Fan Coil Thermostat. Specification & Installation Instructions TFC54F3Y1. Technical Data

Similar documents
Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

± 3% or better at 40%RH and 23ºC [73ºF] 0.8 mm 2 [18 AWG] minimum

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

Networkable Fan Coil Controller Specification and Installation Instructions

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Humidity Controller Specification and Installation Instructions. Model HRO20

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

Humidity Controller Specification and Installation Instructions. Model HROB20

FMT24-SUPER-2S-FP-PROG-F Owner s manual & Technician Settings. Installation

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

Smart Temp. Model

INSTALLATION & USER MANUAL

ET10 Series Stand-alone LCD Fan Coil Thermostat

T6984 A,D,E Electronic Floating Control Thermostats

Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor)

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

T-32-TS Touchscreen Thermostat. Installation Manual

T7984 A,B,C Electronic Modulating Control Thermostats

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents.

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Please read this manual carefully before installation and use.

ETN-24-SUPER-PROG (US Program - Celsius)

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

MICROFAN B.V. Industriestraat PH Horst P.O. Box AA Horst Developing, manufacturing and marketing of MICROFAN

ERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135

Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0

Networkable VAV Controller Specification and Installation Instructions

Installation Manual for Hot Yoga Studio Electric Radiant Heating

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

T500 Series Non-Programmable Thermostats

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

Temperature Controllers

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

Safety & Installation Instructions

Heat Link. Technical Guide

MULTI-STAGE CHILLER CONTROL

ETAF Series VDC Fan output LCD Fan Coil Thermostat

CEM-24 Series. Owner's Manual - Installation and Operating Instructions

ELECTRONIC COMMUNICATING THERMOSTAT

Pressurized Condensate Return System (PCR)

T170 Thermostat. Installation and Maintenance Manual. 24 VAC/ VAC 3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control

Safety & Installation Instructions

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

Smart Temp. ApolloP/n Installation Manual. Version 1.0

B-40/B-41 Modulating Temperature Controller

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

SAS6000UTK-7 UNIVERSAL THERMOSTAT

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

L. Terminal block Connecting Label:

ELECTRONIC HUMIDISTAT: H270

Comfort System T-21-P Touchscreen Thermostat Installation Manual

OPERATION MANUAL. ComfortSense 3000 Series Model No. L3011C Non-Programmable Thermostat. Table of Contents. L3011C Thermostat

Room thermostats with LCD for wall mounting

Control Equipment PTC PTC. modulating wall thermostat. NEP04/

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

4Up to 40kW per sq. ft. (24 kw per sq. ft.) 4Modulating, ON/OFF or staging 4Standard from 0.5 to 1000 kw, larger loads available

Table of Contents SECTION PAGE

READ AND SAVE THESE INSTRUCTIONS

Installation Instructions

RC-122BZ Two Stage Heat/Cool 2 Stage Heat / 2 Stage Cool Thermostat Installation Instructions

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System

- Data Brochure tekmarnet 4 Thermostat 542e

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

T600MEP-2 Programmable Economizer Thermostat

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

Series Temperature Controller Instruction Sheet

Briza Line. Digital Display Unit (Room Thermostat) Model BLC 13-RS Wall Mounting Cat Model BLC 33-RS Semi Flush Mounting Cat.

Safety & Installation Instructions

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module

Installation Instructions

T6865 Series Large LCD Digital Thermostat 24 VAC 2-pipe fan coil control

TEC210x-2 Series Networked Thermostats

SAS6000UTK-7-WIFI OPERATING INSTRUCTION

VT8300 Series Installation Guide 24 Vac Low Voltage

ETN-24-SUPER-SF Series

8000 Series Programmable & Non-Programmable Thermostats for Heat/Cool Applications

Product Manual SZ1145

Control solutions Biofloor

Direct Steam Injection Humidifier

TER Active Room Temperature Sensor (Controller),

Product Manual SZ1009

ATA11U03. Non-Programmable Heat Pump Thermostat. Installation Manual. 97B0082N06 Revised: 16 September, 2013 FOR INSTALLER AND OWNER ONLY

ETN24-P/PD-FC-SUPER2. Owner's Manual - Installation and Operating Instructions

HEAT HEAT HEAT COOL COOL

XWA11V. Walk-In Temp / Door /Alarm / Light Module

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

Model: Edge-HC. 1 edge-hc

WSK300 Multifunction Wall Control

WARNING Important Safety Information

OPERATION MANUAL. ComfortSense 3000 Series Model No. L3021H Non Programmable Thermostat. Table of Contents. Description. Initial Thermostat Power up

