SCHEDULE OF QUANTIY S.N. DESCRIPTION QTY UNIT RATE TOTAL SECTION - A ( PANELS & D.B's) 1 Supply, Installation, Testing & Commissioning of 125 Amps TPN SFU with 100 Amps HRC fuses in the Meter room. QRO Set 2 SITC of Main Power Panel 1 Set Incommer : a) 100 Amps, 25 KA, FP MCCB with accessories as follows : Qty 1 Set i) Thermal O/L Release (Range: 0.8 Ir - 1.1 Ir) ii) Instantaneous magnetic S/C Trip iii) Shunt release b) 100 Amps TPN tinned Copper Bus bars with heat shrinkable sleeving c) AMF with selector switch, 3 Nos 100/5 A, class-1.0, 10 VA metering CT's - One set d) V/M with selector switch (7 position, 0-500 volts) with 2A HRC fuses/mcbs - 1set e) Indication lamps R,Y,B with 3 Nos 2A HRC Fuses/mcb's - 1 set f) APFC meter of Epcos make BR-4000 indicating PF, KVA, KVAR, KW of Epcos make- 1 set Outgoings : 63 A TP MCB- 2 NOS, 40 A TP MCB- 2 NOS, 40 A DP MCB - 3NOS. 25 A TP MCB- 2 NOS, 16 A TP MCB- 2 NOS, 5 Kvar Gas filled heavy duty 3 phase capacitor bank- 1 set Epcos make 10 Kvar heavy duty Gas filled type, 3 phase capacitor bank- 1 set Epcos make (The rate shall include for all components including wiring, terminals etc.) 3 Supply, Installation, Testing & Commissioning of Distribution Boards complete with MCBs / Isolators / Bus bars and interconnections.
a 6 way TPN, IP 42 Double door DB as follows 1 Set Incommer 63A TPN MCB- 1 No. Sub Incomer for each phase 32A DP RCCB Outgoing 16A/20 A SP MCBs -12 Nos. b 4 way TPN, IP 42 Double door DB as follows QRO Set Incommer 40A/ 4 pole ELMCB /300mA- 1 No. Outgoing 10 A/16A/20 A SP MCBs -12 Nos. c 16 wayspn UPS DB for 3 kva UPS with 40Amps/ 4 pole as I/P for UPS 1 Set Incommer 40A,DP MCB - 1 No. Outgoing 16 A SP MCBs -12 Nos(.for UPS Circuits) d 8 way SPN RAW POWER & LIGHTING DB 2 Set Incommer 32A, DP MCB - 1 No. Outgoing 10 A/16A/20 A SP MCBs -04 Nos. e 8 WAY SPN INVERTOR DB QRO Set Incommer 40A DP MCB- 1 No. (for I/C of Invertor) Incommer 32A DP MCB- 1 No. (from O/G of invertor) Outgoing 10/16/20/25A SP MCBs -8Nos. 4 2 Pole with center ON/OFF/ON, 40A MCB housed in MS Box 1 set 5 Supply & Installation of 1.0 KVA inverter with 30 min battery backup with SMF batteries of QRO Set Yuasa / Exide with Prolite / Vivitar make Invertor. Input voltage : 230V, +/- 10% Output voltage : 230V, +/- 2% Battery charger Auto / Manual, float cum Boost.The rate shall include overvoltage cutoff and undervoltage trip. Total of `Section A'
SECTION - B (Cables & Wiring) 1 Supply & Laying of aluminium / copper armoured cables fixed to walls,ceilings, on trays or fixed with alu.clits in ready-made trench as follows: a 3.5 Core 35 sq. mm Armoured Al cable with bare 8 x 2 SWG G.I earth wire 90 mtr b 4 Core16 sq. mm Armoured copper cable with bare 12 SWG G.I earth wire QRO mtr c 4 Core10 sq. mm Armoured Copper cable with bare 12 SWG G.I earth wire 20 mtr d 4 Core 6 sq. mm Armoured Copper cable with bare 14 SWG cu earth wire for Thre phase A/C's. QRO mtr e 3 Core 6 sq. mm Armoured Copper cable for UPS DB from MDB 50 mtr f 3 Core 4 sq. mm Armoured Copper cable 20 mtr g 2 Core 2.5 sq. mm Armoured Copper cable with bare 14 SWG cu earth wire for Single phase A/C's,Fire & Smoke / External Lighting & security pannel. 170 mtr h 2 Core 1.5 sq. mm Armoured Copper cable with bare 12 SWG G.I earth wire for smoke det.internal connections 125 mtr I 1 core6 sqmm FLEXIBLE Copper PVC insulated FRLS leads for UPS. 130 mtr 2 Termination of the above cables with Heavy duty Cu. Lugs & Brass cable glands.( Considering the both Ends of the cable) a 3.5 Core 35 sq. mm Armoured copper cable 4 Nos. b 4 Core16 sq. mm Armoured copper cable QRO Nos. c 4 Core10 sq. mm Armoured Copper cable 4 Nos. d 4 Core 6 sq. mm Armoured Copper cable QRO Nos
