National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

Similar documents
Circulation Report for SIG-TMS Comments Document # 72

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

TECHNICAL COMMITTEE ON FIRE CODE

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

26 of 128 9/23/2014 9:25 AM

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

NFPA Technical Committee on Fire Tests

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Committee on NFPA 85

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

NFPA 72 Code Changes vs 2013

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

Changes in NFPA

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Please think twice about printing this matrix. You can it, along with your ballot to or

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

Center for Life Safety Education

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

The Technical Committee on Commissioning and Integrated Testing

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement


ANSI/NETA Standards Update

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Report on First Revision June 2014 NFPA 5000

MNEC NFPA 72 WHITE PAPER

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

NFPA Changes

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Fire Alarm System Fundamentals

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

TECHNICAL COMMITTEE ON FIRE CODE

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

FIRE & LIFE SAFTEY STANDARD

Narrative Reports As Regulated by 780 CMR, Section 903.0

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Questions/Comments for Richard Roux from Webinar on 7/11/13

Personal Emergency Response (PERS) Verification and Notification Procedures

Date Issued: December 14, 2017 Revision: 2.1

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

National Fire Protection Association

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

Agenda Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems June 23-24, 2014 La Jolla, CA

First Revision No. 339-NFPA [ Section No. 2.2 ]

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

Transcription:

National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems Kim Shea DATE: March 1, 2011 SUBJECT: NFPA 72 ROP TC FINAL Ballot Results (A2012) The Final Results of the NFPA 72 (SIG-TMS) ROP Letter Ballot are as follows: 29 Members Eligible to Vote 2 (P. Harrod, R. Sheets) 20 Affirmative on All 7 s (J. Brooks, J. Elvove, H. Hurst, D. Kerr, P. Larrimer, J. Moore, J. Scibetta) (on one or more proposals as noted in the attached report) 0 Abstentions (on one or more proposals as noted in the attached report) There are two criteria necessary to pass ballot [(1) affirmative 2 / 3 vote and (2) simple majority]. (1) The number of affirmative votes needed for the proposal/comment to pass is 18. (29 eligible to vote - 2 not returned - 0 abstentions =27 0.66 = 17.82) (2) In all cases, an affirmative vote of at least a simple majority of the total membership eligible to vote is required. This is the calculation for simple majority: [29 eligible 2 = 14.5 = (15)] Reasons for negative votes, etc. from alternate members are not included unless the ballot from the principal member was not received. According to the final ballot results, all ballot items received the necessary 2 / 3 required affirmative votes to pass ballot.

1 72-13a Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 3.3.x (Log # CP902 ) Carter, S. Enclosed please find the Minutes from the ROP Meeting that was held January 19-21, 2011 in San Diego, CA and updated Minutes of the PRE-ROP meeting that was held in September. Both of these have been posted to your Document Information Page. Hurst, Jr., H. Manufacturer's Instructions typically include product specifications and the agency listings. Consideration should be given to the addition of this documentation as part of the definition. 72-17 Eligible To Vote:29 Affirmative: 22 : 5 Abstain: 0 : 2 3.3.xx Deficiency, 10.19, 14.2.1.2, and Chapter 15 (New) (Log # 436a ) Brooks, J. I disagree with the new definitions regarding critical and non critical deficiencies. What is critical and non critical really depends upon the emergency that may happen. What may seem to be non critical may become a critical item depending on the location and type of emergency that may occur. Elvove, J. I don't support this change, as although all deficiencies must still be corrected, new text will not require an owner to be notified if non-critical deficiencies are observed. In addition, language in 14.2.1.2.3 mixes terminology as impairments and deficiencies are two terms that should not be used interchangeably. Finally, I believe an NFPA-wide definition for deficiency is needed, rather than having every project or committee develop their own. Note: whether or not this proposal is ultimately accepted, I believe SIG-TMS should be responsible for Impairments whether included in Section 10.19 or in a new Chapter 15. Hurst, Jr., H. Disagreement with the definitions proposed for Chapter 3. Larrimer, P. Adding "critical deficiency" adds confusion to Chapter 14. The ITM contractor should not have to try to determine if the deficiency is critical prior to notifying the owner in writing. Previously, all deficiencies that were not corrected were provided to the owner in writing, but this change will only require that "critical" deficiencies be communicated. The existing wording was less confusing for both the owner and the ITM contractor. Deficiencies can be substituted for defects and malfunctions, but all references to "critical" and "non-critical" should be removed. The new definitions are not helpful. Moore, J. There is a need for more comprehensive impairment handling procedures for fire detection and alarm systems. While modern fire alarm systems provide constant feedback concerning faults in the system, that is not a substitute for a comprehensive impairment handling program that deals with the means and methods of limiting the number and duration of impairments, temporary measures that may be instituted when there are system impairments, and procedures for planned impairments to a system required to repair, expand, or otherwise modify the system. The Technical Correlating Committee should provide direction concerning where there comprehensive impairment handling procedures are to be incorporated into the Code.

