December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

Similar documents
PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

MAXIMIZING FACILITY PERFORMANCE WITH INNOVATIVE HVAC & IRRIGATION SYSTEMS

A/C Cooling Load calculation and measurement

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Air Conditioning Clinic

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Dehumidification: Energy Efficiency Comparisons

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Humidity Control & Psychrometrics

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

Comfort and health-indoor air quality

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

2. In areas of the world where outdoor temperatures are low enough to drop the interior building temperature below setpoint.

Company Acme HVAC Inc. Customer James Allen Preparer J White Address 3652 Shady LaneAnywhere, Earth Phone

HVAC Psychrometric Analysis to Avoid Moisture Problems

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Air Conditioning Clinic. Psychrometry One of the Fundamental Series TRG-TRC001-EN

Redesign of Bennett Hall HVAC System

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Benefits Offered by Passive Dehumidification Wheel Speed Control

LAZY A/C with KEN GEHRING President Emeritus at Therma-Stor LAZY AC

Managing HVAC in High Performance Buildings

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Trane CDQ Desiccant Dehumidification

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Ambient (ºF) Temperature Rise Above

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.


ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Pharmaceutical Facility Design

Indoor Horticulture HVAC System Evaluation Project

Why Doesn t My HVAC System Work?

CE311 Fall 2016 Mid-Term Exam 1

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Explanation of Cooling and Air Conditioning Terminology for IT Professionals

Dehumidification for Industrial Coating Applications. By: Jay Kranker Munters MCS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

A GUIDE TO PASSING THE HVAC EXAM

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

A GUIDE TO PASSING THE HVAC EXAM COVERS MANUALS J.D. AND N. INT. MECHANICAL CODE INTERNATIONAL FUEL GAS CODE INTERNATIONAL ENERGY CODE BUSINESS

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

DADANCO Technical Paper

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

APPLICATION GUIDE BEAMS

Dehumidification Strategies Application Note

Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Designing Energy Efficient Outdoor Air Systems

Controlling Indoor Humidity in High Performance Homes. Danny Gough, Energy Solutions, LP

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Relative Humidity in Schools Jim Cummings and Chuck Withers

RESNET HERS Rater Sample Test Questions 2

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

Dehumidifying with Dedicated Outdoor Air

Richard Hiles ClimateMaster

100% Outdoor Air Dehumidification Methods

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Energy Use in Refrigeration Systems

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Modular Active. Chilled. Beams

Mechanical Analysis Energy Savings Graph 1 Built-up Roof Graph 2 Green Roof

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Alpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Thermodynamics II Chapter 6 Mixtures & Psychrometry

ENGINEERING. Edition No. 13 October 2002

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

Compressor Confusion: Field Findings on the Role of Supplemental Cooling in a Commercial Indirect Evaporative Air Conditioner

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

FirstEnergy Program Overview

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Enclosure Temperature Control

Transcription:

Humidity Control and Heating and Cooling Applications December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

Today s Discussion Discussion of cooling, heating and dehumidification loads. Importance of zone condition selection on efficiency. Airflow energy impact through HVAC equipment and room. Basic equipment options and energy use. Critical importance of commissioning. 2

ROOM LOADS Lights and Water (and others)

Relative Intensity of Lighting

Relative Intensity of Lighting at Specific Wavelengths

Relative Intensity of Lighting at Specific Wavelengths

Lighting Summary Even with 45-65 watts / sq. ft. the PAR value is less than full noon summer sun. Although plants use a small amount of the light energy in the process of converting water into sugars, starches, and O 2, virtually all lighting energy becomes sensible heat load. Total input (including ballasts or drivers) is important.

Latent loads. Evapotranspiration Evaporation + Plant Transpiration Evaporation highly dependant on irrigation method. Drip Irrigation Low evaporation. Flood or Trough Irrigation Higher rate. Spray Irrigation Extremely high evaporation. As much as 300 Btu/hr for large plant in high light. Perhaps best estimated by (water in) (water out); if known.

Plant Physiology Water Transport

Transpiration

Evaporative Cooling Effect As water evaporates energy is converted. 1060 Btu/lb at typical conditions. Plants also use this effect in the transpiration process to cool themselves. Through conduction and convection this in turn cools the air. Care must be observed if used to offset loads. If plants are just emerging, water use and evaporative cooling effect are small.

