Series SFN Unbraided Flexible Hose Assemblies Series SFB Braided Flexible Hose Assemblies

Similar documents
Technical Data. Outlet Connections (Ref. Figure 2) ISO 7-Rc 3/8 1/2 inch NPT 3/4 inch NPT. Nominal Assembly Lengths Ref. Table A

BROCHURE COMMERCIAL FIRE SPRINKLER CONNECTIONS. Product Submittal A PART OF

I-VICFLEX.AB3. Victaulic VicFlex Style AB3 Sprinkler Fittings for Surface Mount Applications WARNING WARNING INTRODUCTION

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

Model vkfd28b braided flexible sprinkler drops (lpcb approved)

WARNING. Flexible Hose AH2 With AB6 With AB6. AH2-CC With AB6 With AB6

TRUST THE ORIGINAL. SUBMITTAL PACKAGE

esfr dry pendent sprinkler Vk501 (k14.0)

10.85 VicFlex Sprinkler Fittings

Seung-Jin Ind.Co.,Ltd.

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

esfr dry pendent sprinkler Vk502 (k14.0)

Exaggerated for Clarity. Residential Pendent, Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

40.49 V27, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Horizontal Sidewall, Recessed Horizontal Sidewall V2744 QUICK RESPONSE

INSTITUTIONAL QUICK RESPONSE FLUSH HORIZONTAL SIDEWALL SPRINKLER VK412 (K5.6) TECHNICAL DATA

DISCONTINUED PRODUCT. reference publication

DISCONTINUED PRODUCT

SPRINKLER HEAD. Upright, Pendent & Recessed Pendent Sprinklers MODEL: SD1010, SD1015, SD1030, SD1032 DESCRIPTION TECHNICAL SPECIFICATION

40.31 V34, K14.0 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS

standard response dry horizontal sidewall sprinklers

40.15 V34, K8.0 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS

40.43 V38, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Low Flow Adjustable Concealed Pendent V3806 QUICK RESPONSE

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

40.10 V27, K5.6. Standard Spray; Upright, Pendent and Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Automatic Sprinklers

INSTITUTIONAL QUICK RESPONSE FLUSH HORIZONTAL SIDEWALL SPRINKLER VK412 (K5.6) TECHNICAL DATA

UL LISTED. SPRINKLER HEADS IN STOCK: Pendent Upright Horizontal sidewall Concealed. RESPONSE Quick response Standard response

quick response Sprinkler 105a October 25, 2010

Norminal Sprinkler Temperature Rating

TECHNICAL DATA OBSOLETE

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Standard response. elo sprinklers

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

INSTITUTIONAL QUICK RESPONSE/QREC FLUSH PENDENT SPRINKLER VK410 (K5.6) TECHNICAL DATA

Quick response concealed horizontal sidewall sprinkler VK481

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

FLUSH HORIZONTAL SIDEWALL

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

mirage standard response concealed pendent sprinkler vk492 (K5.6)

40.65 V36, K8.0. Dry Type Standard Spray. Horizontal Sidewall. Recessed Horizontal Sidewall

40.19 V34, K115 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS

Model F1FR Series Quick Response Standard Spray

569, 570, 571, 572 Series

569, 570, 571, 572 Series

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Handshower, Hose & Handshower Accessories

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

Model RFC Series Residential Sprinklers Flat Cover Plate, Concealed Pendent Sprinkler. Product Features. Product Description

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

40.61 V36, K8.0 SLEEVE AND SKIRT PLAIN BARREL

40.60 V36, K5.6 SLEEVE AND SKIRT PLAIN BARREL

Additional Bulletins applicable to all F1RES LL Sprinklers Wall Wetting - Bulletin 007 Design and Installation - Bulletin 140

FLEXIBLE CORRUGATED TUBE

40.50 V38, K5.6. Adjustable Concealed Standard Spray Pendent Standard and Quick Response

esfr pendent sprinkler vk510 (k25.2)

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Norminal Sprinkler Temperature Rating

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

Automatic Sprinklers

40.11 V27, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

MODEL: FA003U FA004U FA005P FA006P STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

standard response dry horizontal sidewall sprinklers

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

Installation and Maintenance for FlexValue Cleanroom Ceiling Model

UMA-1020 Light Weight Suspended Ceiling Kit

Gas Station & C Store SECTION CWM Job No

568X, 587X, 588X Series

TECHNICAL DATA. model c-2

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

SuperKlean Washdown Products

40.60 V36, K5.6. Dry Type Standard Spray Pendent, Intermediate Level Pendent & Recessed Pendent

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

Installation Instructions

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

Model F3 Dry Sprinklers

Installation Manual PS-225 & PS-275

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

SPRINKLER HEAD. Vertical Sidewall Sprinkler MODEL: SD2133, SD2121 DESCRIPTION MAXIMUM COVERAGE TECHNICAL SPECIFICATION SPRINKLER OPERATION RATINGS

