and Channel indicator and monitoring unit B Operating Instructions 2.00/

Similar documents
MO n : 12JMC rév A

CTT8 TEMPERATURE MONITOR DEVICE

Installation Manual Tracker 221

1.7. Insulation fault evaluators EDS460/490 EDS461/491

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

USER MANUAL FOR OPERATING SYSTEM

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

1.7. Insulation fault evaluators EDS460/490 EDS461/491

COMMANDER 150. User Guide Universal Process Indicator A1

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

RS485 MODBUS Module 8AI

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DIGITAL TEMPERATURE RELAY TR-100

User Guide IM/SM3000 EN Rev. L. SM3000 Multipoint Videographic Recorder

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

E21.X.01.6C-05 Operating Manual EB2000 MC page 1. Operating manual EB2000 MC. for up to 9 sensor modules. Version 3.0

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

REMOTE CONTROL FOR CHILLER MYCHILLER

EasyTronic III MANUAL SERVICE

Process & TeMPerATUre UniversAl input DigiTAl MeTers

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

M1000 Alarm Annunciator

HRX Technical Manual. Version 1.2

User Guide. DATUM L150 Panel-Mounted Universal Level Indicator A1. ABB Instrumentation

725B Configuration Software Manual

Info-Display xx

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

User Guide IM/L160_6. Wall-/Pipe-mount Level Indicator L160

M2500 Engine Controller Installation Manual

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

02/11/2015

Insulation fault evaluator EDS460-DG

Manual GPRS Data Logger PCE-GPRS 2

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

Table of Contents SECTION PAGE

/8 DIN Universal Process Indicator

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Product Manual SZ1145

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

CONTENTS SAFETY SYMBOLS... 1 GENERAL WARNINGS... 1 MAIN FEATURES... 2 MAIN FUNCTIONS... 2 USER UNIT... 3

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

Model A1700 Series Annunciator

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

02/11/2015

Standard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve

Product Manual SZ1144

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder

INSTALLATION INSTRUCTIONS

Poolsmart Plus Touchscreen Heating Controller. Installation & Operating Manual

C7 Programmable, digital room thermostat. Operating Instructions

Carbon Monoxide Transmitter

Mark 25 Ultrapure Water Conductivity Analyzer

Micro-VPAC IIT LSC - Lift Station Controller. User Manual. Version 1.0.2

HTC-915-CONT. Heat-Trace Control system

Series Temperature Controller Instruction Sheet

Lift Station Level Controller

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Bacharach Bodyguard 4 User's Guide

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

eed quality electronic design USER s MANUAL

REPEATER FS5200R INSTRUCTION MANUAL

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Series Digital Controller Instruction Sheet

Section 9 System Operation

ST Wiring diagram. Product description. Four-stage controller. Order number

The Information Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Edited by Foxit PDF Editor Copyright (c) by Foxit Software Comp. Programmable digital room thermostat. NEW software! Operating Instructions

INSTALLATION & USER MANUAL

Operating Instructions tico Temperature Indicator

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Remote alarm indicator and test combination MK2430

Siemens RDY2000BN. Start Up Guide

System 57. An advanced World of intelligent gas detection system management

I/A Series 716C 1/16 DIN Temperature Controller

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

CLEANROOM MONITOR CR3A Network - Installation Instructions

Analog Annunciator Unit SACO 16 A3. Product Guide

Danfoss gas detection unit Type GD Heavy Duty

ME 3011C / Alarm Indication / Quick Reference Guide

Quickheat 30 weather compensated boiler control

CONTROL UNIT: REFERENCE MANUAL

P2267 NETWORK INTERFACE

Parameterisable compact fault annunciator with permanent display

Gas Detection System TOX ALARM DG2000-Garage

21-light Remote Annunciator. Owner s Manual

Refrigerated air dryers

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

FieldServer Driver - Serial FS Notifier NCA

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

Transcription:

and Channel indicator and monitoring unit B 70.0202 Operating Instructions 2.00/00375947