Facilities Construction Can vary significantly. Room within room. Structurally insulated panels (or similar). Partitioned room. Open warehouse.

Typical Rooms

Load Details Building Skin Loss/Gain If Applicable Insulated (or uninsulated) walls, floors, and ceilings. Heat loss as ambient temperature decreases. Heat gain as ambient temperature increases. Concrete floors create a heating load. Doors and windows have different losses and gains than the walls. Solar load has major impact if it exists.

Ventilation for Plants Outdoor air exchange may be required to maintain CO 2 levels for plants. Adds (or subtracts) sensible and latent load. Alternative in a Closed (Sealed) Growing Environment is CO 2 supplementation. Rooms may be kept at higher temperature.

Relative Humidity is relative It represents the ratio of moisture in the air relative to when no more can be held in the air. (Saturated) but..

Relative Humidity Relative humidity is relative to temperature! Higher temperature air is able to hold more moisture. Lower temperature hold lesser amounts before saturation. Therefore, RH changes with temperature!

Relative Humidity is Relative Changes in Dew Point Affect Relative Humidity Changes in Dry Bulb Temperature Affect Relative Humidity

Higher Enthalpy (More Energy Rich) Lower Enthalpy (Lower Total Energy) Lines of Constant Enthalpy

Transpiration Rates Lights On Leaf temperature determines the vapor pressure in the leaf. Air temperature and humidity determines the vapor pressure in the air. Vapor Pressure Deficit (VPD) drives transpiration regulated rates are important for plant growth and health.

Transpiration Rates Lights Off Stomata closed as no light is being received. Evapotranspiration continues at a lower rate during lights off. Slowly decreases over 60-90 minutes. Roughly 30% of full light moisture rate when full dark. This latent load can still be relatively high as sensible load is negligible.

VPD at 1.3 kpa (0.39 Hg) at various DB/WB/RH Different operation, but same drive for growth

Larger Equipment/Higher Energy Use Smaller Equipment/Lower Energy Use

Calculation Methods for Latent Load Derivations of Penman-Monteith equation or similar Net Watering Rate given or calculations

Total Loads and Control - HID Design Conditions 3,500 ft 2, 2,000 plants, 63 watts/sq ft. (85% BE), 318 gal/day net water Early Veg 500 CFM Ventilation - Lights On Description Sensible (Btu/hr) Latent (Btu/hr) Lighting and Appliance 852,500 0 Doors 445 0 Ceiling 5,331 0 Walls 4,564 0 Infiltration -320-199 Ventilation -6,510-7,770 Evapotranspiration 0 150,404 Evaporative Cooling Effect -150,404 - Total 705,606 142,435 705,606/(142,435 + 705,606) = 0.83 SHR Compiled using ACCA Manual N Form N1 and ASHRAE Dehumidification Weather Data

Total Loads and Control - LED Design Conditions 3,500 ft 2, 2,000 plants, 25 watts/sq ft. (95% DE), 318 gal/day net water Early Veg 500 CFM Ventilation - Lights On Description Sensible (Btu/hr) Latent (Btu/hr) Lighting and Appliance 314,078 0 Doors 445 0 Ceiling 5,331 0 Walls 4,564 0 Infiltration -320-199 Ventilation -6,510-7,770 Evapotranspiration 0 150,404 Evaporative Cooling Effect -150,404 - Total 167,184 142,435 167,184/(142,435 + 167,184) = 0.54 SHR Compiled using ACCA Manual N Form N1 and ASHRAE Dehumidification Weather Data

Total Loads and Control - HID Design Conditions 3,500 ft 2, 2,000 plants, 63 watts/sq ft. (85% BE),954 gal/day net water Early Flower 500 CFM Ventilation - Lights On Description Sensible (Btu/hr) Latent (Btu/hr) Lighting and Appliance 852,500 0 Doors 445 0 Ceiling 5,331 0 Walls 4,564 0 Infiltration -320-199 Ventilation -6,510-7,770 Evapotranspiration 0 526,414 Evaporative Cooling Effect -526,414 - Total 326,596 518,445 326,596/(326,596 + 518,445) = 0.32 SHR Compiled using ACCA Manual N Form N1 and ASHRAE Dehumidification Weather Data