CMA-440 Light Weight Suspended Ceiling Kit

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

esfr pendent sprinkler vk510 (k25.2)

Transcription:

Series SFN Unbraided Flexible Hose Assemblies Series SFB Braided Flexible Hose Assemblies SprinkFLEX Stainless Steel Sprinkler Fittings connect the branch line to the sprinkler using a flexible stainless steel hose and reducer. The flexible stainless steel hose and fittings are intended for direct connection to the sprinkler and are particularly suited for use in suspended and hard ceiling applications. Each drop assembly comes with one stainless steel flexible hose, one branch line connection nipple, one sprinkler reducing nipple and bracket system. SYSTEM OPTIONS Preassembled, ready to install, unbraided and braided flexible stainless steel hose lengths: 8" (700mm), 40" (000mm), 48" (mm), 59" (500mm), 7" (800mm) " and 4" outlet fittings for connecting sprinkler Preassembled, ready to install mounting bracket SF04BKT and SF048BKTavailable in 4"and 48" long Mounting bracket allows the sprinkler to be located anywhere within the ceiling with reference marks in the center for ease of installation without the need for measuring. Optional factory installed sprinkler head. TECHNICAL DATA Maximum Working Pressure: psi ( kpa) Maximum Ambient Temperature: 00 F (49 C) Connection to Branch Line: inch NPT Minimum Bend Radius of Flexible Stainless Steel Hose: " (76. mm) per UL Listing 8" (0. mm) per FM Approval The flexible stainless steel hose should not be bent within " 64 mm) of the connection nut at both ends. Listings and Approvals: Unbraided models are UL Listed Braided models are FM Approved and UL Listed Project: Address: Contractor: Engineer: Submittal Date: Notes : Notes : PROJECT INFORMATION APPROVAL STAMP q Approved q Approved as noted q Not approved Remarks:

FLEXIBLE HOSE NON BRAIDED: SFN SERIES BELOW Flexible Sprinkler Hose Fittings NO. DESCRIPTION NO. DESCRIPTION Flexible Hose 7 / 8 " ID Nipple Slip Nut 4 / to / 4 Reducer FLEXIBLE HOSE BRAIDED: SFB SERIES BELOW NO. DESCRIPTION NO. DESCRIPTION Flexible Hose 7 / 8 " ID 4 Slip Nut Braid 5 Nipple Ring Collar 6 Reducer / " to / 4 " BRACKET ASSEMBLY: SFO4BKT & SFO48BKT BELOW 4 48" 4 4" NO. DESCRIPTION QTY* NO. DESCRIPTION QTY* 4" or 48" Support Bracket Hex Screw Bracket Legs Assembly 4 Hub A Assembly MATERIAL SPECIFICATION Corrugated Flex Hose: SS04 Seal: EPDM Slip Nut and Nipple: ZincPlated Carbon Steel Braid and Braid Ring: : SS04 Support Bar: G90 Galvanized Steel Clamp and Center Bracket Assembly: ZincPlated Carbon Steel Hex Screw and Wing Bolt: ZincPlated Carbon Steel Optional TemperResistant Screw: ZincPlated Carbon Steel