Neptronic Toll Free: TEL: (514) Fax:(514)

Transcription:

Fan Coil Thermostat Features: Selectable pipe or 4 pipe system Selectable control mode Selectable fan speed contact Selectable Fahrenheit or Celsius scale Manual Night Set Back override (programmable) Multi level lockable access menu Lockable Set point Selectable internal or external temperature sensor Selectable proportional control band and dead band Change over by contact or external temperature sensor available Technical Data Outputs Contact rating Triac rating Power supply Power consumption Set point range Display resolution Control accuracy Proportional band External sensor thermistor Electrical connection Operating temperature Storage temperature Relative Humidity triac outputs 3 digital outputs (fan) Resistive load: rated load: 1.0 Amp / 4 Vac/Vdc Inductive load: rated load: 0.3 Amp / 4 Vac/Vdc maximum switching capacity: 30 VA / 4 W 0.3 Amp @ 4 Vac (8 VA) to 6 Vac 50/60Hz 1 VA 10ºC to 35ºC [50ºF to 95ºF] ±0.1ºC [0.ºF] Temperature: ±0.5ºC [0.9ºF] @ ºC [71.6ºF] typical calibrated 0.5 ºC to 5ºC [1 ºC to 10ºF] adjustable Type G, 0ºC [3ºF] = 9.49 kω, 5ºC [77ºF] = 10 kω, 50ºC [1ºF] = 3.893 kω, 0.8 mm [18 AWG] minimum 0ºC to 50ºC [3ºF to 1ºF] -30ºC to 50ºC [-ºF to 1ºF] 5 to 95 % non condensing Degree of protection of housing IP 30 to EN 6059 Weight 80 g. [0.18 lb] Presentation Symbols on display Cooling ON 100% output A: Automatic Heating ON 100% output A: Automatic Fan ON 3 rd speeds activated A: Automatic or ºC: Celsius scale ºF: Fahrenheit scale Menu set-up Lock ON Programming mode (Technician setting) Minimum/Maximum set points Energy saving mode ON Dimensions B D Dimension Imperial (in) Metric (mm) A 3.00 78 B 3.00 78 C 1.00 4 D.36 60 A C /11091 1

Mounting Instructions A B C D E CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. A. Remove the screw (captive) holding the base and the front cover of the thermostat. B. Lift the front cover of the thermostat to separate it from the base. C. Pull wire through the base hole. D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. E. Mount the control module on the base and secure using the screw. Terminal description Terminals Pipe 4 Pipe Fan option 1 spd spd 3spd 1 spd spd 3spd 1 Common (COM) Common 4 Vac (4VAC) 4 Vac 3 Sensor (EXT. TS) Change over temp. sensor or contact External temperature sensor 4 NSB input (NSB. INP) Night set back input 5 Triac output 1 (TO1) Cool/Heat Heat 6 Triac output (TO) Reheat Cool 7 Digital output 1 (DO1) - - High - - High 8 Digital output (DO) - High Medium - High Medium 9 Digital output 3 (DO3) 1 speed Low Low 1 speed Low Low Settings on PC Board JP1 RUN PGM Digital output signal selector Mode selector Temperature sensor JP.1-:4V JP.-3:COM JP Connecting strip COM 4VAC EXT.TS NSB. INP TO1 TO DO1 DO DO3 TB1 Mode Selection (JP1) Jumper (JP1) on RUN: JP1 Thermostat is in Operation Mode. RUN Thermostat must be set in this mode to operate properly. If not locked, set point, control mode and speed fan (Heating PGM & Cooling ON, Cooling only ON or Heating only ON) may be modified by end user. JP1 Jumper (JP1) on PGM: RUN Thermostat is set in Programming Mode. PGM Refer to following section about all settings description Digital output signal selection (JP) JP Jumper (JP) on 4VAC: 4VAC All digital output signal is linked to 4 Vac. JP Jumper (JP) on COM: COM All digital output signal is linked to common.