Total Loads and Control Design Conditions 3,500 ft 2, 2,000 plants, 954 gal/day net water - Flower 500 CFM Ventilation - Lights Off Description Sensible (Btu/hr) Latent (Btu/hr) Lighting and Appliance 1,203 0 Doors 445 0 Ceiling 5,331 0 Walls 4,564 0 Infiltration -320-199 Ventilation -6,510-7,770 Evapotranspiration 0 175,471 Evaporative Cooling Effect -175,471 - Total -170,758 167,502 No cooling required. Dehumidification Only Load. Compiled using ACCA Manual N Form N1 and ASHRAE Dehumidification Weather Data

Lights On

Lights Off

Air conditioner and dehumidifier Lighting Load

Air conditioner and dehumidifier Lighting Load

Reheating

Energy use and control Traditional dehumidifiers heat the air when it may not be needed. Cooling needs to work harder. Some equipment has less than full capacity reheat or electric reheat only. New energy needs to be added. Not considered here. All-in-one environmental control is best practice.

Multiple Units Serving a Space

Multiple Units Serving a Space Partial capacity during maintenance/service. Redundancy possible. Footprint and layout advantages. Enhanced staging capability. Energy efficiency. 38

Control coordination is critical

Economizers Number of hours where OA is possible is variable depending on the location and time of year. More care required for filtering with air economizer. May introduce more spores and pests. Both the temperature and humidity are affected if economizer is used. This must be approached carefully. CO 2 Enhanced grows impractical with OA economizer.

Target 76 Dry Bulb 45% RH Outdoor Air too Humid Outdoor Air Too Warm in Lights On May not be able to properly cool or dehumidify Outdoor Air Too Warm Few Hours in Lights Off Will require more energy to heat or humidify.

IMPACTS OF AIRFLOW Affinity Laws Working for Energy Efficiency 42

Affinity Laws (Fan Laws)

Affinity Laws (Fan Laws)

Affinity Laws (Fan Laws) For example, reduction in the airflow (shaft speed) to ½ of the peak flow rate in a given system results in 1/8 of the peak power at the fan shaft.

Importance of Air Movement Plant Leaf Boundary Layer Water vapor builds at leaf boundary layer. Creates higher relative humidity and vapor pressure at leaf surface. Buildup can happen under canopy. Dicots have most stomata on underside of leaf. 20-30% higher relative humidity under canopy if airflow is too low. Slowly moving canopy is goal

10-tons Capacity (120,000 Btu) 3400 CFM Moisture Removed = (3400 CFM *17 grains per lb) / 1555 = 37.2 lbs Water Removed Sensible Cooling= (3400 CFM *Δ 22 F TD) * 1.08 = 80,784 Btu/h Δ 7.8 Btu/lb Δ 17 grains/lb Δ 22 F

Δ 15.6 Btu/lb 10-tons Capacity (120,000 Btu) 1700 CFM Moisture Removed = (1700 CFM *44 grains per lb) / 1555 = 48.1 lbs Sensible Cooling= (1700 CFM *Δ 34 F TD) * 1.08 = 62,424 Btu/h Δ 44 grains/lb Δ 34 F

COMMISSIONING Critical Steps in Ensuring Success

Commissioning Startup by factory trained technicians who know the equipment. Equipment and facility in operation. Challenge with this application. A project manager with timeline is key. Have operators/facility people available during startup for Owner Training. Have local Service Technicians aligned for PM and ready in case of any issues.

Continuous Commissioning Periodic Maintenance for this type of equipment is key. Complete a Start-up on a yearly basis. Review trends to determine if there is an issue. An ounce of prevention is worth a pound of cure.

Sensor Locations and Central Control 72 /65% 85 /35% 79 /55% 60 /11% 76 /50% 76 /55%

Controls Tuning Tune Changes

Remote Monitoring Remote monitoring. E-mail and SMS alerts. Cloud-based service. Real-time data and logging. Allows a team to review together quickly.

Thank you! Craig Burg Desert Aire, LLC craig@desert-aire.com 55