TECHNICAL DATA APPROVED SPRINKLERS FOR USE WITH FOAM CONCENTRATES 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS

Similar documents
QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

standard/quick response extended coverage light and ordinary hazard elo sprinklers

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

micromatic standard response stainless steel sprinklers

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

micromatic standard response Upright sprinkler VK100 (K5.6)

standard response elo upright sprinkler

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

standard response elo upright and pendent sprinklers (storage-density/area)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

standard response Fusible Link Upright sprinkler VK204 (K8.0)

quick response Sprinkler 105a October 25, 2010

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

standard response/ quick response extended coverage

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

microfast quick response Pendent sprinkler VK302 (K5.6)

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

TECHNICAL DATA 3% AR-AFFF

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

TECHNICAL DATA OBSOLETE

micromatic Standard response Horizontal Sidewall sprinkler

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA. Page 1 of 6

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

quick response horizontal sidewall sprinkler vk360 (K8.0)

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

microfast and microfasthp quick conventional sprinklers

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

micromatic Standard response Horizontal Sidewall sprinkler

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

TECHNICAL DATA. Viking Technical Data may be found on. The Viking Corporation s Web site at.

standard response fusible link sidewall sprinkler VK112 (K5.6)

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

standard response dry horizontal sidewall sprinklers

standard response large orifice dry

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

TECHNICAL DATA OBSOLETE

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

mirage standard response concealed pendent sprinkler vk492 (K5.6)

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

STANDARD/quick. Sprinkler 42o. August 8, 2011

TECHNICAL DATA NOTICE

standard response dry horizontal sidewall sprinklers

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

Foam Systems U.S. Quick Reference Guide

esfr dry pendent sprinkler Vk502 (k14.0)

Standard response. elo sprinklers

Storage Sprinkler U.S. Quick Reference Guide

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

Transcription:

Page 1 of 11 1. GENERAL DESCRIPTION Viking Pendent and Upright -Water Sprinklers are non-aspirated foam discharge outlets for use in Wet, Dry, Deluge, Preaction and Refrigerated Area applications. Sprinkler applications are especially challenging for any foam due to the very low operating pressure and expansion reached. Applying foam through a sprinkler head is a very forceful application method and requires foam that can handle direct application and partial submersion into the fuel without losing its fire performance and burn-back resistance. s that shall be regarded as suitable for sprinkler applications shall also be able to withstand a limited time of water deluge directly onto the foam blanket without losing its burn-back properties. Viking Pendent and Upright -Water Sprinklers are FM Approved and UL Listed in both closed head (with bulb) and open head (bulb removed) configurations. Features: Tested, Listed and Approved as -Water Sprinklers with specific s (see section 7). Wide range of K Factors available: K5.6 (K80), K8.0 (K115), K11.2 (K161), K16.8 (K242) For use in high risk applications such as warehouses, aircraft hangers, oil and chemical loading areas, generator rooms, petro-chemical, pharmaceutical and alcohol production plants. 2. LISTINGS AND APPROVALS Viking Water Sprinkler are FM Approved and/or UL Listed as part of a fire extinguishing system combining designated foam concentrates, bladder tanks and proportioning devices. Approved and Listed system components can be found at www.approvalguide.com and www.database.ul.com FM Approved Low Expansion Systems (FM5130) UL Listed GHXV.EX27255 (UL162) 3. Please refer to relevant sprinkler data page. 4. SCOPE OF DELIVERY Ensure that all components are complete and in good condition. Viking /Water Sprinklers are supplied boxed with protective shield or cap. 5. AVAILABILITY Please contact Viking for further information. The product is available directly from Viking and official distributors only. EMEA: Viking SA, ZI Haneboesch, L-4562 Differdange / Niederkorn, Tel.: +352 58 37 37-1, Fax: +352 38 37 36, vikinglux@viking-emea.com Americas: The Viking Corporation, 210 N. Industrial Park Drive, Hastings, Michigan 49058, Toll free phone: (800) 968-9501 APAC: The Viking Corporation (Far East) Pte. Ltd., 69 Tuas View Square, Westlink Techpark, Singapore 637621 Tel: (+65) 6 278 4061, Fax: (+65) 6 278 4609, Email: vikingsingapore@vikingcorp.com 6. PRODUCT VARIANTS Please refer to relevant sprinkler data page. Replaces Form No. F_091316 Rev 18.1 (Added P65 Warning.)