e 3 Core 6 sq. mm Armoured Copper cable 10 Nos f 3 Core 4 sq. mm Armoured Copper cable 4 Nos g 2 Core 2.5 sq. mm Armoured Copper cable 20 Nos h 2 Core 1.5 sq. mm Armoured Copper cable 40 Nos I 1 core10 sqmm FLEXIBLE Copper PVC insulated FRLS leads for UPS / STABILIZER 20 Nos 3 Point wiring with medium grade 20/25 mm PVC conduits with 2 Nos of 1.5 sqmm & 1 no of 1 sqmm (for earth) PVC insulated copper conductors Polycab / Finolex FRLS wires with modular type switches complete with all accessories as detailed in the specifications. The switch boxes shall be flush mounted with partition works or as directed by the Architects and shall be done in co-ordination with interior furniture works. The rate shall include circuit wiring from DB to switchboard & for switchboard to switchboard. The ceiling rose shall be of 3 plate. Conduit shall be fixed on wall / trays or ceiling with spacers & saddles as per standard practice. a Primary light points From DB to SB & SB to SB & SB to Light Points. 35 Nos b Secondary light points Light point to light point 25 Nos c loop point upto 1 Mtr distance 6 Nos d DB controlled primary point (Cost of the switch not to be condsidered. Only wiring 6 Nos from DB to first point needs to be considered.) 4 Point wiring with medium grade 20/25 mm PVC conduits with 2 Nos of 2.5 sqmm & 1 no of 1.5 sqmm (for earth) PVC insulated copper conductors Polycab / Finolex FRLS wires with modular type switches complete with all accessories as detailed in the specifications. The switch boxes shall be flush mounted with partition works or as directed by the Architects and shall be done in coordination with interior furniture works. The rate shall include circuit wiring from DB to switchboard & for switchboard to switchboard. The ceiling rose shall be of 3 plate. Conduit shall be fixed on wall / trays or ceiling with spacers & saddles as per standard practice. a Primary light points DB to Light Point 24 Nos b Secondary light points Light Point to Light Point 16 Nos
Point wiring with medium grade 20/25 mm PVC conduits with 2 Nos of 4 sqmm & 1 no of 1.5 sqmm (for earth) PVC insulated copper conductors Polycab / Finolex FRLS wires with modular type switches complete with all accessories as detailed in the specifications. The switch boxes shall be flush mounted with partition works or as directed by the Architects and shall be done in co-ordination with interior furniture works. The rate shall include circuit wiring from DB to switchboard & for switchboard to switchboard. The ceiling 5 rose shall be of 3 plate. Conduit shall be fixed on wall / trays or ceiling with spacers & saddles as per standard practice. a Independent 16A plug points socket. (upto 17 meter) 14 Nos Total of `Section B' SECTION - C (Lighting Fixtures & Fittings) 1 Supply, Installation, Testing & Commissioning of 9", 230v, 1500 rpm industrial type exhaust 2 Nos fans with louvers of GEC / Crompton make.the rate shall include connection with 3core 0.5 sqmm flexible copper cable from ceiling rose to the exhaust fan. 2 Supply, Installation, Testing & Commissioning of 16" wall fan of Almonard / Remi make. The 5 No rate shall include connection with 3 x 0.5 sqmm PVC Cu.cable. Supply, Installation, Testing & Commissioning of 12" wall fan of Almonard / Remi make. The 1 No rate shall include connection with 3 x 0.5 sqmm PVC Cu.cable. 