Contents 1 Instrument functions... 3 1.1 Ordering details... 3 1.2 Functions of the LMD-96... 4 1.3 Functions of the LMD-400... 5 2 Operation of the LMD-96... 7 2.1 Displays and controls... 7 2.2 Normal display... 7 2.3 Alarm display... 8 2.4 Setting the time... 9 2.5 Entering alarm limits and number of channels... 9 2.6 Installation of a new system... 10 2.6.1 Extension of an installed system... 11 2.6.2 Replacing a faulty analogue input module... 11 3 Operation of the LMD-400... 13 3.1 Displays and controls... 13 3.2 Normal display... 13 3.3 Alarm display... 14 3.4 Alarm print-out... 15 3.5 Report print-out... 15 3.6 Overview of functions... 16 3.7 Setting the time... 16 3.8 Configuring the channels... 17 3.8.1 Factory settings... 17 3.8.2 Altering the module parameters... 18 3.9 Installation of a new system... 19 3.9.1 Extension of an installed system... 20 3.9.2 Replacing a faulty analogue input module... 20 3.10 De-installation... 21 3.11 Configuration... 22 4 Electrical connections... 25 4.1 Connection diagram LMD-96... 25 4.2 Connection diagram LMD-400... 26 2.00/LMD-96/400

1 Instrument functions An LMD monitoring system consists of an LMD as the display/control unit and mtron analogue input modules. It is possible to cover up to 400 channels and monitor them against limit values. The measurements are shown in three red 4-digit, 7-segment displays, 13 mm high. In normal display, the corresponding channel number is indicated next to the measured value of a channel. The 3 or 4 relays and 4 LEDs available in the LMD serve to initiate alarms and signal various system conditions. The cyclic display can be held on any channel. The measurements can then be manually scrolled by operating the up or down keys. The assignment of the analogue input modules to the channel numbers takes place at the installation stage. The outstanding features of the system are the simple commissioning of a complete installation, and the convenient configuration and parameter setting. The three red 4-digit, 7-segment displays and four LEDs give the operator a fast and complete overview of the installation. Data exchange between the modules takes place via the LON bus. 1.1 Ordering details Basic type (1) (2) (3) (4) 7002 02 /. -.. - 23 (1) Basic type Type Code LMD 96/400 02 (2) Basic type extensions Channels Code 96 channels 1 400 channels 2 (3) Outputs Relay and analogue output Code 3 relays in the LMD-96 03 4 relays in the LMD-400 04 (4) Supply Rear Code 110 240V AC +10/-15%, 48 63Hz 23 2.00/LMD-96/400 3

1 Instrument functions 1.2 Functions of the LMD-96 - acquisition and display of 96 channels via 4-channel analogue input modules - monitoring of all channels against two adjustable limit values (alarm and prealarm), as well as for probe break. - alarm generation if set limit values are infringed - display of alarms and signalling via 3 relays and 4 LEDs - acknowledge function - simple installation - three red 4-digit, 7-segment displays, 13mm high - JUMO mtron-itool required for setting the parameters for the measurement inputs 1 24 4-channel analogue input modules LMD-96: 96 channels max. LON 4 2.00/LMD-96/400

1 Instrument functions 1.3 Functions of the LMD-400 - acquisition of 400 channels via 4- and 8-channel analogue input modules - monitoring of limit values with window function - separately adjustable limit values for each channel - acknowledge function - simple installation without additional tools - three red 4-digit, 7-segment displays, 13mm high - printer connection via communication module to report alarm occurrences and their acknowledgement (bus address: 111) - daily journal print-out of all measured values at a specific time - signalling of system conditions via 4 relays and 4 LEDs - linking to SVS-2000 process visualisation software via communication module (bus address: 112) - complete parameter setting of the analogue inputs - masking out of individual channels possible - additional relay output on mtron relay modules possible (bus address: 110) RS232 MODbus LMD-400: 400 channels max. (e.g. 50 x 8 channel analogue input modules) LON 2.00/LMD-96/400 5

1 Instrument functions 6 2.00/LMD-96/400

2 Operation of the LMD-96 2.1 Displays and controls Measured value LED 1 LED 2 LED 3 LED 4 Temperature 1 Channel number Temperature 2 Time Clock Enter key Programming Automatic operation Decrementing Incrementing Normal display Alarm display (immediately on alarm occurrence) Probe break or module failure Upper display measured value (one fixed decimal place) measured value (one fixed decimal place) ---- Middle display channel no. (2-digit, no decimal point) A / P and channel no. A = alarm, P = prealarm channel no. (2-digit, no decimal point) Lower display current time (hh:mm) 2.2 Normal display After switch-on the display will automatically be in scroll mode. The LED in the A key lights up, i.e. the channel number and therefore also the displayed measurement change at 2 second intervals. If the A key is pressed, the instrument changes to manual mode. The LED goes dark and the required channel number can be set with the o and u keys. In both display modes, newly occurring alarms will be displayed immediately. Scroll Scroll-Mode mode Manual Hand-Mode mode (LED (LED on) an) (LED (LED off) aus) 2.00LMD-96/400 7 S