Programming Mode When in this mode this symbol is Please press on button to advance to the next program function, press on button to return to preceding stage and press on button or to change value. You can leave the programming mode at any time, changed values will be recorded. Step Display Description Values 1 3 4 Internal temperature sensor Calibration: Display switches between ts1 and temperature read by internal temperature sensor. You can adjust the calibration of the sensor by comparison with a known thermometer. For example if thermostat has been installed in an area where temperature is slightly different than the room typical temperature (thermostat place right under the air diffuser). Minimum set point: Display switches between Stp and the minimum set point temperature. MIN symbol is also Please select the desired minimum set point temperature. The minimum value is restricted by the maximum value (step #3) Maximum set point Display switches between Stp and the maximum set point temperature. MAX symbol is also Please select the desired maximum set point temperature. The maximum value is restricted by the minimum value (step #) Locking the set point : Display switches between LOC and Stp. You can lock or unlock the set point adjustment by end user. If locked the lock symbol will appear. (max offset ± 5ºC) Minimum range 10 to 35ºC [50 to 95ºF] Default value: 15ºC [59ºF] Maximum range 10 to 35ºC [50 to 95ºF] Default value: 30ºC [86ºF] 5 6 7 Locking the set point (cont d): Select the desired locked set point temperature; this one should be within the temperature range. Adjust the control mode: Display switches between CtL and Aut. Select which control mode you want to authorize: Automatic, cooling or heating, heating only or cooling only. If you want to authorize this entire mode, choose Automatic mode. Set On/Off function enable or disable: Display switches between OFF and ena. You can enable or disable the Automatic mode adjustment by end user. Default value: Unlocked Set point range: 10 to 35ºC [50 to 95ºF] Default value: ºC [7ºF] Default value: Automatic cooling and heating Default value: Enable 8 Set pipes or 4 pipes: Display switches between Pno and P. Select which number of pipes you want to use: pipes or 4 pipes. If you have selected the 4 pipes, go directly to step #15. Default value: pipe 9 10 11 Change over mode selection: Display switches between COc and nc. Please select mode of change over between contact normally cool or contact normally heat or external sensor. Note: This selection will affect TO1 and/or Ct1 if they are set in change over mode. If normally cool nc is selected, heating mode will be activated upon closing of contact. If normally heat nh is selected, cooling mode will be activated upon closing of contact. If external sensor ts is selected, heating mode will be activated when temperature read by external sensor is above the Change Over Set Point temperature tco, and cooling mode will be activated when temperature read by external sensor is under tco, see step #10. If ts is not selected, go directly to step #1. Change over set point temperature: (If ts has been selected at step #9) Display switches between tco and the change over set point temperature selected. Please select the change over set point temperature. Note: heating mode will be activated when temperature read by external sensor is above the change Over Set Point temperature tco, and cooling mode will be activated when temperature read by external sensor is under tco. Change over temperature sensor Calibration: Display switches between COs and the temperature read by the change over temperature sensor (if connected). You can adjust the calibration of the change over sensor by comparison with a known thermometer. Default value: Normally cool Default value: 4ºC [75ºF] (max offset ± 5ºC) Display: 0ºC [3ºF], resistance will be infinite. 50ºC [1ºF], resistance will be short circuited. 3

