y Small dimensions. Easy to install in refrigerated counters or cold rooms

Similar documents
Thermostat KPU. Data sheet

Thermostats type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure switch KPU. Data sheet

Thermostat, Differential thermostat RT

Thermostat RT. Data sheet

When ordering, please state type and code number. Max. Type - Capillary sensor of tube temp. charge length. C m

TEMPERATURE & PRESSURE CONTROLS

TC-5231 Series, TC-5232, & TC-5241 Series

FSW SECTION. Product guide. Thermostats, Pressure Switches & Fan Speed Controls. E SECTION For more information visit

For Technical Service Telephone Facsimile

Commercial Refrigeration Catalog

Electromechanical cold controls for refrigerators and freezers MAKING MODERN LIVING POSSIBLE. Type description

Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s)

49 Danfoss Thermostat Kits Ranco Varifix Kits

Powers Controls ET 134 Low Temperature Detection Thermostat

Electromechanical cold controls for refrigerators and freezers

Tubular Industrial Process

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION. 71

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

This chapter is devided into two sections:

Powers Controls Low Temperature Detection Thermostat

MACH N-407 Heat Pump Air-Cooled Chiller

The T6140A,B Remote Bulb Temperature Controller

Check valve Types NRV and NRVH

PAR5. Product Specifications

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

Frost Protection Thermostat

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Series A28 Two stage Thermostats. Feature and Benefits

Thermostat Catalog 2004

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

Service Step by Step Trouble-Shooting Check-List

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

MAC N-407 Air-Cooled Chiller

Tubular Industrial Process

MR3CCUHV Temperature/Defrost Control

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

INSTALLATION, OPERATION, SERVICE & PARTS SUPPLEMENT for

Kirby Commander Condensing Unit

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Coil-In-Tank Design: Refrigeration System: Cabinet Construction:

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

Ductless Split Systems Wall-mounted, Single Zone Heat Pump

MAKING MODERN LIVING POSSIBLE. Thermostatic expansion valves, type TR 6 REFRIGERATION & AIR CONDITIONING DIVISION.

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Dual Pressure Controls

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

Hoshizaki America, Inc.

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Temperature, Mechanical

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Pressure Enthalpy Charts

Condensing Unit Installation and Operating Instructions

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

FX5 Series Explosion-Proof Electric Air Heaters

R407C Cellar Cooling. Fansets: Single phase, high efficiency, low

THERMOSTATIC EXPANSION VALVES Part 1

Excellent performance with low operating costs, Energy saving and environmentally friendly

General information on refrigerant controllers

13-1. Temperature Regulator

CR1 Series Triton Corrosion Resistant Washdown Heaters

OIL SEPARATORS APPLICATIONS

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

R4H4. Product Specifications

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Technical Review. Remote Condenser Cuber. Enhanced Refrigeration and Water Systems. CM 3 Technology. of a. with. using. models included are:

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

Tube-in-tube heat exchanger Type HE

PAJ3. Product Specifications

Danfoss Scroll for Refrigeration MLM / MLZ

Thermostatic Expansion Valves Type TR 6

Ultra-Safe EXP Unit Heater

BULLETIN 600 SINGLE PHASE

Single pressure controls for Refrigeration, Air-conditioning and Heatpump applications

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Refrigeration Systems and Accessories

Tubular Industrial Process

Commercial High-Efficiency Condensing Units

Transcription:

