Esmi Sense FDP Fire detection panel with ALC2 loop controller

Similar documents
CONTROL PANELS. Tech Data Sheet D01688GB1 10/2012 Fire Detection. Control Panels of the FX 3NET (ALC) Fire Detection System

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual

FX FIRE DETECTION SYSTEM

Installation, Operating and Maintenance Manual

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

Home center Interface Server. Technical sheet

Added password for IP setup page : Password must be in IP format!

SUPREMATouch Modular Fire & Gas Detection System

Fire control panel for modernization

ZXSe Range Data Sheet

On the job around the clock 24/7: Fire detection systems

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

Labkotec Ice Detector

Smart Wireless Sensor

TS400. Operating Manual. Test Station for Microtector II Series (G450/G460)

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

Fire control panel detect 3004 plus and accessories

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008

Manual & Technical Documentation V1.1

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

IntesisBox BACnet/IP Server - Notifier ID3000 series

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

For Complete Fire and Gas Solutions

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

Fire control panels FC360

Fratech Multipath-IP

Multi-Gas-Controller MGC2

Networked Access Control Panel. Installation Guide

Reliably Advanced Extinguishing Control

SET-2000 Hi Level/Oil

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

Fire and Gas Monitoring Panel ST7-HV

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

RAYCHEM NGC-30 COMPONENTS

Excel-EN Conventional Fire Control Panel

Different types of Fire Alarm System

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

SUPREMATouch. Modular Fire & Gas Detection System

Solution F2. Fire Alarm Control Panels one step ahead.

Intelligent addressable fire alarm control panel

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3

Vocia VACIE. Reference Guide

Smart Wireless Sensor

Fire control panels FC726 FC726-XA

APPLICATION DATA SHEET

VACIE REFERENCE GUIDE REVISION 1.2.6

Reliably Advanced Extinguishing Control

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

G SERIES: Security INTEGRATION as you want it. Greater expansion, communication, video integration, system resilience, and automation.

Measuring Recording Online Monitoring Regulation Alarming

NU2 Smart Power Supply (SPS) Manual

SUPREMATouch. Modular Fire & Gas Detection System

Intelligent Single Loop Fire Alarm Control Panel

EXICALL EN70 EXICALL EN70MR EXICALL EN70-ATEX

Fire alarm system EBL512 G3

FEC400 Series. Installation Manual

Halton SAFE / 7.14 user guide and installation instructions

AE-CU Adaptive Escape Routing for Emergency Lighting. From static to adaptive escape routing

Bionics Instrument. Alarm Handling. Gas Alarm Systems

FC722 Fire control panel

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Technical Speci fications 220V AC 50Hz or 110V AC 60Hz Accessories operational voltage. 2x 12V / 7Ah sealed lead acid gel batteries

Instruction Manual Model Backup Switch, 1 for 8

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly

ModBus DE-1 INSTALLATION AND USER MANUAL

FX NET. Advanced fire protection

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

SCAN200E USER S MANUAL

FX FIRE ALARM SYSTEM (ALC) Planning Instructions

561-MB256 plus. Intruder alarm control panel. Performance features

Typical applications include the vibration detector. Detection of vibrations and shocks

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

ECO N DATE DESCRIPTION OF CHANGE CHG

BSR Addressable Fire Detection control panel. Installation operation manual

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Wireless Fire & Security Solutions. Fire Product Showcase

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions

LevelSET S GSM Functionalities Instructions for Commissioning and Use

Installation Manual COPYRIGHT NOTICE

Advanced FireAlarm Panel 1-4Loop

Operations Manual TS400. Test Station for G450/G460 Gas Detector

UNC100 Integra Manual

FIRElux Emergency Lighting

Standard Devices. Electronic Alarm Indication Systems. ME 3011b

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

For more than 35 years METOR metal detectors have been leading the way in the industry. Once again, METOR is setting new standards in metal detection.

DAP III Zone Master User s Guide

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

RACK MONITORING SYSTEM - RAMOS Ultra

APPLICATION DATA SHEET

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

Intelligent 2 & 4 Loop Fire Alarm Control Panels

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

SCR100 User Manual. Version:1.1 Date:Dec 2009

Transcription:

Esmi Sense FDP Fire detection panel The intelligent and modular Esmi Sense FDP fire detection panel provides multiple new features for efficient and reliable fire safety. The Esmi Sense FDP fire detection panel comes in three different models: FDP221, FDP252 and FDP292. You can connect the Esmi Sense FDP fire detection panel to the EcoStruxure Fire Expert online application and the full range of Schneider Electric s intelligent and conventional detectors can be connected to FDP. Esmi Sense FDP is compatible with other fire detection equipment, such as: Fireman s panel FMP2 Zone led panel ZLPX Alarm delay panel DAP2 Multipurpose controller MOX Alarm management system ESGRAF Figure 1. Esmi Sense FDP fire detection panel Esmi Sense FDP also provides an integration server interface, which enables integration to the building management system. Page 1 of 14 2017.

