FC700A Fire detection control unit

Similar documents
FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

Synova TM product catalog.

Fire control panels FC726 FC726-XA

FC723 Fire control panel

FC724 Fire control panel

FC722 Fire control panel

Fire control panels FC360

Building Technologies

FC724 Fire control panel

FC722 Fire control panel

FC2020 Fire control panel

Fire control panel detect 3004 plus and accessories

Sinteso TM product catalog.

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

FS20 Fire detection system

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

ZXSe Range Data Sheet

FC2040. Fire control panel. Sinteso. FS20 series, MP6

Advanced FireAlarm Panel 1-4Loop

Fire control panel for modernization

The EN54 Part 2, 4 and 13 Fire System

561-MB256 plus. Intruder alarm control panel. Performance features

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

DBS721, DBS729 Sounder interbase, Sounder beacon interbase

DC1192 Input /Output module

Intelligent addressable fire alarm control panel

SI120 Guarto Easy I. Alarm system. Fire & Security Products

Remote alarm indicator and test combination MK2430

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules

Fire Detection Systems Product Catalogue (Version )

The EN54 Part 2 & 4 Fire System

OOH740, OOHC740 Automatic fire detectors

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Solution F2. Fire Alarm Control Panels one step ahead.

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

System 800 Addressable Fire Detection & Alarm System

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

On the job around the clock 24/7: Fire detection systems

Intelligent Single Loop Fire Alarm Control Panel

IQ8Control C Fire Alarm Panel

FDCW241 Radio gateway Mounting

FIRElux Emergency Lighting

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Installation, Operating and Maintenance Manual

FDCIO223 (ES 45) Transponder

Touch Screen 1 loop Addressable Fire Alarm Panel

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

Wireless Fire & Security Solutions. Fire Product Showcase

1.7. Insulation fault evaluators EDS460/490 EDS461/491

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Sita200plus. 200detectors. Single loop analogue addressable System

Insulation fault evaluator EDS460-DG

Multi-Gas-Controller MGC2

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

Wireless Fire & Security Solutions. Fire Product Showcase

System 57. An advanced World of intelligent gas detection system management

Fire safety products and accessories siemens.com/cerberus

For Complete Fire and Gas Solutions

Intelligent Addressable Fire Alarm System

Conventional & Twin-wire Fire System

Intelligent Security & Fire Ltd

XC10 Extinguishing control panels

CONTROL PANELS. Tech Data Sheet D01688GB1 10/2012 Fire Detection. Control Panels of the FX 3NET (ALC) Fire Detection System

Just as flexible as your plans The Bosch Modular Fire Panel 5000 Series

SUPREMATouch. Modular Fire & Gas Detection System

TECOM SYSTEMS NETWORK MASTER

CODESEC FIRE ALARM SYSTEMS. security technologies

SUPREMATouch. Modular Fire & Gas Detection System

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

FDOOT241-9, FDOOT241-A, FDO241, FDT241

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Excel-EN Conventional Fire Control Panel

Input module, input/output modules

Cerberus FIT conventional system

FT2080 Fire terminal (Touch) Mounting Installation

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PANELS, KEYPADS & MODULES. Take Fire Protection to the Next Level Fire Products from DSC

Certificate of Product Approval

IntesisBox BACnet/IP Server - Notifier ID3000 series

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Modular Fire Panel 5000 Series Just as flexible as your plans

AND ARCHITECT SPECIFICATIONS

INTELLIGENT FIRE ALARM CONTROL PANEL

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

Solution F1. Fire Control Panels the new generation

Output module (230 V)

Consultant Specification AGILE Wireless Fire Detection System

Addressable Fire Alarm Control Panel

Bionics Instrument. Alarm Handling. Gas Alarm Systems

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

FC121-ZA / FC122-ZA / FC123-ZA / FC124-ZA

FT2080 Fire terminal (Touch) Mounting Installation

Transcription:

FC700A Fire detection control unit Synova 4-16 Loop analogue addressable control panel 128 devices per loop (SynoLOOP) and up to 1000 devices per panel Up to 24 collective lines for Synova TM 600 serie detectors can be connected Up to 16 panels, terminals or gateways can be interconnected on a peer-topeer network (C-Bus). Integrated emergency operation feature ensures EN54 compliance even with control panels handling greater than 512 detectors. For use with Synova TM 300 and 600 series detectors Recognition of connected devices via device read in feature. Superior system integrity with isolators integral to every device Distributed intelligence protocol removes the need for shielded cable on the detection loops. Friendly user terminal with soft key guided system operation Additional LED indicators, synoptic panels and floor repeater options 7 integral card slots for additional 4 loop cards, 8 Zone collective card, RS232 card, LON interface, monitored and unmonitored control modules, network gateway, and VdS module. BMS interface option via ISO1745 Protocol Powerful programming features to fit a wide range of applications. 6A / 24V integral PSU with space for up to 27Ah batteries.

System overview Floor repeater panels FT700A-Visualizer, SWE700A software tool LON/Synopticconverter Control in- /output modules LON-Bus Databus Parallel indicators or synoptic/relay Databus Printer output or Control terminal FT700A RS232 LON interface Gateway FG700A Building management system ISO 1745 Protocol Parallel indicators or synoptic/relay C-Bus Databus DBZ AI DM DF OH HI OP addressable up to 16 SynoLOOPs max. 1000 devices Control unit FC700A ABI EB AB CB Alarm devices SynoLINE600 OP HI SynoLINE600-Ex DJ-Ex Ventilation, OH Aircond. system, HI Elevator OP SynoLINE300 DLO DF DM-Ex DLO SB OP DO-Ex HI DT-Ex SynoLINE600 DF-Ex SynoLINE600-Ex DM DBZ collective OP HI Line modules CPU I-Bus Control modules Control module VdS FBF FSK HM Alarm reception centre (Fire department) Fire control installation VdS periphery: - Fire department control panel - Fire department key cabinet -Main fire alarm box DF-Ex DT-Ex DO-Ex SB LON-Bus LON interface RS232 mains Control in- /output modules LON/Synopticconverter Databus Floor repeater panels or Printer output Parallel indicators or synoptic/relay remote access/maintenance (FT700A-Visualizer, SWE700A) Expansion to a complex fire detection system The structure of the C-Bus network permits the connection of several control panels and control terminals. The C-Bus network contains max. 16 stations (user connected). Any arrangements of station types (FC/FT/FG) are possible. SynoLOOP length may be up to 1400m (dependent on cable type). Control terminal FT700A (max. 15) C-Bus-Gateway FG700A (max. 15) C-Bus I-Bus I-Bus CPU CPU Controlmodules Linemodules Linemodules Controlmodules D-Bus D-Bus Control unit FC700A Control unit FC700A (max. 16) Devices (max. 16) Devices 2

Outline Function The FC700A is a modular 4 16 Loop fire alarm control panel for use with Synova TM analogue addressable devices. The FC700A can be self-contained or operate on a network of up to 16 panels, user terminal or BMS gateways. Additional cards can be added to increase integral control functions and indication as well as to monitor up to 24 collective zones. The system can be programmed via an off line, easy to use software tool to provide a powerful distributed system of unparalleled flexibility. Functional Elements Analogue Addressable Detection The control panel can process the signals from all analogue addressable Synova TM 300 and 600 series detectors as well as manual call points, flame detectors and potential free contacts via input modules. All these devices incorporate an integral short circuit isolator giving maximum system integrity. A single cabling fault on a detection loop will not result in the loss of any devices and the fault can be quickly and accurately identified reducing the amount of time spent faultfinding. The system can be programmed to select detector sensitivity and apply intelligent signal evaluation of single and multiple detectors for safe and reliable fire detection. Collective Collective Synova TM 600 devices can be connected to the FC700A using the E3M080 eight zone collective line card. Up to 25 detectors can be connected to each zone. Additional collective detectors can be added via the loop by using the 1192 input / output module (24V supply required). Conventional Synova TM 300 detectors and other 3 rd party conventional detectors may be added to the system using the CB320A input module (24V supply required). Control In-/Outputs Freely programmable monitored and unmonitored in-/outputs are available either on the detection loop using addressable in-/output modules or internally in the panel. Further in-/outputs are available using Lon Bus control modules. Powerful programming options enable individual in-/outputs to be switched according to the application. In-/outputs can also be controlled across the network. System Programming The FC700A incorporates a phenomenal degree of flexibility in its detection and related control functions. A clear windows based software programming tool allows easy adaptation of a system to meet the most complex of applications. Application Ranges Large industrial complexes Shopping centres Large hotels Regional banking centres / Large office complexes Railway stations etc 3

