DRAWING SCHEDULE NUMBER TITLE M0-1 MECHANICAL NOTES AND LEGEND M1-0 MECHANICAL FLOOR PLAN M4-0 MECHANICAL SCHEDULES M4-1 MECHANICAL LOAD CALCULATIONS M5-0 MECHANICAL DETAILS M8-0 TCS BASYS CONTROLS DRAWINGS AND SEQUENCE OF OPERATION P1-0 PLUMBING PLAN, NOTES, AND LEGEND P1-1 PLUMBING PLAN, RISERS, AND SCHEDULES P5-0 PLUMBING DETAILS F1-0 FIRE SPRINKLER PLAN MPF13-0 MECHANICAL SPECIFICATIONS MPF13-1 MECHANICAL SPECIFICATIONS MPF13-2 MECHANICAL SPECIFICATIONS TYPE OF EQUIPMENT RTU UH, EWH EF or F Ductwork Diffusers DESCRIPTION COMPONENT TAB REQUIREMENTS Rooftop Unit Unit Heater, Electric Wall Heater Exhaust Fan or Fan (any type) TAB REQUIREMENTS BY EQUIPMENT TYPE Entering Air Temp Heater DX Cooling Coil Heating Mode At each branch and/or fitting Airflow at each Diffuser with referenced Mechanical drawing(s) Airflow EAT LAT LAT Supply Air CFM Minimum Outside Air CFM 100% Open Economizer Airflow CFM HP RPM External Static Pressure (+/-) Voltage/Phase Amps LAT HP Voltage/Phase Amps Duct Size Duct CFM Duct Velocity CFM CFM HP External Static Pressure (+/-) RPM Voltage/Phase NOTE: REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS AS RELATED TO TEST AND BALANCE. Fan Electrical Electrical
AIR DISTRIBUTION DEVICE SCHEDULE MARK MANUFACTURER MODEL TYPE NECK SIZE FACE SIZE FRAME FINISH MATERIAL ACCESSORIES (L" X W" OR (L" X W") TYPE DIAMETER") SD-1 (1) (1) PLAQUE FACE 12" 24 X 24 (1) (1) STEEL PFS, DMPR REMARKS RD-1 (2) (2) PLAQUE FACE 12" 24 X 24 (2) (2) STEEL PFS, DMPR TG-1 (3) (3) WALL TRANSFER GRILLE 48 X 12 - (3) (3) STEEL - RG-1 (3) (3) WALL RETURN GRILLE 12 X 12 - (3) (3) STEEL - EG-1 (3) (3) WALL EXHAUST GRILLE 8 X 8 - (3) (3) STEEL - SR-1 (4) (4) DUCT SUPPLY GRILLE 33 X 6 - (4) (4) STEEL DMPR SR-2 (4) (4) DUCT SUPPLY GRILLE 21 X 6 - (4) (4) STEEL DMPR SR-3 (4) (4) DUCT SUPPLY GRILLE 13 X 6 - (4) (4) STEEL DMPR SR-4 (5) (5) DUCT SUPPLY GRILLE 16 X 6 - (5) (5) STEEL DMPR SR-5 (5) (5) DUCT SUPPLY GRILLE 18 X 6 - (5) (5) STEEL DMPR SR-6 (5) (5) DUCT SUPPLY GRILLE 14 X 6 - (5) (5) STEEL DMPR SR-7 (5) (5) DUCT SUPPLY GRILLE 6 X 6 - (5) (5) STEEL DMPR EG-2 (6) (6) EXHAUST GRILLE 8 X 8 - (6) (6) ALUMINUM DMPR ACCESSORIES: REMARKS: PFS-PLASTER FRAME DMPR- DAMPER EXT-LINDAB AIR EXTRACTOR AS-PRICE AIR SCOOP KEY MARK MANUF MODEL FRAME ACCESSORIES FINISH REMARKS NOTE TYPE DAMPER PLASTER FRAME KRUEGER PLQ 23 PRN-100 5HCF23 BRITISH WHITE FOUR WAY BLOW PATTERN (1) SD-1 PRICE SPD 31 VCR-7 AMF B12 TITUS OMNI 3 AG-75 TRM 26 KRUEGER PLQ 23 PRN-100 5HCF23 BRITISH WHITE (2) RD-1 PRICE SPD 31 VCR-7 