Table 1. Esmi Sense FDP fire detection panel specifics FDP221 FDP252 FDP292 Product code FFS00703910 FFS00703920 FFS00703930 Addressable loops 1 4 1 8 1 8 Addressable loop controller AL2 Max addresses on the addressable loop 126 Dimensions (H x W x D) [mm] 360 x 430 x 142 580 x 430 x 142 Weight (without batteries) [kg] 6.6 10.6 11.1 IP rating Ambient operating temperature [ ] Ambient storage temperature [ ] Maximum ambient humidity Frame material over material over colour IP30 +5 +40 +0 +50 94% RH (non-condensing) sheet steel / plastic plastic NS S 1005-R80B Frame colour NS S 7502-B Mains supply voltage Mains supply power Operating voltage range Maximum current consumption in standby condition Maximum current consumption in alarm condition Applied standards 230 Vac ±10% / 50...60 Hz 165 VA 19...30 Vdc 1.0 A at 24 Vdc 4.8 A at 24 Vdc EN54-2, EN54-4 Optional circuit board slots 2 5 9 Batteries 2 x 12 Ah 2 x 17 Ah * ompatibility fireman's panel (FMPX or FMP2) protocol repeater (REPX or REPX-OB) delay alarm panel (DAPX or DAP2) logical controller (MOX or MOX-OB) LED panels for fire zones (ZLPX) * Install the batteries for FDP292 in a separate battery cabinet. Page 2 of 14 2017.

Figure 2. The components inside the Esmi Sense FDP fire detection panel A FDP221 1 MU unit B FDP252 2 PS2 power supply FDP292 3 Batteries 4 Optional circuit board slots Table 2.onstruction of the Esmi Sense FDP fire detection panel omponent FDP221 FDP252 FDP292 Notes Default components User interface 1 1 1 MU master controller unit 1 1 1 PS2 power supply 1 1 1 Optional circuit board slots 2 5 9 Optional circuit boards AL2 loop controller 0 2 0 4 0 4 L line controller 0 2 0 4 0 4 IO control unit 0 2 0 4 0 4 OA control unit 0 2 0 4 0 4 Max 4 controllers in total. Order number FFS00702519. Max 4 controllers in total. Order number FFS00702512. Max 4 control units in total. Order number FFS00702530. Max 4 control units in total. Order number FFS00702531. REPX-OB protocol repeater 0 1 0 1 0 1 Order number FFS00703833. MOX-OB logic control unit 0 1 0 1 0 1 Order number FFS00703835. ZLPX-I zone LED panel 0 1 0 1 0 1 Order number FFS00703841. Page 3 of 14 2017.

omponent FDP221 FDP252 FDP292 Notes Optional plugins for MU master controller unit INFO plugin with RS485 0 1 0 1 0 1 Order number FFS00702523. Network plugin with 2 RS485 ports Network plugin with 2 Ethernet ports 0 1 0 1 0 1 Order number FFS00702524. 0 1 0 1 0 1 Order number FFS00702525. Figure 3. Terminals on the MU unit 1. MicroSD card 2. Micro USB 3. PO 4. MO 5. O3 6. O2 7. O1 8. IN2 9. IN1 10. Ethernet 11. USB 1, USB 2 Option A: INFO device 12. INFO plugin with RS485 Option B1: RS485 (SYS1) + RS485 (SYS2) 13. Network plugin with 2 RS485 ports Option B2: Ethernet (IN) + Ethernet (OUT) 14. Network plugin with 2 Ethernet ports Table 3. Terminals on the MU unit Terminal onnector symbol Function Description PO 24 V - Power supply out (-) 24 V power supply for external devices. 24 V + Power supply out (+) Short-circuit protection, max. 500 ma MO - Monitored output line (-) Fire alarm device line as default (monitored). You can set other functions + Monitored output line (+) with the Fire Expert configuration tool. O1 N lean contact output 1 N Fire alarm router output (default). You lean contact output 1 can set other functions with the Fire Page 4 of 14 2017.