3 Supply, Installation, Testing & Commissioning of 36" ceiling fan of Crompton / Orient / Usha 0 No make. The rate shall include connection with 3 x 0.5 sqmm PVC Cu.cable. 4 Supply, Installation,Testing & Commissioning of 36w LED Fixture 2' x 2'. The rate 14 Nos. The fitting shall be fixed with 16 gauge MS down rods with ball and sockets, check nuts etc. The fitting shall be suspended type mounted on false ceiling. The rate shall include connection with 3 core 0.5 sqmm. flexible copper cable. The brief specification of Fixture is as under : Make : Philips / Wippro / Crompton /or approved by Architects. Choke : Ballast Housing : CRCA sheet 7 tank Processed &Powder coated. Hardware : Passivated, Brass/Anodised. LED : Philips / Osram, Wippro
Fixture should match the CFC area in looks & specification. 5 Supply, Installation, Testing & Commissioning of 18 and 28 watts LED tube Lights 2 NOS 2FT, 3NOS 4FT 5 Nos lamps respectively.the fitting shall be fabricated from CRCA sheet steel, powder coated with opal diffuser,supported by decorated endcaps. Make : Philips / Wipro / Crompton /or approved by Architects. Lamp : Philips / Osram/Wippro/crompton 6 providng & fixing call bell point for manager cabin 1 Nos 7 Supply, Installation, Testing & Commissioning of 18 watts LED down Lighter spot Light 15 Nos. lamps.the fitting shall be fabricated from CRCA sheet steel, powder coated with opal diffuser,supported by decorated endcaps. Make : Philips / Wipro / Crompton /or approved by Architects. Lamp : Philips / Osram/Wippro/crompton 8 Supply, Installation, Testing & Commissioning of main board display light 1 Nos fixture complete with all accessories. Make : Philips / Wipro / Crompton /or approved by Architects. Lamp : Philips / Osram 9 Supply, Installation, Testing & Commissioning of Integral post top light fixture suitable QRO Nos for CFL upto 18 watts consisting of combination of spun aluminium canopy & clear acrylic top cover, cast aluminium pole capon pole / bracket fixture (Lollipop Light) complete with all accessories. Make : Philips / Wipro / Crompton /or approved by Architects. Lamp : Philips / Osram Total of `Section C' SECTION - D (Power Outlets) 1 Supply, installation, testing & comissioning of 20A Reyroll Plug-Sockets with 3 Pin Metal Top housed in metal board with 20A SP MCB. (Make MDS / Crompton) 9 Nos 2 Supply, installation, testing & comissioning of 32/40A FP MCB in Water proof Metal box for Three Phase A/C near outdoor unit 9 Nos
3 Supply, installation, testing & comissioning of 40/32A DP MCB in Metal box. QRO Nos 4 Supply and Fixing 6/16 A Power Switch Socket combine with indicator complete with G.I. mounting box for water filter in Pantry area. 1 Nos 5 Supply & Fixing of 1 No 6 Amps 3 Pin switch-socket with different colour in 3 module Box. (FOR Raw Power) 35 Nos 6 Supply and fixing of modular type shuttered power sockets, data-outlets, telephone sockets complete with chrome plated mounting box. The switch box shall be fitted in partition works. The rate shall be inclusive of connecting of switches / sockets. a)2 Nos of 6A 5pin universal sockets controlled by 2 No16A switch in moduar box. (for UPS Power) 14 set b)3 Nos of sockets 6A 3pin universal 16A.Sw. in mod. box in server room 8 set c)1 No of 16A switch in 3 module box. (for UPS Power) QRO set d)2 Nos of sockets 6A 5pin universal in moduar box. (for UPS Power) QRO set e)1 No of 6A switch in 3 module box. (for UPS Power) QRO set f)1 No of RJ 11 telephone socket outlet 10 set g)2 Nos