Submittal Transmittal Standard St. Joe's - Sonntag Pavillion St. Joseph s Hospital 350 W. Thomas Road Phoenix, AZ 85013 Project # 5690A Tel: Fax: Kitchell Contractors Inc of AZ Date: 9/16/2011 Reference Number: 0140 To: Jarom Prows Comfort Systems USA SW 6875 W Galveston St Chandler, AZ 85226-2516 Tel: (480) 961-7241 Fax: (480) 961-7201 From: David Brown Kitchell Contractors Inc of AZ 1707 E Highland Ave, Suite 190 Phoenix, AZ 85016 Tel: (602) 222-5300 Fax: (602) 798-5750 Transmitted For Delivered Via Tracking Number Action Email Submittal Package No Qty Description Due Date Package Action 0001-23 73 13-1 1 Packaged Air Handling Unit Closed Items Qty Description Item Action 1 1 Packaged Air Handling Unit Closed Cc: Company Name Contact Name Copies Remarks Apprived as noted, Please order ASAP. Signature Signed Date Prolog Manager Printed on: 9/16/2011 KCI_Production_Standardized Page 1 of 1
Ensure coil connections and access doors are oriented as shown on the construction documents. 10822-00 X 0001-237313-1 Digitally signed by Da vid Brown Date: 2011.09.06 09: 18:05-07'00' Brian Spotts t 9/14/2011
Submittal Review RFI Project #: 5690A #### Submittal #: 0001-237313-1 Date: 09/06/2011 9:17:13 AM Submittal Name : Packaged Air Handling Unit X Reviewed and Approved Resubmitted as Noted Not in Compliance with Drawings and Specifications These documents have been reviewed and approved for general conformance with the Contract Documents. The approval is not to be construed as direction from the Contractor to the Subcontractor to deviate from the requirements of the Contract Documents. By : Dave Brown
Material List VFD shipped loose for wall mounting. EXCLUSIONS: Face and bypass dampers, valves, controls RE-SUBMITTAL COMMENTS: WARNING: AIR HANDLER DIMENSIONS HAVE CHANGED.
Catalog 550-5 Vision Air Handler Sizes 003 to 090 MEA 342-99-E
The Vision Air Handler Advantage Operating Efficiency Vision unique design Low air-leakage cabinet design, all inside and outside panel penetrations are sealed Patented gasketed frame channels Energy recovery (plate heat exchanger or energy recovery wheel) Fan selection options (housed forward curve or airfoil, belt drive or direct drive plenum, inline and twin fans) Patented UltraSeal TM low-leak dampers Double wall liners with injected foam insulation Easy, Low Cost Installation Vision unique design Ships assembled or by section Complete disassembly Patented section splicing Extended coil connections with gasketed airseal, external drains and vents Bolted frame construction with removable panels Fan system factory tested and balanced What it can do for you Increases operating efficiency; reduces energy loss and operating costs. Minimizes direct exposure of metal to metal in cabinet framework to reduce cold bridging and condensate collection; lowers operating costs. Reduces cost of heating or cooling outside air; recovers up to 50% of the energy normally exhausted from a building. Results in lowest possible BHP requirements. Maximizes operating efficiency; reduces operating cost. R-13 insulation value reduces condensation and improves operating efficiency. What it can do for you Minimizes install time, reduces installation cost; allows passage through doors, tight spaces and in elevators (ideal for retrofit jobs). Allows for complete knock down during installation if required for tight fit applications. Saves installation time; creates an airtight environment. Eliminates need to remove panels for connection during installation; preserves air-tight environment; saves time and cost. Provides complete accessibility to unit components. Saves time during installation