Standard configuration fire control unit FC700A E3C011 Battery charging module B2F020 Converter 115/230VAC -> 29.6V/6A E3G070 Control module universal E3M111 Line module SynoLOOP Z3I470 Cable set B3Q700 Control terminal H23B010 Cover plate 1 7 2 3 8 Z3I1060 Terminal block preassembled unit with 2x20 terminals in two levels Additional card positions 1 module space total 7 module spaces for optional modules 6 module spaces 4 5 3 6 takes 2 module spaces 4

Accessories to FC700A (Options) ➊ Z3B171 Relay module, 1 changeover contact 250VAC/10A for connection to control modules programmable open collector outputs. Enables interfacing between control installations such as fire doors and plant shut down. ➋ Z3I1060 Terminal block, with 2x20 terminals in two levels for connection facility for the peripheral devices. Allows fast insertion of up to two additional cards when used in conjunction with the Z3I050. ➌ Z3I1050 Connection cable 19 conductors, ready-to-use cable with p.c.b holder and 2x10 plug-in-terminals. Allows fast insertion of up to two additional cards when used in conjunction with the Z3I060. ➍ Z1K030 P.c.b holder with integral terminal block for where more than 2 additional cards are required. ➎ E3I020 RS232 module. Level converter with electrical isolation and EMI protection. 2 serial interfaces RS232 e.g. for printer. ➎ E3G060 6 Way programmable monitored output module. 6 x individually programmable 24V 2A monitored outputs. Max 4A total load. E3I040 LON interface, Converter between I-Bus and LON- Bus. Up to 32 LON-Bus devices connectable. Monitored two-wire bus without loop line function. E3L020 16 Way input / output module. 16 x 24V 40mA inputs or outputs. Each way freely programmable. Can be used in conjunction with Z3B171 to provide 250Vac/10A control outputs. E3G050 8 Way programmable relay control module. 3 x 60V 1A free programmable change over contacts. 5 x 60V 1A free programmable normally open contacts. E3M111 4 Loop analogue addressable module. For use with Synova TM 300 & 600 devices. Max 128 devices per loop. Other connections: - 500mA 24V output E3M080 8 Zone collective module. 8 collective stub lines each with up to 25 detectors. ➏ E3H020 C-Bus-Gateway, Connection between C-Bus network and external RS232 compatible equipment. E.g. BMS interface ➐ B3R051 Parallel indicator panel, Option to control terminal FC/FT. Up to 8 x B3R051 per control terminal possible. E3L030 Control module 'VdS', I-Bus module for the connection of VdS peripheral equipment. ➑ Space for batteries 5

Control terminal FC700A Control terminal built into front terminal (also serves as main CPU) 2 1 5 3 7 6 8 4 9 ➊ Large plain text display (LC display, 240x128 pixels) with background illumination and detailed plain text information on all occurring events: Event type, event location, measures texts, operating states etc. Directly indicated operator guidance texts in alarm situations. Context and system state dependent, comfortable operation with soft keys. Access to other system functions via function menus definable via user profile. ➋ Alarm indicator field: In case of alarm, the red writing "ALARM" lights up. ➌ Indicator fields, partly with command keys 4 ergonomically classified message categories: alarm, fault, isolation and information. The main keys are equipped with light emitting diodes, for a concise, guided operation. ➍ Insertable inscription strips in various languages ➎ Key "Acknowledge message" ➏ Key "Reset message" ➐ Key for switching forward alarm messages ➑ Function key pad for numeric inputs (password, direct selection of locations etc.) ➒ Optional key switch to enable operation Options to control terminal Z3S200 for the locking of doors and/or access authorization for operation H26T030 Plexiglas door 6