of RJ 11 telephone socket outlet 1 set h) 1 No RJ 45, cat 6, DATA I/O complete with GI chrome plated mounting box. The rate shall be inclusive of termination of the IO's of D Link/ MTNL router and VSAT Tikona Router 15 set Total Of `Section D' SECTION - E (Miscellenous Work) 1 Preparation and commissioning of earthpits with 300x300x3mm thick copper electrode plate complete with chamber, watering arrangement, charcoal, salt etc; The electrode shall be connected with 8 gauge cu wire and terminated into the chamber. The rate shall include cost of earthing wire upto the Chamber. 1 No
2 Preparation and commissioning of earthpits with 600x600x6mm thick GI electrode plate complete with chamber, watering arrangement, charcoal, salt etc; The electrode shall be connected with 32x6 mm thick cu strip and terminated into the chamber. The rate shall include cost of earthing strip upto the Chamber. QRO No 3 Supply and laying of 32mm x 6mm thick G.I. earthing strip fromearthing chamber to the main power panel and it's termination. The portion of the strip underground shall be laid upto the depth of at least 75 cms. The portion on building wall upto the main panel shall be fixed with spacers and clamps. 80 mtrs 4 Same as bove but with single core 25 sqmm PVC insulated Copper conductor through 25mm dia heavy gauge pvc pipe. The rate shall include cost of pipe & all materials. (inside the building). QRO mtrs 5 Same as above but with single core 25 sqmm PVC insulated Copper conductor through class `B' GI pipe. The rate shall include cost of pipe & all materials. (from earth pit to building). QRO mtrs 6 Same as above but with 8 gauge Copper conductor through 25mm dia heavy gauge pvc pipe. The rate shall include cost of pipe & all materials. (inside the building). 58 mtrs 7 Same as above but with single core 16 sqmm PVC insulated Copper conductor through class `B' GI pipe. The rate shall include cost of pipe & all materials. (from earth pit to building). QRO mtrs 8 Supply & fixing of 4 digit Token indicator with all installation 1 No 10 Providing & Laying the CC TV RG 59 co-axial copper 4+1 cable,in 25mm heavy duty PVC conduit with all accessories with DVR unit to CC TV Camera as directed by Architect and the drawing 200 mts 11 Commissioning and Installation of DVR and CC TV Dome camera as directed by Architect and drawing 1 job The DVR and Cameras would be provided by the Bank Total of `Section E' SECTION - F (PVC Trunking & WIRING) 1 Trunking / Conduits for Electrical Raw & UPS power circuits, telephones, Cat -6 cabling etc. the laying of the PVC Trunking / conduits Through wooden partitions and concealed through wall The rate should include the cost of the trunking / conduits, wiring connecting with all necessary hardware. 30 mtr
2 Supply and laying of three partition PVC Trunking / Conduits. The Trunking / raceways / conduits shall be fixed to the flooring with clamps for finished levels as per site conditions or through partitions with all accessories, bends, pull wire etc; but excluding the floor mounted junction boxes which shall be paid separately. The PVC trunking / raceways shall be earthed with copper earthing clips at suitable intervals. The distance between the data conduits & power conduits shall be maintained at least 6" apart. a 300mmx50mm, 2mm thick Hot dipped galvanised three partition trunking complete with cover, coupler plates, hardware and accessoreies QRO mtr b Same as above but of size 100mmx40mm, 2mm thick QRO mtr c 82mm x 38mm PVC Trunking, 2 mm thk. 