and promotes proper operation. Discharge or inlet plenum sections Easy Maintenance and Serviceability Vision unique design Easy-to-remove access panels in a wide range of section depths Removable cross-member frame channels Extended fan bearing lube lines Extended coil drain connections Hinged access doors with full-grip handles Adapts easily to ductwork and provides a turning section for stacked components. What it can do for you Makes it fast and easy to clean and inspect drain pan, clean or remove coil, clean interior. Allows for top or side coil removal without disrupting unit integrity. Makes lubricating fan system easier. Reduces coil venting time; helps coil condensate drain completely. Allows for proper inspection. McQuay Cat 550-5 5
Introduction Introduction Quality McQuay air handling equipment has been respected and regarded as high quality for nearly 60 years. McQuay has taken a major step in redefining the indoor air handler with the Vision air handler. Demands for improved indoor air quality, low sound, high operating efficiency and smaller mechanical rooms require a better product for today s air handler market. The McQuay Vision air handler is designed to meet or exceed these demands. The key to providing such a high quality product is in the basic design. The McQuay Vision air handler's patented construction provides unequaled thermal efficiencies and low leak rates. In addition, Vision air handlers offer tremendous flexibility in sizing, component options, and unit arrangements to meet the indoor air quality, operating efficiency, sound and installation requirements for today s extensive commercial and custom markets. Flexibility By virtue of its unique frame design, the McQuay Vision air handler offers tremendous flexibility. This flexibility is reflected in our unique Variable Dimensioning feature that allows units to be sized in two-inch increments (height and width) to fit the available space. Numerous section and component options, and the ability to arrange components in whatever arrangement is required, allow Vision air handlers to be customized to the requirements of each job, without expensive field modifications. Finally, Vision air handlers can be shipped as a completely assembled unit, in modules or by component sections for new or retrofit applications that require smaller sections for passage through the building. Cabinet Construction McQuay Vision air handler cabinetry consists of a box-type frame channel the backbone of the unit and easy-to-remove panels or hinged access doors. The unique, patented frame channel design allows three identical pieces to be bolted together to form a corner of the unit. Channel material is G90 unpainted galvanized steel (optional painted G60 galvanized steel) with neoprene gasketing on all flanges to minimize leakage. Gasketing is also factory applied at all contact surfaces between interior and exterior metal components to minimize thermal bridging. See Figure 2. Panels are secured to the unit with fasteners that can be easily removed to access the unit interior. The frame channel and panels are easily disassembled and reassembled, giving contractors tremendous flexibility in installing and servicing the units even where space is limited saving time and money. Patented splice joints (Figure 3) help guide sections together for a tight fit, saving additional time and money on installation. Splice joints are also fully insulated at the factory. Figure 2: Patented Gasketed Frame Channel This unique cabinet design results in air tight, thermally efficient units, which translates into energy savings over the life of