2 Operation of the LMD-96 H H As long as the number of channels contains the value 0 (when a new instrument is switched on), no measurements will be retrieved or displayed. v Section 2.5 Entering alarm limits and number of channels When an installed system is switched on, it takes 20 seconds before valid measurements are available. During this time, the first two displays will be switched off. 2.3 Alarm display The desired alarm functions are activated by entering a limit value in place of the not programmed entry ( ---- ). v Section 2.5 Entering alarm limits and number of channels All measurements are cyclically retrieved in turn and compared with the set limit values in the LMD-96. If an infringement is detected, the corresponding alarm is generated. If an alarm occurs, it is displayed immediately. However, in the background, measurements are still cyclically retrieved and compared with limit values. Further alarms are stored. As well as the alarm displays described above, the system conditions are displayed via 3 relays and 4 LEDs. The 3 relays operate as break contacts (negative logic). Basic position Prealarm Alarm Probe break Relay 1 active inactive active active Relay 2 active active inactive active Relay 3 active active toggle operation, whenever active unacknowledged alarms are waiting LED 1 off on off off LED 2 off off on off LED 3 off off flashes, whenever unacknowledged off alarms are waiting LED 4 off off off on A genuine alarm must always be acknowledged by E, before relay K3 returns to the basic position. This is also the case if the alarm condition clears before it is acknowledged. The relays, and consequently the LEDs K1 and K2, are only in the alarm condition for as long as the alarm or prealarm is actually present. LED K4 indicates a probe break or bus interruption. 8 2.00/LMD-96/400

2.4 Setting the time 2 Operation of the LMD-96 The time can be set in either manual or scroll mode. Input of the time can be ended at any time by pressing the clock key. The instrument returns automatically to normal display. h Press the U key h Set the day (upper display) using the o and u keys h Confirm with E h Set the month (middle display) using the o and u keys h Confirm with E h Set the year (lower display) using the o and u keys h Confirm with E h Set the hours using the o and u keys h Confirm with E h Enter the minutes and set using the o and u keys h Confirm with E 2.5 Entering alarm limits and number of channels h Press the p key Manual mode Scroll mode Normal display Pgm LED off Pgm Temp1 Temp2 Clock Display 1: prealarm limit value ENTER Display 2: alarm limit value ENTER Display 3: number of channels ENTER Parameter level Pgm LED on h Change the value which is currently flashing using the o and u keys 2.00/LMD-96/400 9

2 Operation of the LMD-96 Range of values: - limit value for prealarm -250 to+ 850 C (Temp1 key) - limit value for alarm -250 to +850 C (Temp2 key) - channel number 1 96 (Clock key) h Confirm the entered value with E h When all parameters are confirmed, leave the parameter level again, using the p key. 2.6 Installation of a new system The installation can be completed without any additional aid. h Wire up the modules in accordance with the connection diagram The following installation procedure fixes the module number and consequently the channel number for all analogue input modules (module no. 1: channels 1 4, module no. 2: channels 5 8, etc...). h Press p + o ( 1 flashes in the middle display) h Press the installation key (4) on the module using a ball-pen or pencil. After a successful installation, the value in the middle display increases. h Repeat the procedure until all modules are installed h End the installation with p + o h Adjust the number of channels v Section 2.5 Entering alarm limits and number of channels 10 2.00/LMD-96/400