2 72-28 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 3.3.52 Condition, 3.3.228 Response, and 3.3.240 Signal (Log # 498f ) Hurst, Jr., H. Disagreement with the definitions being proposed. 72-65 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Chapter 4 (Log # 117f ) Brooks, J. I disagree with all the new requirements being added for record keeping. The substantiation given does not justify the increase in the amount of documentation that will be required. This proposal imposes a new cost for even the simplest fire alarm system for a small building with little benefit to the owner. 72-74 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Chapter 8 (Log # 333f ) Brooks, J. I disagree with all the new requirements being added for record keeping. The substantiation given does not justify the increase in the amount of documentation that will be required for even the simplest fire alarm system. 72-80 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.xx (New) (Log # 325 ) 72-81 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.xx (New) (Log # 326 )

3 72-84 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3 (Log # 327 ) 72-85 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3 (Log # 483 ) 72-86 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3 (Log # 516 ) 72-86a Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3 (Log # CP901 ) Carter, S. The "Inspection Personnel" definition seems vague in that id does not specify what kind of competence the person should have. Consider clarifying by answering the question; "What should the person be trained and experienced in?" Scibetta, J. The wording for Inspection and Testing Personnel should be altered. 10.4.3.1 should read: "Inspection personnel shall be performed by personnel who have demonstrated competence through knowledge, training and experience acceptable to the authority having jurisdiction or meet the requirement of 10.4.3.3." Additionally 10.4.3.2 should read: " Testing personnel shall have knowledge, training and experience of the testing requirements for fire alarm and signaling equipment of this code acceptable to the authority having jurisdiction or meet the requirement of 10.4.3.3." Currently, the wording does not require inspectors to demonstrate competence through knowledge nor requires testing personnel to demonstrate competence through training. Knowledge, training and experience are important in the fulfillment of both tasks. 72-87 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3.1 and 10.4.3.2 (Log # 541 )

4 72-88 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 10.4.3.1.xx (New) (Log # 485 ) 72-173 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Chapter 13, 14, and 15 (Log # 482 ) 72-174 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Chapter 14 (Log # 25 ) 72-175 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 14.2.1 (New) (Log # 543 ) Hurst, Jr., H. The proposed annex information is redundant and runs on and on. Elvove, J. The proposal provides a needed discussion regarding the purpose of inspection, testing and maintenance and its limitations, but it still needs some cleaning up during ROC. First, the annex to 14.2.1.1 should include examples of related installation standards (e.g., ASME A17.1, NFPA 90A, NFPA 92, etc.). Second, the paragraph number pertaining to periodic testing needs to be changed to 14.2.1.4. Third, language in Annex A.14.2.1.2 and A.14.2.1.4 pertaining to (emergency control) functions and their respective interfaces needs to be revised as the terms apply to end to end testing and other interfaced systems to be consistent with actions taken by SIG-PRO to better define these terms (See ROP-43). 72-176 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.2.1.2.4 (New) (Log # 87 )

5 72-177 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.2.2.2 (Log # 429 ) 72-178 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.2.2.4 (Log # 323 ) 72-179 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.2.9 and A.14.2.9 (New) (Log # 271 ) 72-180 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.3.1 (Log # 135 ) Carter, S. Several items should also require the "Verify Location and Condition" method for consistency. For item 20 and 21, move the method currently written for 20(a.) and 21(a.). Additional methods should be considered for 20 (b.) (c.) (d.) and 21 (b.) (c.) (d.). Elvove, J. This table has been revised to add visual inspections methods, but methods haven't been provided for every component (i.e., I don't believe defaulting to item 1 is appropriate for all subsequent items). If there is no text at this time, it might be better to use reserved as a place holder. But the table needs to include inspection methods for supervisory signal and waterflow devices, items 11(i) & (j), so to differentiate between an NFPA 72 inspection and an NFPA 25 inspection. I also recommend deleting item 14, interface equipment, since that equipment may not be part of the fire alarm systems (e.g., a fire pump controller or a separate clean agent fire suppression system panel), and thus not be within the scope of a typical NFPA 72 inspection.