the unit. Vision air handlers are capable of leakage rates less than 0.5 cfm per square foot of cabinetry at -7.5" to +6.25" positive w.c. Units will not sweat when exposed to interior air temperatures down to 50 F, and exterior room conditions up to 70% relative humidity. Vision air handler panels use the latest technology to provide the lowest deflection, lightest weight and most importantly, the most thermally efficient 2-inch thick panel system available. R-13 insulation quality injected-foam is thermally pressed between inner and outer liners yielding an extremely rigid panel. The inner liner comes standard with galvanized steel or optional stainless steel. The outer liner standard is galvanized steel with options of pre-painted, or pre-painted heavy-gauge, galvanized steel. Base rails are provided as an option on unit sizes through 21 square feet and are standard on larger units. They are available to meet jobsite height requirements, ranging from 4" to 12" and can eliminate the need for a housekeeping pad saving time and money on installation. A full perimeter base rail per shipping section is factory assembled. Figure 3: Patented Splice Joint for Section-to-Section Joining 6 McQuay Cat 550-5
Vision Unique Standard Features Vision Unique Standard Features Patented UltraSeal Low-Leak Dampers Help maximize operating efficiency Reduces operating cost Extended Coil Connections Reduces installation costs Reduces maintenance time Aids proper drainage Grommet seal reduces leakage Rugged Cabinet Enclosure Rigid, thermal efficient (R-13) injected-foam panels are strong and lightweight Promotes longer unit life Smooth Interior Surface Reduces dirt accumulation Facilitates cleaning Helps improve IAQ Gasketed Frame Channel Eliminates metal-to-metal contact between paneling and framework Minimizes cabinet condensate and corrosion Facilitates top and side component removal Promotes long life 8 McQuay Cat 550-5
Vision Unique Standard Features Custom-Modular design Allows custom selection and configuration of components Allows design of system to meet space and performance requirements Frame Channel Disassembly Allows two-sided access. Easier, faster service and maintenance Patented Splice Collar Reduces installation cost Creates an airtight environment Visible Double-Sloped Drain Pan Makes inspection and cleaning easier Helps improves IAQ Variable Height Base Rails (4" to 12") Eliminates costly housekeeping pad Allows for condensate trapping McQuay Cat 550-5 9
Vision Customized Options 2-7. ) 4-6 7 4 - : 0 ) 7 5 6 - + 1-4 * -, - 4 " ) / 7 ) 4. 1 6-4 9 0 - - - - 4 / ; 4 - + 8-4 ;. * 2, ) 2-4 0 4 1 1 6-4 ) 0 - ) 6 1 / ) 4 / - + 1 ) + + - 5 5 + / 0 6 / + * 1 ) 6 1 0 4 1 6 ) + 1. + ).. ) 6 9 1. ) 5 7 2 2 ;. ), 1.. 7 5-4 0 4 1 + 1 * 9 6 0 4 7 ) + + - 5 5 + ) 4 6 4 1, / -. 1 6-4 ) 6 6-7 ) 6 4 2-7, 15 + 0 ) 4 / - 2-7 ' 1. + ).. ) 6 9 1. ) 1-6 2-7 ". ) 6 2 ) 6-4 9. ) 6 + 7 * - 1 6 - / 4 ) 5 6 - ) ), " 4 9 9 ) 6-4 -, 17 + / + / 4 9 2-7. ) 4 0 6 / * ) / ) 14. 9 5-5 1. ) 1: * : 9 16 0 ". 1 6-4 + ) 4 6 4 1, / - - : 6-4 ) 5 ) " 4 9-5 1. ) 7 6 1 - + 1 5 - + 6 1 5 1: 1 / * : 1: * : 9 16 0. 1 6-4 1: * : 9 16 0 ) /. 1 6-4 * ) / 4 1/ 0 6 ) / - 5. ) + 1. ) + 1. * 2. ) ), 8-4 6 1+ ) + 1, - + 0 4!, - + 0 4, - + 8-4 6!, - + 8-4 6 Energy Recovery Equipment Sound Attenuators Marine Lights and Accessories McQuay Cat 550-5 11
