.01, Annex B. For definitions pertaining to area classification refer to API RP 500, Section 3; API RP 505, Section 3; NFPA 497, Sections 1-3; NFPA 499, Sections 1-3; ISA-TR12.24.01, Section 2; and ISA- 12.01.01, Section 3. 4. General Area classification for electrical installations should be performed by a team of people who are knowledgeable of governing codes and standards. They should also be familiar with applicable process equipment, operations and maintenance; electrical safety procedures; and electrical installation requirements for classified areas. This work process, along with the associated worksheets, should be used to define the basis for area classification, determine the electrical area classification, and create the documentation. Section 5 of this Practice provides additional, specific guidance for area classification procedures pertaining to areas containing flammable or combustible liquids or gases (Class I materials). Page 3 of 18

Engineering Guide for Determining Electrical Area Classification August 2002 Section 6 of this Practice provides additional, specific guidance for area classification procedures pertaining to areas containing combustible dusts (Class II materials). Figure 1 in this Practice is a process flowchart that displays the major activities associated with the assessment of locations with Class I or Class II materials for area classification. 4.1 Selection of Project-Specific Reference Materials See Figure 1 Item 1, Assemble Data References and Government Regulations. The first step in performing an area classification is to determine whether zones or divisions will be used and the selection of the appropriate reference standards for the project. New Area Classification Guidelines, IEEE Industry Applications Society Magazine, provides additional background on the development of API RP 500 and API RP 505 and the criteria for the selection of either the division or the zone method of classification. Comment: The NEC prohibits the overlap of the two classification methods in a facility. For existing facilities that were classified using the division method, there is little incentive for reclassifying unless major revisions are planned. For new facilities or stand-alone units in which there is no overlap, the use of the zone method recognizes additional methods of protection. Table 1 lists the suggested industry standards for assessing area classification: Method of Classification Type of Installation* Class I, Division Class I, Zone Class II, Division All ISA-TR12.24.01 NFPA 499 Petroleum Facilities (including Refineries) Chemical Process Areas API RP 500 API RP 505 NFPA 499 NFPA 497** NFPA 497** NFPA 499 Table 1 Suggested Industry Standards for Assessing Area Classification * In addition, the classification of laboratories using chemicals may fall under the guidance of NFPA 45. ** For large, high-pressure plants, the API recommendations are more suitable (refer to NFPA 497-1997, Para. 3-6.4). Page 4 of 18

Engineering Guide for Determining Electrical Area Classification 4.2 Data Requirements See Figure 1 Item 2, List All Material Properties Class I, II, and III Materials. The next task in the work process is to obtain pertinent information, e.g., process descriptions, process flow diagrams (PFDs), material balance sheets (MBSs), piping and instrumentation diagrams (P&IDs), Material Safety Data Sheets (MSDSs), equipment lists, and an up-to-date plot plan for all locations to be considered for area classification. The plot plan should indicate the location of major process equipment, roads, and all below-grade locations. Any existing electrical area classification drawings and supporting documentation should be obtained. Review the areas adjacent to the project to determine possible sources of leaks that could impact the area classification within the scope of work area. An actual walk-through of the area is highly recommended. 4.3 Materials and Properties See Figure 1 Item 2, List all Material Properties Class I, II, and III Materials and Item 3, Determine Class and Group. Using process data, list all Class I and Class II flammable/combustible materials for the area under study on Form No. 1. For Class I materials, fill in the material properties, such as flash point, ignition temperature, T-Codes, lower flammable limit (LFL), and vapor density. For Class II materials, fill in the material properties, such as layered or cloud ignition temperature and particle density. When there are variations in the properties of flammable materials, note the reference source on the form. NFPA 497-1997, Appendix B, provides one example for dealing with mixtures of materials. For gas mixtures containing hydrogen sulfide, reference API RP 500 or API RP 505, as appropriate. Using the appropriate references and standards, determine and enter the class and group of the materials on Form No. 1. 4.4 Release Sources See Figure 1 Item 4, Locate All Hazardous Material Release Sources. Review all potential flammable and combustible material release sources. On the PFD, P&ID, and/or plot plan, mark those sources that the team agrees need to be considered for area classification purposes. The API and NFPA standards provide a limited amount of guidance on the selection of appropriate sources for the purpose of area classification. However, as noted in Volatility and Mists Electrical Area Classification s Important Variables, IEEE Industry Applications Society Transactions, Within the petrochemical industry there is significant controversy and disagreement on what should and should not be considered a source of release when developing area classification recommendations probably more than on any other aspect of the task. While API RP 500 and NFPA 497 do not provide quantitative guidance on the identification of potential sources, API RP 505 provides additional guidance on the relationship between the grade of release and the zone classification in Section 6.5.8 Page 5 of 18