AMF B12 TITUS OMNI 3 AG-75 TRM 26 KRUEGER S85 SURFACE - - BRITISH WHITE (3) TG-1/RG-1/EG-1 PRICE 535 SURFACE - - B12 TITUS 25RL SURFACE - - 26 (4) (5) SR-1/SR-2/ SR-3 SR-4/SR-5/ SR-6/SR-7 (6) EG-2 LINDAB RGS-3 DUCT EXT - GALVANIZED 'EXT' IS THE AIR EXTRACTOR - - - - - - - - - - - - KRUEGER 880H DUCT OBD - BRITISH WHITE ONLY USE FOR RECTANGULAR DUCTWORK PRICE 520L DUCT D - B12 ONLY USE FOR RECTANGULAR DUCTWORK TITUS 300RL DUCT AG-15-26 ONLY USE FOR RECTANGULAR DUCTWORK - - - - - - - - - - - - TITUS 50F SURFACE AG-15 PFA 26 OPTIONAL CORE; 1/2''x1/2''x1'' FAN SCHEDULE ELECTRICAL OPER MARK MFR MODEL CFM S.P. H.P. VOLT/PH/HZ WT REMARKS (IN W.G.) (WATTS) (LBS) EF-1 LOREN COOK 70 SQN-B 170 0.625 1/4 120/1/60 80 1,2 EF-2 BROAN QTXE150 150 0.100 (51.3) 120/1/60 12 3 REMARKS: 1 PROVIDE WITH FACTORY MOUNTED DISCONNECT SWITCH AND BACKDRAFT DAMPER. 2 EXHAUST FAN TO BE CONTROLLED THRU SCENE 2 CONTROLLER. REFER TO ELECTRICAL DRAWINGS. 3 EF SHALL RUN 24-7 AT CONSTANT SPEED. OUTSIDE AIR REQUIREMENTS ROOM ROOM UNIT GROSS FMC - 2010 FMC - 2010 ZONE ACTUAL PURPOSE CLASSIFICATION SERVED FLOOR AREA OA RATE/ DEFAULT PEOPLE OA RATE/ AIR TOTAL SYSTEM OUTSIDE REMARKS AREA REQUIREMENTS OCCUPANCY REQUIREMENTS DISTRIBUTION OA REQ'D NUMBER AIR (SQ. FT.) (CFM/SF) (CFM) (#/1000 S.F.) (# PEOPLE) (CFM/PER.) (CFM) EFFECTIVENESS (CFM) (CFM) 1.00 DISPLAY AREA SALES RTU-1 178 0.12 21 15 3 7.5 20 0.8 52 RTU-1 450 1.01 SALES AREA#1 SALES RTU-1 1,295 0.12 155 15 19 7.5 146 0.8 376 RTU-2 820 1.02 SALES AREA#2 SALES RTU-2 1,537 0.12 184 15 23 7.5 173 0.8 447 RTU-3 460 1.03 SALES AREA#3 SALES RTU-2 1,251 0.12 150 15 19 7.5 141 0.8 364 1.04 FITTING AREA DRESSING ROOMS RTU-3 522 0.12 63 15 8 7.5 59 0.8 152 1.05 MANAGERS OFFICE OFFICES RTU-3 82 0.06 5 5 2 5.0 10 0.8 19 1.06 STOCKROOM STORAGE ROOM RTU-3 1,834 0.12 220 - - - - 0.8 275 1.07 TOILET #1 TOILET ROOMS - 68 - - - - - - 0.8-1.08 TOILET #2 TOILET ROOMS - 68 - - - - - - 0.8-1.09 JANITORS CLOSET STORAGE ROOM RTU-3 10 0.12 1 - - - - 0.8 2 TOTAL 6,845 TOTAL 1,685 TOTAL 1,730 ELECTRIC UNIT HEATER SCHEDULE HEATING ELECTRICAL MARK MFR MODEL CAPACITY INPUT AMPS VOLT/PH/HZ REMARKS (BTU/HR) KW UH-1 QMARK MUH074 25,600 7.5 9.0 480/3/60 1 REMARKS: 1.) PROVIDE WALL MOUNTED THERMOSTAT AND INTEGRAL DISCONNECT SWITCH. CONTROL DAMPER SCHEDULE UNIT INLET PRIMARY AIR MARK MANUFACTURER MODEL SIZE SIZE MAX MIN REMARKS (CFM) (CFM) CD-1 YOUNG'S REGULATOR 2075-12" 550 140 1,2 REMARKS: 1 FURNISH WITH #T-312-CE THERMOSTAT AND #30-35 TRANSFORMER. 2 PHONE #(440)-232-9700 FOR LOCAL REPRESENTATIVE.