INSTALLATION INSTRUCTIONS SFO4BKT & SFO48BKT Open Hub Bracket (SFO) Installation of SPRINKFLEX Commercial Ceiling Flexible Sprinker Drop System HOSE MODEL: SFB8, SFB40, SFB48, SFB59, SFB7 Braided SFN8, SFN40, SFN48, SFN59, SFN7 Unbraided BRACKET MODEL: SFO4BKT SFO48BKT Our SprinkFLEX flexible sprinkler hose fitting has limited flexibility and intended to use for direct connection to fire sprinkler in wet systems in accordance with NFPA, D and R. Our SprinkFLEX flexible sprinkler hose fitting can be installed for use in ceilings with grids which meets ASTM C65 and ASTM C66 referenced by IBC, and is approved for use in standard intermediate and heavy duty structural classification. Determine the place where the sprinkler head will be located. The standard bracket SFO4BKT is 4 inches (600mm) long and shall be mounted on the 4 inch (600mm) ceiling grid. The long bracket SFO48BKT is 48 inches long (mm) long and shall be mounted on the 48 inch (mm) ceiling grid. The sprinkler should be located as close as possible to the center of the distance between ceiling grids (if necessary). Slide reducer bracket onto the cross support bar. Loosely attach the reducer bracket and two clamps on the support bar and place clamps onto ceiling grid so that they support bar crosses the location where the sprinkler will be located (if necessary). See Fig. Fig. Fig. Fig. Separate nipple (if necessary) from the flexible hose and attach the nipple onto the branch line. Make sure that the arrow is in the appropriate direction of flow to the sprinkler and to use pipe thread sealant and/or Teflon tape at the connection to the branch line. See Fig.. Attach one end of the flexible hose on to the nipple and tighten the slip nut to hand tight plus / turn (equivalent to 5 ftlbs.) Do not twist the flexible hose. See Fig.. 4 Bend the flexible hose into a curve that locates the sprinkler reducer at the other end of the flexible hose in the area where the sprinkler will be located. The tube arc should not be twisted and arc should be as large and smooth as possible. The minimum bending radius is inch (76. mm) per UL Listing and 8 inch (0mm) per FM Approval. FLEXIBLE HOSES ARE NOT TO BE INSTALLED STRAIGHT (NO BENDS). THE FLEXIBLE STAINLESS STEEL HOSE SHOULD NOT BE BENT WITHIN / INCHES (64 MM) OF THE CONNECTION NUT AT BOTH ENDS.

Insert the sprinkler 5 reducer into bracket, close hub and lock shaft on reducer bracket. Locate the reducer bracket and sprinkler reducer where the sprinkler will be, and loosely tighten the butterfly bolts on the bracket. See Figure 4A. 6Attach the sprinkler to the sprinkler reducer. Put a wrench on the sprinkler reducer to counteract the tightening torque and prevent the flexible hose from twisting. Reference the sprinkler Fig. 4A manufacturer s sprinkler data sheet for appropriate sprinkler tightening torque, sprinkler wrench and other guidance. Fig. 5 WARNING Fig. 4B 7Verify that the sprinkler reducer is seated in the reducer bracket, precisely locate the sprinkler in all three axis in accordance with the sprinkler manufacturer s data sheet. Tighten all butterfly bolts on clamps and bracket. The torque requirements for butterfly bolts are minimum 40 inlb and maximum 50 inlb. See Fig 4B. 8After tightening all the bolts, verify that the sprinkler is properly located in accordance with the manufacturer s instruction. If not, loosen the butterfly bolts and readjust as required. See Fig 5. Read and understand all instructions before attempting to install any SprinkFLEX products. Wear safety glasses, hardhat, and foot protection during installation. These installation instructions are intended for an experienced, trained installer. The user must understand the purpose of these products, common industry standards for safety, and the potential consequences of improper product installation. Failure to follow these installation instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage. Installation for ASTM C65 metal ceiling suspension systems installed in accordance with ASTM C66 standards.