2 Operation of the LMD-96 2.6.1 Extension of an installed system h Preselect a module number at the installation level using the o and u keys h Press the installation key (4) on the module using a ball-pen or pencil. The module number which is set is assigned to this module. After a successful installation, the value in the middle display increases. A If a module number is duplicated when an installation is extended, this will lead to an incorrect measurement display, because the LMD-96 receives measurements from 2 different modules. 2.6.2 Replacing a faulty analogue input module It is possible to exchange the Plug & Play memory, or to re-install the module. v Section 2.6.1 Extension of an installed system To replace the Plug & Play memory: h Switch off the supply h Remove the plug connectors and take out the module h Fit the Plug & Play memory of the faulty input module into the new module h Restore the connections by plugging in h Switch on the supply 2.00/LMD-96/400 11

2 Operation of the LMD-96 12 2.00/LMD-96/400

3 Operation of the LMD-400 3.1 Displays and controls Measured value LED 1 LED 2 LED 3 LED 4 Key 1 Channel number Key 2 Alarm limit value Clock key Enter key Programming Automatic operation Decrementing Incrementing Upper display Middle display Lower display Normal display measured value (one decimal place) channel no. (3-digit, no decimal point) Alarm display (on alarm occurrence) measured value (one decimal place) A = alarm (Cd 05=1) P = prealarm (Cd 05=1) O = overrange (Cd 05=0) U = underrange (Cd 05=0) and channel number display of the alarm limit value (one decimal place) or U key: the current time appears for 5 seconds Probe break or module failure ---- channel no. (3-digit, no decimal point) 3.2 Normal display After switch-on, the display will automatically be in scroll mode (LED in the auto key lights up), i.e. the channel number, and therefore also the displayed measurement, change at the set scroll rate. v Section 3.11 Configuration Cd 02 2.00/LMD-96/400 13

3 Operation of the LMD-400 If the A key is pressed, the instrument changes to manual mode. The LED goes dark and the required channel number can be set with the o und u keys. In both display modes, newly occurring alarms will be displayed immediately. Scroll Scroll-Mode mode Manual Hand-Mode mode (LED (LED on) an) (LED (LED off) aus) H The number of channels is factory-set to 0. Measurements will only be retrieved and displayed when this is changed to a different value. H When an installed system is switched on, it takes 60 seconds before valid measurements are available. During this period the lower display will show the current time. v Section 3.11 Configuration 3.3 Alarm display When an LMD-400 is installed, monitoring of the measurements against alarm limits takes place in the analogue input modules. However, the alarm limits as well as other parameters can be changed. v Section 3.8.2 Altering the module parameters As well as the measurements, the alarm conditions of the input modules are retrieved in a cyclical sequence. If an alarm occurs, the LMD-400 automatically changes to the channel which has initiated the alarm. Further alarms are stored. In addition, the system conditions are displayed via 4 relays and 4 LEDs. The 4 relays operate as break contacts (negative logic) Normal display Lower limit underrange Prealarm Upper limit overrange Probe break or bus interruption Relay 1 active inactive inactive active active Relay 2 active active active inactive active Relay 3 active switches on and off in time with the flashing pulses of the LED switches on and off in time with the flashing pulses of the LED Relay 4 active active active active inactive LED 1 off on on off off LED 2 off off off on off LED 3 off flashes, whenever unacknowledged alarms are waiting off flashes, whenever unacknowledged alarms are waiting LED 4 off off off off on off An alarm must always be acknowledged with E before relay 3 returns to the normal position. This is also the case if the alarm condition clears before it is acknowledged. The relays, and conse- 14 2.00/LMD-96/400

3 Operation of the LMD-400 quently the LEDs 1 and 2, are in the alarm condition only for as long as the alarm or prealarm is actually present. LED 4 indicates a probe break or bus interruption. 3.4 Alarm print-out A communication module must be available for an alarm print-out. The data are transmitted via the RS232 serial interface to an ASCII printer, using only the RxD, TxD and GND lines (no handshake). For this reason, a sufficiently large backup memory must be available in the printer, or a lower baud rate must be set. The alarm print-out with all alarms which have occurred takes the following format: Date Time Channel no. Alarm status current measured value dd.mm.yy hh:mm XXX Alarm = alarm Pre = prealarm UUUUU = underrange OOOOO = overrange ACK = acknowledge Range = probe break Bus = module not replying YYY.Y Example: 01.03.1999 15:15 27 Alarm 45.0 3.5 Report print-out The date and time are printed on the first line, then 8 channels are printed in a line. Current alarm values are shown in brackets. noinp means that the channel is switched off (no sensor). Example for 12 channels: 13.03.1999 10:55 001...008 27.0 23.5 66.3 48.9 66.3 (33.6) 66.3 12.5 009...012 22.0 21.3 noinp 55.9 The report print-out can be initiated either manually via the key combination o + E, or automatically at a programmable set time. v Section 3.11 Configuration 2.00/LMD-96/400 15