Page 2 of 11 7. PERFORMANCE DATA HYDROCARBON FUELS Min. Height U.S. Metric 4 Upright Pendent ft. m ft. m gpm/ft 2 lpm/m 2 gpm/ft 2 lpm/m 2 PSI (bar) Max Listed 2 Water Discharge Density Tested 3 Sprinkler Approval VK145, VK300, VK301, -- 5.0 1.5 20.0 6.1 0.20 8.1 0.30 12.2 13 0,89 FM 1%S C6 --, VK303 5.0 1.5 20.0 6.1 0.30 12.2 0.30 12.2 29 1,99 FM -- 5.0 1.5 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM --, VK353 6.0 1.8 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM VK530, VK531 -- 8.0 2.4 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM -- VK377, 6.0 1.8 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM 3%S C6 16.8 241.9 VK580 -- 8.0 2.4 33.0 10.1 0.50 20.4 0.50 20.4 9 0,62 FM VK145, VK300, VK301, -- -- 5.0 1.5 20.0 6.1 0.20 8.1 0.30 12.2 13 0,89 FM, VK303 5.0 1.5 20.0 6.1 0.30 12.2 0.30 12.2 29 1,99 FM 8.0 2.4 20.0 6.1 0.20 8.1 0.30 12.2 13 0.89 FM -- 5.0 1.5 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM --, VK353 6.0 1.8 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM VK530, VK531 -- 8.0 2.4 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM -- VK377, 6.0 1.8 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM 16.8 241.9 VK580 -- 8.0 2.4 33.0 10.1 0.50 20.4 0.50 20.4 9 0,62 FM 3%M C6 VK300, VK301 -- 8.0 2.4 20.0 6.1 0.20 8.1 0.30 12.2 13 0,89 FM VK145, VK300, -- 5.0 1.5 20.0 6.1 0.20 8.1 0.30 12.2 13 0,89 FM VK301, --, VK303 5.0 1.5 20.0 6.1 0.30 12.2 0.30 12.2 29 1,99 FM -- 5.0 1.5 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM --, VK353 6.0 1.8 30.0 9.1 0.30 12.2 0.30 12.2 14 0,96 FM VK530, VK531 -- 8.0 2.4 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM -- VK377, 6.0 1.8 33.0 10.1 0.30 12.2 0.30 12.2 7 0,48 FM 16.8 241.9 VK580 -- 8.0 2.4 33.0 10.1 0.50 20.4 0.50 20.4 9 0,62 FM 1 This chart shows approvals available at the time of printing. 2 Density indicated is minimum application density required per FM5130 Standard for Extinguishing Systems. This density cannot be reduced.

Page 3 of 11 K- Factor ALCOHOL - IPA U.S. Metric 4 Upright Pendent ft. m ft. m gpm/ft 2 lpm/m 2 PSI (bar) Min. Height Listed 2 Tested 3 Sprinkler Approval VK300, VK301 -- 5.0 1.5 20.0 6.1 0.20 8.1 13 0,89 FM VK145, -- 5.0 1.5 20.0 6.1 0.30 12.2 29 1,99 FM --, VK303 5.0 1.5 20.0 6.1 0.30 12.2 29 1,99 FM -- 5.0 1.5 30.0 9.1 0.30 12.2 14 0,96 FM --, VK353 6.0 1.8 30.0 9.1 0.30 12.2 14 0,96 FM VK530, VK531 -- 8.0 2.4 33.0 10.1 0.30 12.2 7 0,48 FM -- VK377, 6.0 1.8 33.0 10.1 0.30 12.2 7 0,48 FM 16.8 241.9 VK580 -- 8.0 2.4 33.0 10.1 0.50 20.4 9 0,62 FM Max K- Factor U.S. Metric 4 Upright Pendent ft. m ft. m gpm/ft 2 lpm/m 2 PSI (bar) VK145, VK300, VK301, -- KETONE - ACETONE -- 5.0 1.5 20.0 6.1 0.30 12.2 29 1,99 FM, VK303 Min. Height Max Listed 2 Tested 3 Sprinkler Approval 6.0 1.8 20.0 6.1 0.30 12.2 29 1,99 FM 1 This chart shows approvals available at the time of printing. 2 Density indicated is minimum application density required per FM5130 Standard for Extinguishing Systems. This density cannot be reduced.