15 mtr d 62mm x 38mm PVC Trunking, 2 mm thk. 8 mtr e 32mm PVC conduits medium guage 60 mtr f 25mm PVC conduits medium guage 40 mtr g 20mm PVC conduits medium guage 45 mtr h 75mm.x 32mm pvc Trunking of LK/MK make to be fixed on partition QRO mtr 3 Supply and fixing of 50 mm deep GI finish junction boxes suitable for receiving of three partion trunking. The Junction boxes shall have knock outs from all the four sides. The Junction boxes shall be laid in trenches as detailed in item No.3. The top cover shall be fixed with counter shunk screws. QRO Nos 4 Same as item 3 above but to receive 40 mm deep three partition under floor trunking QRO Nos 5 Supply and fixing 450mm x 450mm x 50 mm deep GI junction boxes. The junction boxes shall have knock outs on all the sides suitable for raceways / conduits. The knock outs shall be removed at site as per requirement. The junction boxes shall be laid in the trenches for raceways / conduits as detailed in item no. 3. The top cover shall be fixed with counter shunk screws. QRO Nos 6 Supply and fixing 100mm x 100mm x 50 mm deep PVC junction boxes suitable for receiving of two partion trunking. The junction boxes shall have knock outs on all the sides suitable for PVC Trunking / conduits. The knock outs shall be removed at site as per requirement. The junction boxes shall be fixed on floor or wooden partition. The top cover shall be fixed with counter shunk screws. 10 Nos
7 Supply and fixing 250mm x 250mm x 50 mm deep PVC junction boxes suitable for receiving of two partion trunking. The junction boxes shall have knock outs on all the sides suitable for PVC Trunking / conduits. The knock outs shall be removed at site as per requirement. The junction boxes shall be fixed on floor or wooden partition. The top cover shall be fixed with counter shunk screws. 5 Nos 8 Supply and laying of 25mm medium gauge pvc conduits on walls, ceiling or through partitions with spacers and saddles as per standard practice. 40 mtr 9 Supply & Laying of Cat 6 cable of Avaya / Amp / Digilink make through already laid raceways 400 mtr 10 Supply & fixing of 5 pair telephone MDF consisting of tag blocks in groups of 10 pair dis connector type Krones complete with powder coated MS enclosure, Krone mounting arrangement, telephone distribution chart and with locking arrangement. QRO No 11 Supply & fixing of Krone tag blogs 20 pair as above 1 Nos 12 Supply & Fixing of 3x8 EPABX System of reputed make to Clients approval (including supply of 8 handsets) 1 No 13 Supply & Laying of.5mm dia electrolytic tinned copper conductors pvc insulated twisted pair with rip cord telephone cable through already laid condits/ raceways complete with connections. (Make : Delton / Finolex) a. 2 pair QRO Mtr b. 3 pair 190 Mtr 14 Supply & Laying of.5mm dia electrolytic tinned copper conductors pvc insulated twisted pair with rip cord telephone cable through already laid condits/ raceways. b. 10 pair 40 Mtr c. 20 pair QRO Mtr 15 Terminations of telephone cables on krone blocks complete with gland and identification chart etc; a. 10 pair 1 Job b. 20 pair QRO Nos 16 Supply & Laying of RJ 59 Cable in PVC Conduit QRO mtr