MAKING MODERN LIVING POSSIBLE Data sheet Thermostat Type KP The KP Thermostats are temperaturecontrolled electrical switches. All KP Thermostats have a single pole double throw (SPDT) changeover switch. The position of the switch depends on the temperature control setting and the bulb temperature. A KP Thermostat can be directly connected to single-phase a.c. motors of up to about 2.7 HP, or installed in the control current circuit of d.c motors and large a.c. motors. Features y Wide regulating range y Can be used for deep freeze, refrigeration and air conditioning systems y Welded bellows elements mean increased reliability y Small dimensions. Easy to install in refrigerated counters or cold rooms y Ultra-short bounce times. Long operating life. Unnecessary control equipment cut-in and cut-out is avoided y Standard versions with changeover switch Possible to obtain opposite switch function or to connect a signal y Electrical connection at the front of the unit. Facilitates rack mounting. Saves space y Suitable for alternating and direct current y No spade or lug terminals required y Integral 1 / 2 NPSM swivel cable connector Allows direct attachment of 1 / 2 in. male pipe thread connector y Extensive and wide range Approvals UL approval for USA and Canada, file E31024 DKRCC.PD.CA0.E6.22 / 520H8784 A/S (RC-MDGP / jmn), 2015-03

Technical data Ambient temperature Switch -40 150 F (5 F for maximum 2 hours) Single pole changeover switch (SPDT) Contact load 120 V a.c. 240 V a.c. 16 FLA 96 LRA 8 FLA 48 LRA 240 V d.c. 12 W pilot duty Cable entry Enclosure Integral 1 / 2 in. female NPSM swivel cable connector allows direct attachment of 1 / 2 in. male pipe thread. ~NEMA 1; IP30 to IEC 529 (drip proof) This grade of enclosure is obtained when the unit is mounted on a flat surface or bracket. The bracket must be fixed so that all unused holes are covered. Regulating ranges KP 61 KP 63 KP 62 Vapour charge KP 69 KP 73 KP 71 KP 98 OIL Adsorption charge KP 98 HT -50 0 50 100 150 200 250 300 [ F] Electrical wiring KP, single thermostat KP 98, dual thermostat 60-1420.10 KP, single thermostat KP 98, dual thermostat 2 DKRCC.PD.CA0.E6.22 / 520H8784 A/S (RC-MDGP / jmn), 2015-03

Ordering Charge Type Bulb type Regulation range [ F ] at lowest temperature setting [ F] Differential t at highest temperature setting [ F] Reset [in.] [ft ] Code no. Vapour KP 61 B -20 55 8 40 2.2 13 Auto 80 6.5 060L200266 KP 62 C -20 60 10 40 2.7 13 Auto 060L201566 KP 71 E2 25 70 4.5 18 4 18 Auto 80 6.5 060L201066 Adsorption 2) KP 73 D -15 60 8 36 6.3 36 Auto 80 6.5 060L2066 KP 73 E1 0 80 10 35 10 35 Auto 80 6.5 060L202966 3) KP 98 E2 Oil: 140 250 HT: 210 350 Oil: fixed 25 HT: fixed 45 Oil: fixed 22 HT: fixed 45 Manual (Max.) 40 80 3.2 6.5 060L202466 1) Bulb must be installed in colder position than thermostat housing and capillary tube. 2) Bulb can be placed warmer or colder than thermostat housing. 3) Factory setting: cut-in: 60 F cut-out: 25 F Thermostat bulb types A Straight capillary tube Sensing lenghts: 15 in. of 80 in. B Dia. 3 / 8 in. x 2 3 / 4 in. remote air coil C Dia. 1 9 / 16 in. 1 in. air coil (integral with thermostat) D Dia. 3 / 8 in. 3 3 / 8 in. double contact remote bulb Note! Cannot be used in sensor (bulb) pocket E E1: Dia. 1 / 4 in. 3 3 / 4 in. remote bulb E2: Dia. 3 / 8 in. 4 1 / 2 in. remote bulb A/S (RC-MDGP / jmn), 2015-03 DKRCC.PD.CA0.E6.22 / 520H8784 3

Design / Function Key sketch of KP thermostat Vapour charge 1 2 3 7 8 9 15 16 60-1016.12.11 12 60-272.12.12 Vapour charge 3 1 8 2 16 12 7 60-660.15.22 13 14 9 19 15 Adsorption charge 3 1 8 2 16 12 7 60-10.13.21 1. Temperature setting spindle 2. Differential setting spindle 3. Main arm 7. Main spring 8. Differential spring 9. Bellows 12. Switch 13. Terminals 14. Earth terminal 15. Cable entry 16. Tumbler. Sensor 19. Capillary tube 13 14 9 19 15 4 DKRCC.PD.CA0.E6.22 / 520H8784 A/S (RC-MDGP / jmn), 2015-03