PLUMBING SCHEDULE FIXTURE VALVE/FAUCET CONNECTIONS ELECTRICAL MARK DESCRIPTION MFR MODEL MFR MODEL WASTE VENT CW HW VOLTAGE PHASE REMARKS WATTS WC-1 LAV EWH FCO FD WATER CLOSET AMERICAN CADET - - 4" 2" 3/4" - - - - 1, 10, 11 HANDICAP STANDARD #2467.016, WHITE LAVATORY AMERICAN LUCERNE AMERICAN RELIANT 3 1-1/2" 1-1/2" 1/2" 1/2" - - - 2, 3, 12 STANDARD #0355.012.020 STANDARD #7385.003.002_LH WATER HEATER BOSCH ES4 - - - - 3/4" 3/4" 120 1 1440 4 TANK TRONIC 3000 T 4-GALLON FLOOR CLEAN JAY R. SMITH SERIES 4000 TO - - - - - - - - - 9 OUT SUIT FLOOR FINISH FLOOR DRAIN JAY R. SMITH 2005A-PO5O - - 3" 1-1/2" - - - - - 8 MOP SINK FIAT #MSB-2424 AMERICAN UTILITY 3" 1-1/2" 3/4" 3/4" - - - 5 MS PRODUCTS STANDARD #8354.112.004 ELECTRIC ELKAY EZTL8C - - 1-1/2" 1-1/2" 1/2" - 120 1 325 6 EWC WATER COOLER TWO LEVEL WALL CLEAN JAY R. SMITH 4532S - - - - - - - - - 7 WCO OUT REMARKS: 1 PROVIDE WITH BEMIS MANUFACTURING MODEL 1955SSC STANDARD WHITE OPEN FRONT SEAT LESS COVER. 2 PROVIDE WITH JR SMITH #0700 FLOOR MOUNT LAVATORY CARRIER. 3 PROVIDE WITH TRUEBRO LAV GUARD MODEL #102 FOR TRAP AND SUPPLY PROTECTION. 4 PROVIDE WITH A WATTS PLT-5 2.1 GALLON POTABLE WATER EXPANSION TANK (ET). INSTALL BOTTOM OF HEATER MINIMUM 7'-0" A.F.F.. 5 PROVIDE WITH FIAT PRODUCTS VINYL BUMPERGUARD #E-77-AA. 6 PROVIDE WITH DEARBORN 17GA. TRAP, TRAP ADAPTER AND ANGLE STOP. 7 CAST IRON CLEANOUT TEE WITH STAINLESS STEEL ROUND COVER. PLUG TO BE GAS AND WATER TIGHT. 8 FLOOR DRAIN TO BE PROVIDED WITH TRAP SEAL DEVICE (TS), PROSET TRAP GUARD, SURE SEAL TRAP SEALER OR EQUAL. 9 PROVIDE POLISHED NICKLE BRONZE COVER WITH ZARB-1470-A CLEANOUT PLUG. 10 PRESSURE ASSISTED TANK-TYPE. 11 FURNISH RIGHT HAND AND LEFT HAND MODELS AS REQUIRED PER ADA. 12 PROVIDE WITH MIXING VALVE, AMERICAN STANDARD MODEL #605XTMV1070.