TOTAL of `Section - F' SECTION - G (SMOKE DETECTION SYSTEM) 1 Supply, Installation, testing and commissioning of CONVENTIONAL 2 LOOP fire Alarm Control Panel with 24 Volts SMF batteries suitable for 24 hours back up time with battery charger complete as specified in the specifications. (Four nos potential free contacts as output for tripping the AC feeder is required from Fire Alarm Control panel.) make - Eureka Forbes / Zicom / Notifier / Honeywell / Nitin Fire / Digicon Engineers / Morely etc; (Other makes subject to approval of Architect / Consultant / Client.) 1 No 2 Supply,fixing,testing and commissioning of smoke/heat detectors dual chamber CONVENTIONAL type complete with base plate, MS Junction box for termination / connections etc; (Make Appolo series 65, System Sensor ) 6 Nos 3 Same as above but Heat Detector QRO No 4 Supply,installation,testing and commissioning of response indicators suitable for above smoke detector complete with MS junction box, top hylem sheet and with all required accessories (for closed rooms / cabins) 6 Nos 5 Supply,installation,testing and commissioning of type manual break glass unit flush mounted in partition or concealed in walls for manual action of ALARM in case of FIRE 1 Nos 6 Supply,installation,testing of dual tone fire alarm hooter complete with accessories including wiring 1 No TOTAL of `Section - G' SECTION - H (SECURITY SYSTEM - INTRUDER ALARM SYSTEM) 1 Supply,fixing,testing and commissioning of microprocessor based Four zone INTRUDER ALARM Control Panel complete with 12 volt SMF batteries suitable for 24 hours back up time complete with battery charger etc; make - Secutec / Zicom / DATS / Honneywell / Technocrat or equivalent (Other repute make subject to approval of Architect / Consultant) 1 No 2 Supply,fixing,testing and commissioning of motion detectors 1 Nos 3 Supply, Installation, Testing & Commissioning of alarm sounder complete with accessories 2 Nos
4 Supply,installation,testing of panic switch complete with accessories including wiring 5 Nos TOTAL of `Section - H' SECTION - I (AIR CONDITIONING SYSTEM) 1-a Supplying and erecting split type room Airconditioning unit 1 TR 5 star capacity 230/250V, 50 cycles, A.C. supply having 1 No of air handling unit hi-wall / floor mounting type complete at position (Server Room/Manager's Cabin) Nos. 2 b Supplying and erecting split type room Airconditioning unit 2 TR 5 star capacity 230/250V, 50 cycles, A.C. supply having 1 No of air handling unit hiwall / floor mounting type complete at position (Branch Area) Nos. 4 c Removing and re erecting existing split type Airconditioning unit 1 TR, A.C. having 1 No of air handling unit hi-wall / floor mounting type complete at position. Servicing must before installation (Battery Room) Nos. 1 2 Supply, installation, testing and Commissioning of AC Timer switch for server room AC Nos. 1 3 Supplying & erecting copper pipe suitable for refrigeration system having 22 guage thickness and inner dia / size 12 mm complete. with nitrile rubber insulation. Rmt 60 4 Supplying & erecting copper pipe suitable for refrigeration system having 22 gauge thickness and inner dia / size 22 mm complete. Rmt 60 5 Supply & errection of Electrical Cable 4c x 2.5 sqmm Rmt 130 6 Supplying & erecting I.S.I. mark Rigid P.V.C. conduit 32 mm. dia. with necessary accessories in wall/floor with chiselling appropriately Rmt 50 7 Outdoor Stand Nos 7 8 Standard Installation Nos 7 TOTAL of `Section - I'
SECTION - A : Panel's and DB's SECTION - B : Cable and Wiring SECTION - C : Lighting fixtures and Fittings SECTION - D : Power Outlets SECTION - E : Miscellaneous Works SECTION - F : Raceways & Wiring SECTION - G : Smoke Detection System SECTION - H : Intruder Alarm System SECTION - I : Air Conditioning Systems SUM TOTAL OF SECTIONS : A, B, C, D, E, F, G, H and I CONTINGENCIES 5% GST as applicable GRAND TOTAL AMOUNT