Page 4 of 11 1%S C6 3%S C6 3%M C6 0.16 6.5 7 0,48 UL 0.22 9.1 7 0,48 UL VK377, 0.32 13.0 7 0,48 UL 16.8 241.9 VK580 -- 0.46 18.9 7 0,48 UL 0.16 6.5 7 0,48 UL 0.22 9.1 7 0,48 UL VK377, 0.32 13.0 7 0,48 UL 16.8 241.9 VK580 -- 0.46 18.9 7 0,48 UL HYDROCARBON FUELS Listed 2 0.16 6.5 7 0,48 UL 0.16 6.5 7 0,48 UL 0.22 9.1 7 0,48 UL VK377, 0.32 13.0 7 0,48 UL 16.8 241.9 VK580 -- 0.46 18.9 7 0,48 UL 1 This chart shows listings available at the time of printing. 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced.

Page 5 of 11 * UP=Upright, PD=Pendent ALCOHOL - IPA Listed 2 0.22 (UP)* 0.16 (PD)* 9.0 (UP)* 6.5 (PD)* 14.5 (UP) 7 (PD) 0,99 (UP) 0,48 (PD) 0.29 11.8 12 0,83 UL VK377, 0.32 13 7 0,48 UL 16.8 241.9 VK580 -- 0.46 18.9 7 0,48 UL UL KETONE - ACETONE Listed 2 0.29 11.8 24 0,48 UL 0.32 13 15 0,48 UL VK377, 0.40 16.2 11 0,75 UL 16.8 241.9 VK580 -- 0.46 18.9 7 0,48 UL 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. FOMTEC FOAM HYDROCARBONS Listed 2 Enviro USP 5 -- VK2021 0.22 9.0 7 0,48 UL 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. 5 For fresh water use only.

Page 6 of 11 1% Viking - F20717 CG - C1B 3% Viking - F20718 CG - C3B 2.8 40.3 4.2 60.0 2.8 40.3 4.2 60.0 HYDROCARBON FUELS VK001, VK021, VK325, VK326, VK340, VK341 VK002, VK006, VK327, VK328 VK001, VK021, VK325, VK326, VK340, VK341 VK002, VK006, VK327, VK328 -- 0.16 6.5 29 2 UL / FM -- 0.16 6.5 12.8 0.89 UL / FM 0.16 6.5 7 0.48 UL / FM 0.22 9 7 0.48 UL / FM -- 0.16 6.5 29 2 UL / FM -- 0.16 6.5 12.8 0.89 UL / FM Listed 2 0.16 6.5 7 0.48 UL / FM 0.22 9.0 7 0.48 UL / FM VK377, 0.32 13.0 7 0.48 UL / FM 16.8 242.0 VK580 -- 0.46 18.7 7 0.48 UL / FM 3% - MS Viking - F20719 CG - C306-MS-C 3% AR- CG - C334-LV VK125, VK300, VK301, VK315, VK316 VK353 0.16 6.5 7 0.48 UL / FM 0.22 9.0 7 0.48 UL / FM 0.16 6.5 7 0.48 UL / FM 0.22 9.0 7 0.48 UL / FM VK377, 0.32 13.0 7 0.48 UL / FM 16.8 242.0 VK580 -- 0.46 18.7 7 0.48 UL / FM 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. New page issued.

Page 7 of 11 3% AR- CG - C334-LV ALCOHOL FUELS Listed 2 0.24 9.8 16 1.1 UL / FM 0.29 11.8 11.4 0.79 UL / FM VK377, 0.38 15.5 11 0.76 UL / FM 16.8 242.0 VK580 -- 0.55 22.4 9.4 0.65 UL / FM 3% AR- CG - C334-LV KETONE FUELS Listed 2.28/.30* 11.4/12.2* 22/26* 1.52/1.79* UL / FM 0.34 13.8 16 1 UL / FM VK377, 0.41 16.7 12 0.83 UL / FM 16.8 242.0 VK580 -- 0.55 22.4 9.4 0.65 UL / FM 3% AR- CG - C334-LV ETHER FUELS Listed 2 0.26 10.6 12 0.83 UL / FM 0.30 12.2 12.7 0.88 UL / FM VK377, 0.32 13.0 7 0.48 UL / FM 16.8 242.0 VK580 -- 0.46 18.7 7 0.48 UL / FM 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. * Where two values are given, the first value applies to upright sprinklers and the second value applies to pendent sprinklers.