6 72-181 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.3.1, Item 15 (Log # 442 ) 72-182 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.3.1, Item 15 (Log # 443 ) 72-183 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.3.1, Table 14.4.2.2, and Table 14.4.5 (Log # 566a ) Carter, S. Area of Refuge Two-Way Communication Equipment does not appear to be incorporated into 72-180 as specified by the committee statement. Elvove, J. Ensure that as part of this Accept in Principle, that proposed revisions to Tables 14.3.1 and Tables 14.4.5 are incorporated into the respective tables that were revised by ROP-180 and ROP-187b. Reeser, M. Second sentence needs to read Systems with 5 or more stations shall be operated... to pick up those systems which only have 5 stations. 72-184 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.1.1.1 (Log # 46 ) 72-185 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.1.2.1 (Log # 47 )

7 72-186 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.1.2.2 (Log # 27 ) 72-187 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 and Table 14.4.5 (Log # 542 ) Elvove, J. See my comment on ROP 187b (CP-900). 72-187a Eligible To Vote:29 Affirmative: 25 : 2 Abstain: 0 : 2 14.4.2.2(14)(j) (Log # 583 ) Hurst, Jr., H. All that should be required is for water flow to activate the switch. If a full trip activates the switch then the alarm bypass valve is not required for switch activation. The switch may be activated through different means required within NFPA 25. Larrimer, P. The water flow switch is a switch just like every other switch. The Code should be consistent. It should read "The switch shall be operated and receipt of the signal shall be verified." The verbiage that is to be deleted should be replaced with NFPA 25 material and placed in the annex to inform the tester/owner of the proper way to test the water flow switch to comply with both NFPA 25 and NFPA 72. NFPA 25 Reads (and this should go in the annex): 5.3.3.3 Testing waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector s test connection. Elvove, J. Text should be revised to simply refer to NFPA 25 for waterflow device testing as NFPA 72 shouldn't dictate how to conduct a test when that test is governed under another standard. In this case, the requirement for testing waterflow devices is covered by NFPA 25. The result of having this requirement is the potential for conducting four water flow tests when only two may be needed, if when testing waterflow devices per NFPA 25, the alarm signal is verified at that time. 72-187b Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2, Table 14.4.5 (Log # CP900 )

8 Carter, S. For a few items where initial/reacceptance is required but partial is not required, the label "N/A" should be added for consistency (ex. Item 4 (c.) (d.) (e.) (f.)) For item 12(d)(3) the periodic frequency should be decided to remove the????? label. For item 12(5) it appears a requirement is repeated. I suggest that items 17(c) and 19 separate the initial/reacceptance methods from the partial methods to be consistent with the manner in which this is done in 17(a) and (b). For item 22(c)(1) and 22(c)(2) the method incorrectly references 8(a) and 8(b) respectively. Elvove, J. The proposal provides a much needed overhaul and consolidation of the testing frequency and methods table, but as one would expect with a major revision, it will need some additional cleaning up during ROC. For example, item 4 could use clarifying information that indicates that ECS equipment includes area of refuge two way communication systems (see ROP-183). Under item 10(e), new text from ROP 72-188 & 189 appears twice. Under item 12(e)(3), no test frequency has been provided. Under item 19, a reference to ASME A17.1 needs to be added since not all installation standards are NFPA standards. In this same section, language needs to be revised and clarified to distinguish between emergency control function operation and activation during acceptance, reacceptance and periodic testing, and also be consistent with terminology developed by SIG-PRO in ROP-43. Hurst, Jr., H. The revised wording of Table 14.4.2.2.3(b) is applicable to an onboard DACT. Testing of telephone line seizure and telephone line fault conditions of stand alone DACT will probably not involve the fire alarm control panel. Verification of trouble signals and resetting will occur on the DACT and not at the fire alarm control panel. No test method listed in Table 14.4.2.2.1(f). Table 14.4.2.2.8 uses the term manufacturer in several paragraphs and specifies a specific manufacturer in others. In some paragraphs, it is unclear what specific manufacturer is implied. 72-188 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item12(e) (Log # 258 ) 72-189 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item12(e) (Log # 273 ) 72-190 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 13(b) (Log # 237 ) 72-191 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(d)(1) (Log # 251 )