Engineering Guide for Determining Electrical Area Classification August 2002 5. Class I Materials and Table 2. Table 2 indicates that a continuous grade of release has a flammable mixture present 1,000 or more hours per year, a primary release has a flammable mixture present between 10 hours and 1,000 hours per year, and a secondary release has a flammable mixture present less than 10 hours per year. API RP 505 goes on to indicate that while there are no firm relationships relating the time that flammable mixture occurs in zones, many use the rule-of-thumb shown in Table 3. Table 3 in API RP 505 shows the typical relationship between zone classification and the presence of flammable material and indicates Zone 0 as having flammable mixtures present 1,000 hours or more per year (> 10%), Zone 1 as having flammable mixtures present 10 hours to 1,000 hours per year (0.1% to 10%), Zone 2 as having flammable mixtures present 1 hour to 10 hours per year (0.01% to 0.1%), and unclassified as having flammable mixtures present less than 1 hour per year (0.01%). With today s environmental regulations and restrictions and the impact that it has had on process equipment design, criteria used in the past for selecting potential sources may need to be reviewed and updated for each facility. Additional factors such as maintenance practices, monitoring, response facilities, and past experience with similar process facilities may influence the selection of potential release sources. Potential Class I release sources are discussed in API RP 500, Appendix D and API RP 505, Appendix D. Other documents and company practices may also be applicable. Review the PFD and P&ID documents and identify possible flammable and combustible material release sources. Mark those sources that need to be considered for area classification purposes on the appropriate physical plan drawings and tabulate them on Form No. 2. From the information on Form No. 2 and the reference codes and standards, determine and indicate the extent of the divisions (or zones, as applicable) on the appropriate physical plan drawings. Comment: Minimizing the extent of the classified area may lower the initial electrical equipment and installation costs, but certainly safety should not be reduced. However, it is prudent to evaluate the grouping of overlapping or near-by areas into a single, readily defined classified area. It may be cost-effective to lump multiple-point sources within close proximity into one classified area if conduit versus cable is used to reduce the number of sealing fittings required at area classification boundary crossings. Also, the area classification of future project additions and modifications in adjacent areas might require the upgrade of the electrical equipment and installations. It may also be prudent to extend the classified area to coincide with other easily identified boundaries or equipment. For example, it may clarify the extent of the classified area for a particular facility by extending the area to the edge of unit paving or adjacent roadway boundaries. Page 6 of 18

Engineering Guide for Determining Electrical Area Classification Review the plan drawings and determine if physical items such as barriers, dikes, sumps, and elevation changes may influence the extent of the division or zone. Refer to Section 7 of this Practice for methods of reducing area classification. Appendix 1 of this Practice provides a process for evaluating individual point sources for Class I hazardous area assessment. This process is, in general, based on a process displayed in Figure C.2 in ISA-TR12.24.01. The process has been modified to address both divisions and zones and has also been modified to address the requirement for transition zones as described in API RP 500 and API RP 505. 6. Class II Materials NFPA 499 provides guidance in the classification of areas where combustible dusts are produced, processed, or handled, and where dust released into the atmosphere or accumulated on surfaces could easily be ignited by electrical systems or equipment. Review the PFD and P&ID documents and identify possible combustible dust release sources. Mark those sources that need to be considered for area classification purposes on the appropriate physical plan drawings. Indicate the extent of the boundaries on the appropriate physical plan drawings using the guidelines of NFPA 499. Evaluate the plan drawings and determine if physical items such as barriers may influence the extent of the division classification. Refer to Section 7 of this Practice for methods of reducing area classification. Appendix 2 of this Practice provides a process for evaluating individual point sources for Class II hazardous area assessment. This process is based on the criteria for evaluating areas described in NFPA 499. 7. Classification Alternatives See Figure 1, Item 25, Evaluate Class I Classification Alternatives. 7.1 General It is prudent to consider alternatives for reducing classified areas to improve safety, operability, and maintainability. 7.2 Pressurization Pressurization is a method for reducing area classification within enclosures, rooms, or buildings in Class I and Class II locations. Refer to NFPA 496 for details. Page 7 of 18