VISION AIR HANDLING UNIT TECHNICAL DATA Date Saved : August 25 2011 QUOTE ID REP. OFFICE Climatec, Inc. JOB NAME St Joseph AHU SALESPERSON Bryan Nelson MODEL NUMBER CAH014GDDC ENGINEER Affiliated UNIT TAGGING AH-1 VERSION 9.43 Unit configuration Inline horizontal Drive (handing) location Right SUPPLY RETURN / EXHAUST Air volume 6480 s cfm Altitude 1100 ft Turning loss 0.00 in WC. External static 1.50 in WC. Total static 2.78 in WC. External H x W 42 x 74 (Not including base rails) ins Outer panel Liner Insulation Frame Base Sound baffles Tread Plate floor liner Shrink wrapping CASING DETAILS Standard G90 galv steel (unpainted) Galvanized steel (Unless noted per section) R-13 Injected Foam (Unless noted per section) 2 ins 6" formed channel None (Unless noted per section) None (unless noted per section) No 1 MIXING BOX(28 ins) SECTION 1 Drip pan None Drip side - Floor grating No OUTSIDE AIR RETURN AIR Length x Width 20.00 x 70.00 20.00 x 70.00 ins Location End Top Dampers UltraSeal Low Leak UltraSeal Low Leak Actuation - - Rated cfm 6480 6480 cfm Air pressure drop 0.07 in WC Quantity 1 1 FILTER DATA Type Pleated Clean air press. drop 0.29 ins WC Efficiency MERV 8 Mean air press. drop 0.64 ins WC Face velocity 383 fpm Dirty air press. drop 1.00 ins WC Face area 16.9 ft2 Access Side Air volume 6480 cfm BANK ARRANGEMENT No. of filters Size H x W x D 3.0 24 x 24 x 2 ins 3.0 12 x 24 x 2 DOOR DATA Door location Drive side Window size None Door width 24 ins Light None Door opening Outward SPECIAL Extra filters 1 set(s) Intersept Antimicrobial treatment Tread Plate floor liner None Liner (As casing details) Insulation (As casing details) (AH-1) McQuay International, www.mcquay.com Page 1 of 3
VISION AIR HANDLING UNIT TECHNICAL DATA Date Saved : August 25 2011 1 MIXING BOX(28 ins) SECTION 1 Sound baffles None Special static pressure - ins WC Filter Gauge None 2 CHILLED WATER COIL(34 ins) SECTION 2 Coil model 5WL1105B Number of coils 1 Total capacity 289538 Btu/h Number of rows 5 Sensible capacity 236506 Btu/h Fins per inch 11 Air volume 6480 cfm Entering db/wb 90.2 / 68.6 F Entering water 44.0 F Leaving db/wb 55.4 / 54.1 F Leaving water 54.2 F Finned height x length 33 x 61 ins Water flow rate 56.80 gpm Face area 13.98 ft2 Water pressure drop 7.20 fthd Face velocity 464 ft/m Water velocity 3.70 ft/s Coil air pressure drop 0.55 ins WC Fluid volume 10.0 gal Fluid weight 85.00 lb Connection type Threaded Fin material Aluminum (.0075) Connection Qty x size 2 x 2.50 ins Tube material Copper (.020) Connection location Drive side Header material Copper Connection material Carbon steel Case material Galv. steel Glycol type (%) - (0 %) Drain pan Stainless steel Fouling Factor 0 Drain pan side Drive side Turbospirals No Coil code 5WL1105B Electro-fin coat None DOOR DATA Door location Drive side Window size None Door width 18 ins Light None Door opening Outward 3 SUPPLY FAN SECTION(34 ins) SECTION 3 Air volume 6480 cfm Motor power 7.5 HP External static pressure 1.50 ins WC Motor type ODP Total static pressure 2.78 ins WC Frame size 213 T frame Cabinet static pressure 0 ins WC Electrical supply 460/60/3 Type Centrifugal - Plenum Motor efficiency Premium Blade type/class Airfoil / 2 Motor speed 1750 rpm Quantity of Fans 1 Block-off Plate No Fan wheel diameter 18.25 ins Motor pole 4 Brake horsepower 4.94 HP Full load current 9.7 A Operating/Max speed 2426 / 2930 rpm Lock rotor current 80 A Orientation Axial Motor supplier Generic Air modulation None Actual drive serv. fac. 1.57 Drip pan None Bearing type Extended - L50 (400K) Drip pan side - Outlet velocity 0 ft/m Wheel guard None Inlet screen None Belt guard Provided Outlet screen None Inspection port None Motor location Behind Fan Material type Aluminium Number of blades 9 DRIVES * Fan sheave BK60H Motor sheave BK80H Number of belts 1 Belt BX65 * McQuay reserves the right to provide a different but equivalent drive package. (AH-1) McQuay International, www.mcquay.com Page 2 of 3