9 72-192 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(d)(3) (Log # 142 ) 72-193 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(d)(5) (Log # 252 ) 72-194 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g) (Log # 290 ) 72-195 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(1) (Log # 427 ) 72-196 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(1) (Log # 253 ) 72-197 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(2) (Log # 254 )

10 72-198 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(2) (Log # 275 ) 72-199 Eligible To Vote:29 Affirmative: 25 : 2 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(2) (Log # 291 ) Elvove, J. This proposal should have been accepted as it correctly attempts to clarify that the testing of CO detectors, as it applies to NFPA 72, is limited to the smoke sensing element, and defers the non-fire CO testing requirements to NFPA 720. Larrimer, P. I believe that the proposal clarifies that a "combination" smoke/co alarm is only required to be tested for smoke by the changes proposed. Unlike the item in 14(h) which is a CO detector for fire, the item in 14(g)(2) is governed by both NFPA 72 for smoke/fire and NFPA 720 for CO and the proposal is trying to clarify this. Some might think that the CO part must be tested under NFPA 72, which is not the intent of the code. 72-200 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(5) (Log # 255 ) 72-201 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(g)(6) (Log # 256 ) 72-202 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 14(h) (Log # 257 )

11 72-203 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 15 (Log # 276 ) Scibetta, J. Sound level meters should still be used during periodic testing. While I agree with the proponent's statement that testing audibles during periodic testing should not include ensuring compliance with any particular design, the alarm technician should still ensure that audible signals are clearly heard above the average ambient sound level for a given mode. Such verification assures the building owner that audibles can still be heard, without providing commentary on whether design changes have had an impact. Recommend re-wording of Table 14.4.2.2 Item 15 (a) (2) to read as follows: "Periodic testing shall verify the operation of the notification appliances. Sound pressure levels for signals shall be measured with a sound level meter meeting ANSI S1.4a, Specifications for Sound Level Meters, Type 2 requirements. The sound level meter shall be set in accordance with ANSI S3.41, American National Standard Audible Evacuation Signal, using the time-weighted characteristic F (FAST). Sound pressure levels shall be measured to ensure that audible signals are clearly heard above the average ambient sound level for the given mode(s) outlined in Chapter 18." Additionally, Table 14.4.2.2 15 (b) (2) should read as follows: "Periodic testing shall verify the operation of the notification appliances. Sound pressure levels for signals shall be measured with a sound level meter meeting ANSI S1.4a, Specifications for Sound Level Meters, Type 2 requirements. The sound level meter shall be set in accordance with ANSI S3.41, American National Standard Audible Evacuation Signal, using the time-weighted characteristic F (FAST). Sound pressure levels shall be measured to ensure that audible signals are clearly heard above the average ambient sound level for the given mode(s) outlined in Chapter 18. Audible information shall be verified to be distinguishable and understandable." 72-204 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 15 (Log # 507 ) 72-205 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 15(i) (Log # 139 ) Larrimer, P. The committee states: "The substantiation asserts that sensitivity testing of system smoke detectors will result in "substantial life safety benefits" but does not provide data to quantify this." This is in fact the reason that sensitivity testing should be eliminated since sensitivity testing has not been justified for system detectors nor for smoke alarms. 72-206 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 17(f) (Log # 277 )

12 72-207 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 18(b) (Log # 161 ) Hurst, Jr., H. vote for proposal 72-208. Committee statement referencing proposal 72-208. 72-208 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 18(b) (Log # 444 ) Hurst, Jr., H. The proposed wording of this proposal regarding the fire alarm control panel is only applicable to an onboard DACT configuration. The wording does not support testing of a stand alone DACT. The fire alarm control panel will not necessarily be involved in the testing of a stand alone DACT. 72-209 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 18(f) (New) (Log # 438 ) Hurst, Jr., H. No basis was provided for the 5 minute failure verification. 72-210 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 18(f) (New) (Log # 439 ) Hurst, Jr., H. No basis was provided for the 5 minute failure verification. 72-211 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item19(g) (New) (Log # 440 )