Step Display Description Values Set local reheat On/Off or TPM: If you have selected pipe at step #8 1 13 14 15 16 17 18 19 0 1 3 Display switches between LHt and OFF. Select which signal output you want for TO. You can choose OFF (no signal selected), ON heating only, ON heating & fan, PULSE heating only, PULSE heating & fan output. If you select OFF (no local reheat), go directly to step #17. Proportional band for local reheat (TO): Display switches between Pb.L and the value of the local reheat proportional band, heating symbol is also Please select the desired value of local reheat proportional band. Dead band for local reheat (TO): Display switches between db. L and the value of the local reheat dead band, heating symbols are also Please select the desired value of local reheat dead band. Go to step #17. Internal/external temperature sensor selection: If you have selected 4 pipe control mode at step #8 Display switches between ts and in or out. Please select internal or external sensor. If you select internal sensor in, go directly to step #17. External temperature sensor calibration: Display switches between ts and the temperature read by the external temperature sensor (if connected). You can adjust the calibration of the external sensor by comparison with a known thermometer. Proportional band 1 in heating: Display switches between Pb.1 and the value of the 1 st heating proportional band, heating symbol is also Please select the desired value of 1 st heating proportional band. Proportional band 1 in cooling: Display switches between Pb.1 and the value of the 1 st cooling proportional band, cooling symbol is also Please select the desired value of 1 st cooling proportional band. Dead band in heating: Display switches between db.1 and the value of the dead band in heating, heating symbols are also Please select the desired value of dead band in heating. Dead band in cooling: Display switches between db.1 and the value of the dead band in cooling, cooling symbols are also Please select the desired value of dead band in cooling. Set fan speed automatic mode enable or disable: Display switches between FAn and ena. Fan symbol is also You can enable or disable the Automatic mode adjustment by end user. If you selected to disable the automatic mode, go directly to step #3. Time out fan contact: Display switches between Fto and the automatic shutoff delay value (in minutes) when there is no demand. MIN and fan symbols are also Please select the desired value of the automatic shutoff delay. Fan speed contact: Display switches between FAn and SPd and the speed of the fan. Fan symbol is also Select which speed contact you want: speed 1, speed or speed 3. Default value: Off 0.5 to 5.0ºC [1.0 to 10.0ºF] Increment: 0.5ºC [1.0ºF] Default value:.0ºc [4.0ºF] 0.3 to 5.0ºC [0.6 to 10.0ºF] Default value: 0.3ºC [0.6ºF] Default value: Internal temperature sensor (max offset ± 5ºC) Display: 0ºC [3ºF], resistance will be infinite. 50ºC [1ºF], resistance will be short circuited. 0.5 to 5.0ºC [1.0 to 10.0ºF] Increment: 0.5ºC [1.0ºF] Default value:.0ºc [4.0ºF] 0.5 to 5.0ºC [1.0 to 10.0ºF] Increment: 0.5ºC [1.0ºF] Default value:.0ºc [4.0ºF] 0.3 to 5.0ºC [0.6 to 10.0ºF] Default value: 0.3ºC [0.6ºF] 0.3 to 5.0ºC [0.6 to 10.0ºF] Default value: 0.3ºC [0.6ºF] Range: 0 to 15 min. Increment: 1 min. Default value: 0 min. Default value: Enable 4 5 Delay cooling contact (protection for compressor): If you have selected 4 pipe at step #8 Display switches between noc and the value (in minutes) of the delay to activate / reactivate cooling contact. MIN and cooling symbols are also Please select the desired value of the delay cooling contact. Night set back derogation time: Display switches between nsb and the derogation time in minute. MIN and NSB symbol is also Please select the desired derogation time. If you select OFF, the thermostat is off when NSB is activated. If you select OFF, go directly to step #1. Default value: Hi speed (3) Range: 0 to 15 min. Increment: 1 min. Default value: min. Range: OFF or 00 to 180 min. Increment: 15min. Default value: 10 min. 4

Step Display Description Values Heating Set point during Night set back: 6 Display switches between Stp and the value of the heating set point Range: 10 to 35ºC [50 to 95ºF] temperature during night set back. NSB and heating symbols are also Default value: 16ºC [61ºF] Please select the heating set point temperature during night set back. The minimum value is restricted by the maximum value (step #7) Cooling Set point during Night set back: 7 Display switches between Stp and the value of the cooling set point temperature during night set back. NSB and cooling symbols are also Please select the cooling set point temperature during night set back. The maximum value is restricted by the minimum value (step #6) Range: 10 to 35ºC [50 to 95ºF] Default value: 8ºC [8ºF] 5

Operation Mode Step Description Display At powering up, thermostat will light display and activate all LCD segments during seconds. Illuminating the LCD. To illuminate the LCD, you just have to push onto or buttons. LCD will light for 8 seconds. A Temperature display In operation mode, thermostat will automatically display temperature read. To change the scale between ºC and ºF, press on both and for 3 seconds. Set point display and adjustment: B To display the set point, press two times on or Set point will be displayed during 5 seconds. To adjust set point, press on or while the temperature set point is Note: If set point adjustment has been locked, symbol will be Night set back (NSB): When thermostat is in night set back mode, NSB symbol is displayed, so set point for cooling and/or heating are increased as per the setting made in programming mode. C If not locked, night set back can be derogated for a predetermined period by pressing onto any of the 4 buttons. During period of NSB derogation the symbol will flash. If NSB does not flash, the derogation period is finished or the Night set back derogation has been locked in programming mode. Control mode selection : To change the control mode, press on. Control mode will be displayed during 5 seconds. You can choose one of the following: Automatic Cooling or Heating D Cooling and Heating OFF Cooling only Heating only Note: These selections can vary according to the choice made on step #6 & 7. E Fan speed mode selection: To change the fan speed mode, press on You can choose one of the following: Automatic speed Low speed Medium speed High speed. Fan speed mode will be displayed during 5 seconds. Note: These selections can vary according to the choice made on step #1 & #3. Night set back Wiring Terminals Common 1 4 Vac OCCUP.STA 4 Xfo Line voltage Time clock or Terminals Common 4 Vac OCCUP.STA 1 4 Xfo Line voltage Time clock Schematic Xfo Line voltage Time clock 6

Notes: Recycling at end of life At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com. 7