Page 8 of 11 3% AR- CG - C334-LV ESTER FUELS Listed 2 0.21 8.5 12 0.83 UL / FM 0.26 10.6 9 0.62 UL / FM VK377, 0.35 14.2 7 0.48 UL / FM 16.8 242.0 VK580 -- 0.46 18.7 7 0.48 UL / FM 3% AR- CG - C334-*LV DENATURED ALCOHOL Listed 2 0.19 7.7 10.3 0.71 UL / FM 0.24 9.7 8 0.55 UL / FM VK377, 0.34 13.8 8 0.55 UL / FM 16.8 242.0 VK580 -- 0.46 18.7 7 0.48 UL / FM 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced.

Page 9 of 11 HYDROCARBON FUELS Listed 2 2.8 40.3 VK001, VK325 -- 0.16 6.5 30 2.06 UL NATIONAL FOAM Aer-O-Water C6 1% TM C6 Aer-O-Lite 3% Aer-O- Water 3EM C6 Universal Gold C6 1%/3% AR- 4.2 60.0 VK002, VK327 -- 0.16 6.5 13 0.89 UL 2.8 40.3 VK001, VK305, VK325 0.16 6.5 7 0.48 UL 0.22 9 7 0.48 UL -- 0.16 6.5 30 2.06 UL 4.2 60.0 VK002, VK327 -- 0.16 6.5 13 0.89 UL 0.16 6.5 7 0.48 UL 0.22 9.0 7 0.48 UL -- 0.32 13.0 7 0.48 UL 0.16 6.5 7 0.48 UL 0.22 9.0 7 0.48 UL 0.16 6.5 7 0.48 UL 0.22 9.0 7 0.48 UL -- 0.32 13.0 7 0.48 UL 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. * Where two values are given, the first value applies to upright sprinklers and the second value applies to pendent sprinklers.

Page 10 of 11 NATIONAL FOAM Universal Gold C6 1%/3% AR- ALCOHOL FUELS Listed 2 0.24/.21* 9.8/8.5* 16.5/12.5* 1.14/.86* UL 0.29 11.8 11.4 0.79 UL VK377, 0.42 17.1 12 0.83 UL NATIONAL FOAM Universal Gold C6 1%/3% AR- KETONE FUELS Listed 2.28/.30* 11.4/12.2* 22/26* 1.52/1.8* UL 0.34 13.8 16 1.1 UL -- 0.41 16.7 12 0.83 UL NATIONAL FOAM Universal Gold C6 1%/3% AR- ETHER FUELS Listed 2 -- 0.21 8.5 12 0.83 UL -- 0.26 10.6 9 0.62 UL -- 0.32 13.0 7 0.48 UL 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. * Where two values are given, the first value applies to upright sprinklers and the second value applies to pendent sprinklers.

Page 11 of 11 NATIONAL FOAM Universal Gold C6 1%/3% AR- ESTER FUELS Listed 2 -- 0.21 8.5 12 0.83 UL -- 0.26 10.6 9 0.62 UL -- 0.32 13.0 7 0.48 UL 2 Density indicated is minimum application density required per UL 162 - Equipment and Liquid Standard. This density cannot be reduced. * 8. INSTALLATION Refer to appropriate Installation Standards (i.e. NFPA, VdS, LPCB, etc.) and / or applicable FM Global Property Loss Prevention Data Sheets such as 4-12, -Water Sprinkler Systems. 9. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water or /Water Solution flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 10. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly. 11. INSPECTION, TESTS AND MAINTENANCE Refer to respective requirements, according to the relevant standards for Inspection, Testing and Maintenance. Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. If applicable, refer to FM Global Property Loss Prevention Datasheet 4-12 for specific test and commissioning criteria. In addition, the Authority Having Jurisdiction (AHJ) may have additional maintenance, testing and inspection requirements that must be followed. WARNING Any system maintenance or testing that involves placing a control valve or detection system out of service may eliminate the fire protection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected areas. 12. DISPOSAL At end of use the product described here should be disposed of via the national recycling system. 13. ACCESSORIES AND SPARE PARTS Please refer to relevant sprinkler data page. Replaces Form No. F_091316 Rev 18.1 (Added P65 Warning.)