13 Hurst, Jr., H. No basis was provided for the 5 minute failure verification. 72-212 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 21(b), Table 14.4.5 Item 17(b)(2) and A.14.4.8.2 (Log # 278 ) Hurst, Jr., H. 21(b)(3) Change "be done to" to "meet". 72-213 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Table 14.4.2.2 Item 23 (Log # 131 ) Hurst, Jr., H. Currently only three control relays are required for fire alarm/elevator interface (primary recall, secondary recall, and shunt trip). Other elevator functions do not require alarm activation for testing. 72-214 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 23 and A.14.4.2.2 (Log # 274 ) Elvove, J. See my comment on ROP-187b (CP-900). 72-215 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.2.2 Item 26(2) (Log # 136 )

14 72-216 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.3 and 14.4.4 (Log # 44 ) 72-217 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.3 and 14.4.4 (Log # 45 ) 72-218 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.5 Item 24(h) (Log # 441 ) 72-219 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Table 14.4.5.1 Item 1 and 2 (Log # 426 ) 72-220 Eligible To Vote:29 Affirmative: 24 : 3 Abstain: 0 : 2 14.4.5.3 (Log # 8 ) Elvove, J. Once again, the contradiction on sensitivity testing requirements for smoke alarms has been correctly pointed out, and again, the committee maintains the double standard. Either remove the requirement for sensitivity testing smoke alarms (since they will eventually be replaced in 10 years anyway), or shoot the moon and require that all smoke alarms, regardless of location be sensitivity tested, if there's technical substantiation for sensitivity testing smoke alarms. Don't base the requirement on whether or not it's enforceable. Kerr, J. If sensitivity testing is not required in multi-family dwellings, detectors should be replaced after 10 years regardless of manufactures instructions. I agree with the submitter that detectors tend to fail more sensitively and thus create a society that ignores alarms and increase false alarms. False alarms cost tax payers millions of dollars each year in responses buy Fire Departments. Fire Fighters and the public are involved in accidents with injuries and loss of life from fire fighters responding to false alarms.

15 Larrimer, P. NFPA 72, 14.4.5.3 requires sensitivity testing of smoke alarms one year after installation, the 3rd year after installation, and the 8th year after installation at a minimum if all previous sensitivity tests pass. It seems pretty clear that replacing a relatively cheap device would be less expensive than the sensitivity testing and documentation required by 14.4.5.3. Eliminating sensitivity testing for smoke alarms is a good first step. The committee should state why sensitivity testing is necessary for a smoke alarm as I don't believe that any technical justification for such testing that has ever been provided. See also my comment on 72-205 (Log #139). The committee states: "The substantiation asserts that sensitivity testing of system smoke detectors will result in "substantial life safety benefits" but does not provide data to quantify this." This is in fact the reason that sensitivity testing should be eliminated since sensitivity testing has not been justified for system detectors nor for smoke alarms. 72-220b Eligible To Vote:29 Affirmative: 25 : 2 Abstain: 0 : 2 14.4.5.3, Table 14.4.2.2 (Log # CP905 ) Elvove, J. See my comment on ROP-220. Larrimer, P. See my negative comment on 72-220 (Log #8). Sensitivity testing for smoke alarms been never been justified regardless of the location/occupancy in which they are installed. It is not clear that technical justification has ever been provided to the committee to require sensitivity testing for system detectors. If that justification exists, it has yet to be presented to the committee to my knowledge and it doesn't seem to be readily available for review. 72-221 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.5.5.3 (Log # 43 ) 72-222 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.7.1 (Log # 141 ) 72-223 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 14.4.8.1 and A.14.4.8.1 (New) (Log # 289 )

16 Larrimer, P. There is no valid reason to treat single station alarms differently based on where the single station alarms are located. Requirements should be device specific and not based upon the occupancy in which they are located. The VA (and other jurisdictions) have the exact same devices used in the exact same types of structures (with different occupancy classifications) with the same enforcement personnel, but NFPA 72 Chapter 14 provides different testing criteria without substantiating why the criteria is different. This proposal should have been accepted. I believe that the requirement to replace smoke alarms every 10 years came from the household chapter based on the components of the smoke alarm. See NFPA 72-1999, parage 8-3.5 and the Handbook Page 318. Either the devices should be replaced based on the component degradation argument or the requirement to replace them should be removed for all smoke alarm regardless of the location in which they are installed. 72-224 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.9 (Log # 42 ) 72-225 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.4.12.1 (Log # 41 ) 72-226 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.5.1 (New) (Log # 195 ) 72-227 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.5.2 (New) (Log # 196 ) 72-228 Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 14.6.2.4 (Log # 9 )