FRICTION LOSS DATA & SPECIFICATIONS MODEL NUMBER INLET SIZE (INCHES) CM OUTLET ORIFICE SIZE (INCHES) CM HOSE ASSEMBLY LENGTH [L] INCHES (mm) MINIMUM BEND RADIUS FM in. (mm) UL in. (mm) MAX NUMBER OF 90 BENDS UL FM (UL) EQUIVALENT LENGTH OF in. DIAMETER SCHEDULE 40 PIPE FT (m) (FM) 5.6 kfactor (FM) 8.0 kfactor UL PSI (KPA) MAX RATED WORKING PRESSURE FM PSI (KPA) INTERNAL DIAMETER (I.D) HOSE SERIES SFB8 4 8.6 (5.7) SFB40 9 (000) 44 4.6 (7.5) SFB48 (.54) / (.7) 47 () 8 (0) (76.) 6 8.5 (8.6) SFB59 59 (500) 76 4.4 (0.4) SFB7 7 (800) 4 78 40.4 (.) (79) (05) SFB8 9 8.8 (5.7) SFB40 9 (000) 54 4.8 (7.6) SFB48 (.54) /4 (.90) 47 () 8 (0) (76.) 55 8.7 (8.7) SFB59 59 (500) 70 4.6 (0.5) SFB7 7 (800) 4 9 40.6 (.4) SFB8 E 0.6 (6.) SFB40 E 9 (000) 6.6 (8.) SFB48 E (.54) / (.7) 47 () 8 (0) 0.5 (9.) SFB59 E 59 (500) 6.4 (.) SFB7 E 7 (800) 4 4.4 (.9) SFB8 E 0.8 (6.) SFB40 E 9 (000) 6.8 (8.) SFB48 E (.54) /4 (.90) 47 () 8 (0) 0.7 (9.4) SFB59 E 59 (500) 6.6 (.) SFB7 E 7 (800) 4 4.6 (.0) SFN8 SFN40 9 (000) 9 SFN48 (.54) / (.7) 47 () (76.) 56 SFN59 59 (500) 59 SFN7 7 (800) 67 SFN8 8 SFN40 9 (000) 54 SFN48 (.54) /4 (.90) 47 () (76.) 6 SFN59 59 (500) 74 SFN7 7 (800) 74 NOTES: * MODEL NUMBERS: THE SFN DESIGNATES SPRINKFLEX UNBRAIDED HOSE SERIES. THE SFB DESIGNATES SPRINKFLEX BRAIDED HOSE SERIES, THE E DESIGNATES ELBOW. * MAX AMBIENT TEMPERATURE RATING ON ALL MODEL NUMBERS ARE 00⁰F (48⁰C ). * EQUIVALENT LENGTHS ARE SHOWN WITH MAXIMUM NUMBER OF 90 DEGREE BENDS AT THE MINIMUM BENDRADIUS PER AGENCY. 45 DEGREE OR 0 DEGREE BENDS EQUAL 90 DEGREE BEND. DIFFERENT VALUES WERE OBTAINED BY FM AND UL DUE TO THE DIFFERENCE IN MINIMUM BEND RADIUS, TESTING PROTOCOL AND CALCULATION METHODS. PLEASE SEE INDIVIDUAL STANDARDS FOR MORE INFORMATION RELATIVE TO FRICTION LOSS (EQUIVALENT LENGTH OF PIPE). * FM EQUIVALENT LENGTH CALCULATION INCLUDES SPRINKLER HEAD FRICTION LOSS. * SEE LISTING(S) APPROVAL AGENCY FOR THE LATEST APPROVAL DETAILS. (79) (79) (79) (05) (05) (05) FP0.8

IMPORTANT INSTALLATION INFORMATION SprinkFLEX products must be installed according to current, applicable National Fire Protection Association (NFPA, D, R, etc.) standards or equivalent standards for wet, dry, or preaction systems. Deviations from these standards or alterations to SprinkFLEX products or sprinklers will void any warrant. In addition, installations must meet provision of the local authority having jurisdiction and local codes, as applicable. For suspended ceiling applications, the ends of the SprinkFLEX Bracket must be installed to the rails of an ASTM C65 ceiling installed in accordance with ASTM C66 standards. SprinkFLEX Stainless Steel Sprinkler Fittings and/ or the SprinkFLEX Bracket must not be intermixed with other manufacturer s products. Refer to the specific product submittal for applications and listing information. These submittals are located on the website at www.sprinkflex.com. Size the piping system to provide the minimum required flow rate for the sprinkler system. Flush the system to remove foreign material. Continue to flush the system until water runs clear. DO NOT install sprinkler system piping through heating ducts. DO NOT connect sprinkler system piping to domestic hot water systems. DO NOT install sprinklers where they will be exposed to temperatures that exceed the maximum ambient temperature rating for the sprinkler. The flexible stainless steel hose should not be bent or fluctuated upanddown or sidetoside when it is pressurized for test. The flexible stainless steel hose should not be bent within inches/64 mm of the connection nut at both ends. Flexible stainless steel hose and fittings have limited flexibility and are intended only to be installed with bends at their respective minimum bend radii. Protect wet piping systems for freezing temperatures. If construction is altered, refer to applicable standards to determine if additional sprinklers are required. The owner is responsible for maintaining the fire protection system in proper operating condition. For minimum maintenance and inspection requirements, refer to NFPA 5 and the NFPA pamphlet that describes the care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. UL Maximum KFactor of Sprinkler to be connected to Sprinkler Reducing Nipple: " outlets: 8.0 4" outlets:. Licensed under one or more of the following U.S and International Patent Pending: #6,,54, #6,9,784, #6,75,8, #7,0,680, #6,488,097 Installation instructions dated /7/8 Rev B