Technical Data Control unit Mains supply voltage 115/230VAC, +10%/-15%, 50/60Hz Power consumption 40... 220VA Emergency power operating Standard Optional Integral battery space Charging current Charging characteristics Battery Monitoring Mains monitoring 12... 24h Up to 72h Up to 2 x 12V 27Ah sealed lead acid batteries Max. 1.7A (current limited) 16 preset charging characteristics for correct charging of different battery makes Full symmetry monitoring - 1V Difference Battery presence test every 55s Battery load test 3A for 10s every 23hr Manual battery load test via keypad Programmable mains fault warning delay 1 30 minutes Detection Loops Standard panel 4 (Expandable 16) Devices per loop Max. 128 Integral input / outputs Standard panel Remote transmission Alarm Remote transmission Fault 2 x 24V / 2A sounder circuits 7 x 24V / 40mA programmable input / outputs 24V Auxiliary outputs 1 x 630mA (Monitored for failure) Operating temperature 0.+40 C Storage temperature -20.+60 C Humidity Max. 95%, no condensation According to IEC71-3-3 class 3K5 Colour housing RAL 7035 light grey Protection category (IEC 60529) IP40 Approval VdS pending 7

Details for ordering Type Part no Designation Weight Control unit FC700A-1 A5Q00004734 Control unit pre-assembled (includes one 18.000kg E3C011, E3G070 and E3M111) Accessories control unit E3I020 460239 RS232 module 0.100kg E3I040 499310 LON interface 0.178kg E3G050 460255 Control module 'contacts' 0.163kg E3G060 542539 Control module 'monitored' 0.360kg E3H020 546658 C-Bus Gateway 0.424kg E3L020 546645 Control module 'Drivers' 0.153kg E3L030 475 994 Control module 'VdS' 0.352kg E3M111 511531 Line module SynoLOOP 0.241kg E3M080 460268 Line module 'Collective' 0.189kg E3G070 546661 Control Module universal (Already included 0.203kg in the standard version) E3C011 505479 Battery charging module (Already included 0.250kg in the standard version) B3R051 490513 Parallel indicator panel 0.448kg Z3I1050 A5Q00004717 Connection cable 19 conductors with terminal 0.164kg block and p.c.b. holder Z1K030 484231 Terminal block including p.c.b. holder for additional cards 0.051kg Z3I1060 A5Q00004722 Terminal block with 2 x 20 terminals 2.5mm2 0.220kg Z3B171 484383 Relay module 250VAC 10A 0.040kg H23B010 476210 Cover plate for control unit housing (Already 0.331kg included in the standard version) Z3I380 475567 I-Bus connection cable to connect the 0.028kg modules to the mounting section below FCA725 A5Q00004833 Inscription stripes Spanish FCA775 A5Q00004834 Inscription stripes Italian FCA785 A5Q00004835 Inscription stripes polish B3D021 505259 Dual RS232 ITF Box 0.183kg Z3S200 579349 Key switch for operating panel 0.110kg H26T030 570530 Plexiglas door to B3Q700 0.350kg M3C700 A5Q00004798 USB Software dongle for the programming tool SWE700A AX1201 225487 Battery 12V / 27Ah 8.460kg AX1210 475570 Battery 12V / 15Ah 5.680kg Additional power supply H38G310 484930 Housing set including door 12.750kg B2F020 470588 Power supply 115/230VAC -> 29.6VAC 6A 0.770kg Z3I470 484341 Cable set for additional power supply 0.057kg E3C011 505479 Battery charging module 0.250kg AG Alte Landstr. 411 CH-8708 Männedorf Tel. +41 1-922 6111 Fax +41 1-922 6450 www.sibt.com 2004 Copyright by AG Data and design subject to change without notice. Supply subject to availability. Document no. 007829_a_en_-- Manual FC700 Edition 03.2004 Section 1