3 Operation of the LMD-400 3.6 Overview of functions uuu Scroll-Mode mode (LED on) an) Manual Hand-Mode mode (LED off) aus) Up-Enter Clock Uhr Pgm Pgm-Up 5 sec Sek. current aktuelle time Uhrzeit Reportausdruck print-out Parameterebene level Installation Clock Uhr Pgm-Up Set Uhrzeit time stellen Configuration Konfiguration 3.7 Setting the time The time can be set in either manual or scroll mode. Input of the time can be ended at any time by pressing the clock key. The instrument returns automatically to normal display. h Press the clock key twice h Set the day (upper display) using the o and u keys h Confirm with E h Set the month (middle display) using the o and u keys h Confirm with E h Set the year (lower display) using the o and u keys h Confirm with E h Set the hours using the o and u keys h Confirm with E h Enter the minutes and set using the o and u keys h Confirm with E 16 2.00/LMD-96/400

3 Operation of the LMD-400 3.8 Configuring the channels 3.8.1 Factory settings Analogue input module, 4-channel Analogue input module, 8-channel Sensor 0 400 Ω according to version Linearisation Pt100 Pt100 Scaling start 0 0 Scaling end 100 100 Lower limit 0-50 Upper limit 100 +50 Prealarm limit 0 0 2.00/LMD-96/400 17

3 Operation of the LMD-400 3.8.2 Altering the module parameters All table settings in the connected analogue input modules can be altered with the LMD-400. 18 2.00/LMD-96/400

3.9 Installation of a new system 3 Operation of the LMD-400 No further aids are required for the installation. Altogether up to 400 channels of analogue input modules can be covered, and in addition 1 relay module and 2 communication modules can be connected. h Wire up the modules according to the connection diagram The following installation procedure fixes the module number and consequently the channel number for all analogue input modules (module no. 1: channels 1 4, module no. 2: channels 5 8, etc...). h Press p + o ( 1 flashes in the middle display) appears after key (4) on the first communication module was pressed for the printer connection. Address: 111 appears after key (4) on the second communication module was pressed for the supervisory level. Address: 112 appears after key (4) on the relay module was pressed. Address:110 h Press the installation key (4) on the module with a ball-pen or pencil The middle display is counted up, if an analogue input module was installed. The lower display will show an r, P or b, depending on the type of module which is currently installed. h When all connected modules have been identified, end the installation with p + o h Adjust the number of channels v Section 3.11 Configuration H If only one communication module is to be used as the MODbus interface for the supervisory level, Cd14 must be reset to MODbus protocol at the configuration level. Instead of the P for printer, a b is then displayed during the installation. 2.00/LMD-96/400 19

3 Operation of the LMD-400 3.9.1 Extension of an installed system h Preselect a module number in the installation level using the o and u keys h Press the installation key (4) on the module with a ball-pen or pencil The module number set is assigned to this module. After a successful installation, the value in the middle display increases. A If a module number is duplicated when a system is extended, this will lead to an incorrect measurement display, because the LMD-400 receives measurements from 2 different modules. 3.9.2 Replacing a faulty analogue input module It is possible to exchange the Plug & Play memory or to re-install the module. v Section 3.9.1 Extension of an installed system To replace the Plug & Play memory: h Switch off the supply h Remove the plug connector and take out the module h Fit the Plug & Play memory of the faulty input module into the new module h Restore the connections by plugging in h Switch on the supply 20 2.00/LMD-96/400

3.10 De-installation 3 Operation of the LMD-400 If any previously installed communication modules or the relay module are no longer required, they can be taken out of the system again. h Press p and o h Press the U key repeatedly, until the module letter to be removed flashes h Press E The module letter disappears from the display and is consequently removed from the system. h Remove further modules with U and E, if required H The N key takes you back to the installation level. v Section 3.9 Installation of a new system h End the de-installation with p and o H The configuration level is accessed automatically. 2.00/LMD-96/400 21