VISION AIR HANDLING UNIT TECHNICAL DATA Date Saved : August 25 2011 3 SUPPLY FAN SECTION(34 ins) SECTION 3 ANTI-VIBRATION MOUNTS / SPRINGS Type Spring Seismic restraint With snubbers DOOR DATA Door location Drive side Window size 12 x 12 ins Door width 30 ins Light Marine light kit and switch only Door opening Outward 4 PLENUM SECTION(18 ins) SECTION 4 Drip pan None Drip side - Opening location Top Opening size 14.00 x 70.00 ins Safety grating No Air pressure drop 0.02 ins WC DOOR DATA Panel Location Removable panels Window size None Panel Width 14 ins Light None Panel Opening Outward NOTES Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on ARI Standard 430. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1-2007. The approving authority is responsible for compliance of multi-component building systems. SHIPPING SECTION DETAILS Length (inches) Weight (lb) Section 1 28 425 Section 2 34 774 Section 3 34 862 Section 4 18 229 TOTALS 114.00 (Lower level total) 2290 (Entire unit weight) UNIT SOUND 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated 78 74 72 80 67 62 46 37 Unit discharge 89 85 87 96 90 88 84 76 Unit return 83 80 83 97 81 80 74 73 (AH-1) McQuay International, www.mcquay.com Page 3 of 3
Opening X Y Z W(Width) H(Height) A Damper 0.00 2.00 16.00 70.00 20.00 B Damper 2.00 2.00 48.00 70.00 20.00 C Cold water outlet 32.60-7.00 43.69 2.50ins. MPS - D Cold water inlet 37.85-7.00 13.31 2.50ins. MPS - E Condensate drain conn. 45.00-2.90 9.00 1.25ins. MPS - F Supply outlet 98.00 2.00 48.00 70.00 14.00 Dimensions measured from A B F B C C D E F A D E NOTE: Base 6.00ins deep, Cross members extend 4ins on each side of the unit. VIEW: General Arrangement No Ends DRAWN: August-25-2011 (15:29) JOB NAME: St Joseph AHU UNIT TAGGING: AH-1 MODEL: CAH014GDDC
Opening X Y Z W(Width) H(Height) A Damper 0.00 2.00 16.00 70.00 20.00 B Damper 2.00 2.00 48.00 70.00 20.00 C Cold water outlet 32.60-7.00 43.69 2.50ins. MPS - D Cold water inlet 37.85-7.00 13.31 2.50ins. MPS - E Condensate drain conn. 45.00-2.90 9.00 1.25ins. MPS - F Supply outlet 98.00 2.00 48.00 70.00 14.00 Dimensions measured from B C F A D E NOTE: Base 6.00ins deep, Cross members extend 4ins on each side of the unit. VIEW: Right Side DRAWN: August-25-2011 (15:29) JOB NAME: St Joseph AHU UNIT TAGGING: AH-1 MODEL: CAH014GDDC
Opening X Y Z W(Width) H(Height) A Damper 0.00 2.00 16.00 70.00 20.00 B Damper 2.00 2.00 48.00 70.00 20.00 C Cold water outlet 32.60-7.00 43.69 2.50ins. MPS - D Cold water inlet 37.85-7.00 13.31 2.50ins. MPS - E Condensate drain conn. 45.00-2.90 9.00 1.25ins. MPS - F Supply outlet 98.00 2.00 48.00 70.00 14.00 Dimensions measured from A B F C D E NOTE: Base 6.00ins deep, Cross members extend 4ins on each side of the unit. VIEW: Top DRAWN: August-25-2011 (15:29) JOB NAME: St Joseph AHU UNIT TAGGING: AH-1 MODEL: CAH014GDDC
20 bhp 15 bhp 10 bhp 7.5 bhp 10.0 5 bhp McQUAY INTERNATIONAL FAN SELECTION 9.0 8.5 3000 rpm 2800 rpm 8.0 2600 rpm 7.5 7.0 2400 rpm 6.5 6.0 2200 rpm 5.5 5.0 2000 rpm 4.5 4.0 1800 rpm 3.5 1600 rpm 3.0 VAV System Line 1400 rpm 1200 rpm 1000 rpm 800 rpm 2.5 2.0 1.5 1.0 3 bhp 2 bhp 1.5 bhp 1 bhp 600 rpm 400 rpm 0.5 0.0 8.0 6.0 4.0 2.0 0.0 CFM (IN 1,000's) 18.2" Airfoil Plenum Supply Fan at Standard Conditions Fan speed 2426 rpm Max speed 2930 rpm Efficiency 57.4 % Air volume 6480 cfm Total static 2.90 inswg Brake horsepower 5.2 bhp Minimum CFM 1619 cfm Minimum Fan Speed 946 rpm Unit tagging AH-1 Date August-25-2011 Job name St Joseph AHU Time 15:30 Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on ARI Standard 430. STATIC PRESSURE (IN. OF WATER)