17 Scibetta, J. The committee response to this proposal should have been "Reject" due to the fact that Committee Proposal 72-230a was accepted, which calls for the elimination of the list in 14.6.2.4. Proposal 72-228 called for an addition to that list. Seeing that the committee has proposed to eliminate the list, this proposal should have been rejected. The Committee action on Committee Proposal 72-229a meets the intent of this proposal. 72-229 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 14.6.2.4 (Log # 88 ) 72-229a Eligible To Vote:29 Affirmative: 26 : 1 Abstain: 0 : 2 Figure 14.6.2.4 through Figure 14.6.2.4(e) (Log # CP904 ) Scibetta, J. This proposal does not fully meet the intent of Proposal 72-229 since there is no allowance for a Date/Time column on the Supplemental pages of the Inspection and Testing form, namely the Initiating Device Supplemental form and the Notification Appliance Supplemental form. There is ample room for re-sizing to allow for a "Date/Time" column on those forms. It was mentioned that recording date and time for each device/appliance would create a burden in certain cases. However, it should be noted that 14.6.2.4 states that the inspection record shall include "all applicable information. If the date/time of each device inspection/test is deemed as non-applicable information, it does not have to be provided. Furthermore, each form states at the beginning that it shall be permitted to modify a given form as needed by the service provider to provide a more clear record. If a service provider feels that providing the date and time of each device inspection or test makes the record less clear, they can modify the form to eliminate the Date/Time column. By placing a Date/Time column in the Initiating Device and Notification Appliance Supplemental forms, NFPA will be presenting a model format for inspection and testing data that service providers can use as a springboard for their own version of the form if necessary. Additionally, the Initiating Device Supplemental Form is incorrect. The form has the correct heading but below the heading it reads, "It includes an interconnected systems test record." The body of the form shows the table from the Interconnected Systems Supplemental Form. Instead, the body of the form should have the same format as the the Notification Appliance Supplemental form, except with appropriate table headings (please refer to original forms submitted by Task Group). Furthermore, the Notification Appliance Supplemental Form should not have an address column. These two forms do not reflect the work of the Task Group that was assigned to this proposal and that was reviewed and accepted by the committee. Carter, S. It appears that perhaps an editorial mistake has been made in Figure 14.6.2.4a such that it is the same as Figure 14.6.2.4c. It appears that Figure 14.6.2.4a should include a table for recording initiating device test results and Figure 14.6.2.4c should be titled "Interconnected Systems". Elvove, J. The ballot includes 12 forms when there should only be 6, because many have been duplicated. Hence, so it's not clear what this proposal is supposed to look like (Figures 14.6.2.4, 14.6.2.4a through e; Forms for System ITM, Initiating Devices, Notification Appliances, ECS, MNS). 72-230 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Figure 14.6.2.4 (Log # 421 )

18 72-230a Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Figure 14.6.2.4 (Log # CP903 ) 72-231 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Figure 14.6.2.4 and A.14.6.2.4 (Log # 506 ) 72-262 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 18.4.10.4, 18.4.10.5 (New) and D.2.4.1 (Log # 505a ) 72-565 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 A.10.4.3.1(2) (Log # 539 ) 72-575 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 A.14.4.2.2 (Log # 531 ) Elvove, J. Be sure to link this proposed new annex note to the applicable section of Table 14.4.2.2 as revised by ROP-187b (Log CP900) pertaining to interface equipment. This proposed new annex could also be tied directly to 14.4.5.4. Moore, J. The term "monitor module" is not defined in the Code and should be changed to "signaling line circuit interface," which is specifically defined in the Code.

19 72-576 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 A.14.4.12.1.3, A.14.4.12.1.4, and A.14.4.12.1.5 (Log # 18 ) 72-577 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Figure A.14.6.2.4 (Log # 420 ) 72-604 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 D.3.4 (New) (Log # 546 ) 72-605 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 D.3.6.1 (Log # 508 ) 72-606 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 D.4.1.2 (Log # 504 ) 72-609 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 Annex G (Log # 489 )

20 72-614 Eligible To Vote:29 Affirmative: 27 : 0 Abstain: 0 : 2 H.1.2.1 (Log # 24c )