3 Operation of the LMD-400 3.11 Configuration The Cd functions are used to adapt the particular module to the specific application. It is possible to leave the configuration level at any time with the p + o keys. All entries acknowledged with E are stored automatically. v Section 3.6 Overview of functions h Enter the password and acknowledge with E h Select the required Cd function using the o and u keys and acknowledge with E h Set the required value and acknowledge with E Code Meaning Value range Factory setting Cd 1 display of software version - - Cd 2 scroll time for channel switching 1 60 sec 2 Cd 3 time of daily report print-out 00:01 23:59 0000 0000 means no print-out Cd 4 number of channels 1 400 0 Cd 5 0 = range monitoring 1 = limit monitoring 1 HSet the low limit very low Cd 6 Cd 7 upper limit for all channels ---: different upper limit for all channels lower limit for all channels ---: different lower limit for all channels -199.0 to +850.0 --- -199.0 to +850.0 --- 22 2.00/LMD-96/400

3 Operation of the LMD-400 Cd 8 Cd 9 Cd 10 differential for prealarm ---: value is to be entered for each channel with linear linearisation, this is the display value for start of the standard signal range with all other linearisations: offset for all channels ---: value is to be entered for each channel display value for end of the standard signal/ resistance thermometer range --: value is to be entered for each channel h End the configuration with p + o -199.0 to +850.0 --- -199.0 to +850.0 --- -199.0 to +850.0 --- Cd 11 password setting 0 99 0 Cd 12 baud rate 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 7 = 38400 5 Cd 13 parity 0 = none 1 = even 2 = odd Cd 14 switching between printer operation or MODbus protocol for supervisory level 0 = printer operation 1 = MODbus 0-2.00/LMD-96/400 23

3 Operation of the LMD-400 24 2.00/LMD-96/400

4 Electrical connections 4.1 Connection diagram LMD-96 Relay outputs 1 3 Terminals, connector 4 Relay 1 4.1 n.o. (make) 4.2 common Relay 2 4.3 n.o. (make) 4.4 common Contact protection: varistor S14K300 Contact life: 10 6 operations at rated load contact rating: 230V 3A (resistive load) Relay 3 (changeover contact) 4.5 n.o. (make) 4.6 common 4.7 n.c. (break) Supply Terminals, connector 5 110 240V AC +10/-15%, 48 63 Hz L1 N PE line neutral protective earth LON interface Terminals, connector 3 FTT 10A 78kbaud 3.1 3.2 3.3 technical earth screened twisted pair screened twisted pair 2.00/LMD-96/400 25

4 Electrical connections 4.2 Connection diagram LMD-400 Relay outputs 1 4 Terminals, connectors 4 and 2 Relay 1 4.1 n.o. (make) 4.2 common Relay 2 4.3 n.o. (make) 4.4 common Contact protection: varistor S14K300 Contact life: 10 6 operations at rated load contact rating: 230V 3A (resistive load) Relay 3 (changeover contact) 4.5 n.o. (make) 4.6 common 4.7 n.c. (break) Relay 4 (changeover contact) 2.1 n.o. (make) 2.2 common 2.3 n.c. (break) Supply Terminals, connector 5 110 240 V AC, +10/-15%, 48 63 Hz L1 N PE line neutral protective earth LON interface Terminals, connector 3 FTT 10A 78kbaud 3.1 3.2 3.3 technical earth screened twisted pair screened twisted pair 26 2.00/LMD-96/400

4 Electrical connections 2.00/LMD-96/400 27

M. K. JUCHHEIM GmbH & Co Hausadresse: Moltkestraße 13-31, 36039 Fulda, Germany Lieferadresse: Mackenrodtstraße 14, 36039 Fulda, Germany Postadresse: 36035 Fulda, Germany Telefon: (06 61) 60 03-0 Telefax: (06 61) 60 03-5 00 E-Mail: mail@jumo.net Internet: www.jumo.de United Kingdom JUMO Instrument Co. Ltd. Temple Bank, Riverway GB-Harlow, Essex CM20 2TT Phone (0 12 79) 63 55 33 Fax (0 12 79) 63 52 62 USA JUMO PROCESS CONTROL INC. 735 Fox Chase, Coatesville, PA 19320 Phone 610-380-8002, 800-554 JUMO Fax 610-380-8009