Design / Function (continued) The switch in the KP has a snap-action function and the bellows move only when the cut-in or cut-out value is reached. The design of the KP thermostat provides the following advantages: high contact load ultra-short bounce time vibration resistance up to 4 g in the range 0 1000 Hz long mechanical and electrical life. KP 98, dual thermostat Max. reset 3 18 1 16 12 5 18 1. Temperature setting spindle (OIL) 3. Main arm 5. Temperature setting spindle (HT) 7. Main spring 9. Bellows 10. Capillary tube (OIL) 11. Capillary tube (HT) 12. Switch 13. Terminals 14. Earth terminal 15. Cable entry 16. Tumbler. Sensor (bulb) 18. Locking plate 7 14 9 10 C B A HT 15 13 11 KP98 9 60-10.13.21 Dual thermostat KP 98 is used as a protection against too high discharge gas temperature and to ensure a suitable oil temperature in the compressor. To avoid the temperature of the hot gas exceeding the maximum permissible value during extreme operating conditions (low evaporating pressure, high condensing pressure, high suction vapour superheat) a KP 98 thermostat can be used on the high temperature side (HT). If the temperature of the hot gas becomes too high the refrigerant will break down and the compressor discharge valve will become damaged. The risk is greatest in refrigeration systems that operate on a high compression ratio (e.g. in systems with NH 3 or R 22) and in applications with hot gas bypass. This unit has two separate thermostat functions. The HT sensor that controls the discharge gas temperature is fitted on the discharge tube immediately after the compressor. For larger compressors, the sensor can be built into the discharge tube. KP 98 is available for protection against low oil temperature. Compressor manufactureres recommend fitting a heating element in the crankcase to prevent refrigerant boiling out of the oil during start. KP 98 is the correct thermostat for controlling this heating element. Why a heating element? During standstill, refrigerant is dissolved in the crankcase oil. If the oil is cold and the standstill period is long, a large amount of refrigerant can dissolve in the oil. This leads to two problems: 1. When the compressor is started, the refrigerant will boil off, causing a high risk of liquid hammer and consequent compressor damage. 2. The oil loses its lubricating capability when it is thinned with refrigerant. To avoid these problems a heating element controlled by a KP 98 should be fitted in the crankcase to keep the oil warm. This prevents dangerous amounts of refrigerant being dissolved in the oil. The OIL sensor that controls the oil temperature is located in the compressor oil sump. A/S (RC-MDGP / jmn), 2015-03 DKRCC.PD.CA0.E6.22 / 520H8784 5

Terminology Differential The differential is the difference between the make and break temperatures. A differential is necessary for satisfactory automatic operation of the system. Mechanical differential (intrinsic differential) The mechanical differential is the differential set by the differential spindle. Operating differential (thermal differential) The operating differential is the differential the plant operates on. Operating differential is the sum of the mechanical differential and the differential produced by the thermal time constant. Reset 1. Manual reset: Units with manual reset can only be restarted after the reset button has been activated. On min. reset units the set value is equal to the cut-out value for falling temperature. On max. reset units the set value is equal to the cut-out value for rising temperature. 2. Automatic reset: These units are automatically reset after operational stop. Setting Thermostats with automatic reset Set the upper activating temperature on the range scale. Set the differential on the DIFF scale. The temperature setting on the range scale will then correspond to the temperature at which the refrigeration compressor will be started on rising temperature. The compressor will be stopped when the temperature has fallen in relation to the differential setting. Please note that the differential depends on the range setting. Therefore, the differential scale must only be used as a guideline. If the compressor will not stop at low stop temperature settings, check whether the differential is set at too high a value! The thermostat will automatically reset and the compressor will start once the temperature rises above the range scale setting. Thermostats with minimum reset Set the stop temperature on the range scale. The differential is a fixed setting. The compressor can be restarted by pressing the Reset button after the temperature on the thermostat sensor has risen by a value equal to the fixed differential setting. Thermostats with maximum reset Set the stop temperature on the range scale. The differential is a fixed setting. The compressor can be restarted by pressing the Reset button after the temperature on the thermostat sensor has fallen to a value equal to the fixed differential setting. 6 DKRCC.PD.CA0.E6.22 / 520H8784 A/S (RC-MDGP / jmn), 2015-03

Charges 1. Vapour charge Note: When the sensor is coldest, the ambient temperature has no effect on regulating accuracy. 9. Bellows element. Sensor (bulb) 19. Capillary tube Here the interdependence between the pressure and temperature of saturated vapour is utilized, i.e. the element is charged with saturated vapour plus a small amount of liquid. The charge is pressure-limited; a further increase in pressure after evaporation of all the liquid in the sensor () will only result in a small pressure increase in the element. This principle can be utilized in thermostats for low temperature, etc. where evaporation must be able to take place from the free liquid surface in the sensor (within the operating range of the thermostat), and where at the same time, the bellows must be protected against deformation when kept at normal ambient temperatures. Since the pressure in the element depends on the temperature at the free liquid surface, the thermostat must always be placed so that the sensor is colder than the rest of the thermostatic element. The evaporated liquid will recondense at the coldest point, i.e. the sensor. Thus, as intended, the sensor becomes the temperature-controlling part of the system. 2. Adsorption charge 9. Bellows element. Sensor (bulb) 19. Capillary tube In this case the charge consists partly of a superheated gas and partly of a solid having a large adsorption surface. The solid is concentrated in the sensor () and it is therefore always the sensor that is the temperature-controlling part of the thermostatic element. The sensor can be placed warmer or colder than thermostat housing and capillary tube, but variations from 70 F ambient temperature will influence the scale accuracy. A/S (RC-MDGP / jmn), 2015-03 DKRCC.PD.CA0.E6.22 / 520H8784 7

Dimensions [in.] and weights [lbs] KP 61 KP 73 KP 61 KP 73 rear side 60-1011.13 60-1024.14 60-1019.12 60-771.14 60-1023.14 KP 98 KP 98 rear side Wall bracket Angle bracket Net weights: KP 61 KP 73: approx. 0.9 lbs KP 98: approx. 1.3 lbs 8 DKRCC.PD.CA0.E6.22 / 520H8784 A/S (RC-MDGP / jmn), 2015-03

Dimensions [in.] and weights [lbs] (continued) KP 63 KP 61, KP 79 KP 62 KP 75, KP 98 KP 73 KP 73 Net weights: KP 61 KP 73: approx. 0.9 lbs KP 98: approx. 1.3 lbs A/S (RC-MDGP / jmn), 2015-03 DKRCC.PD.CA0.E6.22 / 520H8784 9

Accessories Part Description Code no. Bracket (universal hole pattern) Angle bracket 060-105366 Seal screw (KP only) For use when sealing the setting 060-105766 Bulb clamp Screw and nut included Lenghts = 3 in. 0-420366 Clamping band Screws and nuts included Lenghts = 15 in. 0-420466 Bulb holder kit 1 Bulb holder (1pc.) 2 Clamp (4 pcs.) 0-420166 Copper damping coil Capillary tube lenghts [in.] For KP pressure switches KP thermostats MP differential pressure switches with 1 / 4 in. female flare nuts both ends. For KP pressure switch and MP differential pressure switch 18 060-007066 36 060-007166 54 060-007266 ISO 9001 quality approval Refrigeration and Air Conditioning Controls, part of the concern, is certified in accordance with international standard ISO 9001. This means that fulfils the international standard in respect of product development, design, production and sale. A/S (RC-MDGP / jmn), 2015-03 DKRCC.PD.CA0.E6.22 / 520H8784 10