Terminal onnector symbol Function Description lean contact output 1 Expert configuration tool. Max 30 Vdc/1.0 A. O2 lean contact output 2 Fault warning router output (default). The relay is energized in normal lean contact output 2 condition (drawn) and releases in case N lean contact output 2 N of fault. You can set other functions with the Fire Expert configuration tool. Max 30 Vdc/1.0 A. O3 N lean contact output 3 N Fire alarm output (default). You can set other functions with the Fire Expert lean contact output 3 lean contact output 3 IN 1 + lean contact input 1 Fault in fire alarm router (monitored and - normally open as default). You can set other functions with the Fire Expert configuration tool. IN 2 + - lean contact input 2 Fault in fault warning router (monitored and normally open as default). You can set other functions with the Fire Expert configuration tool. Ethernet none LAN configuration, connection to Fire Expert and service. USB 1 none onfiguration and software update. USB 2 none Spare port for future development. Micro USB none Maintenance. MicroSD none The FDP user interface and software are stored on the MicroSD card. Do not remove the MicroSD card under any circumstances. Optional plugins: 2 x RS485* 2 x Ethernet* T/R + Transmit/Received Data + Network plugin (RS485). Serial communication to FDP/FX network. T/R - Transmit/Received Data - Order number FFS00702524. Gnd Ground none Network plugin (Ethernet). onnection to FDP network. Order number FFS00702525. 1 x RS485 T/R + Transmit/Received Data + INFO plugin (RS485). Serial communication to INFO devices. Order T/R - Transmit/Received Data - number FFS00702523. Gnd Ground * The MU unit has room for either the 2 x RS485 OR 2 x Ethernet plugin. Both plugins cannot be installed on the same circuit board. Page 5 of 14 2017.

Figure 4. Terminals and fuses on the PS2 power supply 1. Terminals for the battery monitoring device 2. Battery fuse, 6.3 A 3. Power outputs PO1 and PO2 (24 V) 4. Battery start button 5. Terminal for the battery cable 6. Battery temperature sensor 7. Mains terminal 8. Factory assembly adjustment only Table 4. Terminals and fuses on the PS2 power supply Terminal onnector symbol Function Description Battery monitoring device BATT MON 1 4 Terminals for the battery monitoring device. If you install the optional battery monitoring device, FDP gives a fault warning if batteries are disconnected or removed. One battery monitoring device monitors one pair of batteries. PO1 24V- Power supply out - 24 V power supply for external devices. 24V+ Power supply out + Short-circuit protection, max. 4A. PO2 24V- Power supply out - 24 V power supply for external devices. 24V+ Power supply out + Short-circuit protection, max. 4A. Mains fuse - Mains fuse (T4A/ 250V) The mains connection is protected with a T 4 A fuse (only replaceable by service personnel) Battery fuse Fuse T 6.3 Battery fuse (T6.3A/ 250V) The battery connection is protected with a T 6.3 A fuse. NT NT Temperature sensor Monitors the ambient temperature around batteries. Battery BATT - Battery - Battery connection (back-up power) BATT + Battery + Mains N Neutral Mains connection L Ground Live Ground Page 6 of 14 2017.

Figure 5. Terminals on the AL2 circuit board 1. Addressable loop 1 2. Addressable loop 2 3. PO2 4. PO1 The AL2 circuit board (order number FFS00702519) is an optional feature. Table 5. Terminals and fuses on the AL2 circuit board Terminal onnector symbol Function Description PO1 - Power supply out - 24 V power supply for external devices. Short-circuit protection, + Power supply out + max. 500 ma. PO2 - Power supply out - 24 V power supply for external devices. Short-circuit protection, + Power supply out + max. 500 ma. Addressable loop 1 Addressable loop 2 B - Addressable loop return - Addressable loop for AL2 addressable detectors and devices. B + Addressable loop return + Max. 126 addresses. A - Addressable loop outgoing - A + Addressable loop outgoing + B - Addressable loop return - Addressable loop for AL2 addressable detectors and devices. B + Addressable loop return + Max. 126 addresses. A - Addressable loop outgoing - A + Addressable loop outgoing + Page 7 of 14 2017.

Figure 6. Terminals on the L circuit board 1. 16 conventional line terminals The L circuit board (order number FFS00702512) is an optional feature. Table 6. Terminals and fuses on the L circuit board Terminal onnector symbol Function Description 16 conventional line terminals - onventional line - onnection for conventional detectors and other conventional devices. + onventional line + onventional lines can be configured as input lines. Page 8 of 14 2017.

Figure 7. Terminals on the IO circuit board 1. IN4 2. IN3 3. IN2 4. IN1 5. O2 6. O1 7. PO2 8. PO1 9. MO4 10. MO3 11. MO2 12. MO1 Table 7. Terminals on the IO circuit board Terminal onnector symbol Function Description IN1 + lean contact input 1 Fault warning, normally closed (default). - You can set other functions with the Fire Expert configuration tool. IN2 + lean contact input 2 Fault in extinguisher, normally closed - (default). You can set other functions with the Fire Expert configuration tool. IN3 + lean contact input 3 Extinguisher activated, normally open - (default). You can set other functions with the Fire Expert configuration tool. IN4 + lean contact input 4 Smoke vents activated, normally open - (default). You can set other functions with the Fire Expert configuration tool. O1 N lean contact output 1 N Fire alarm output (default). You can set other functions with the Fire Expert lean contact output 1 lean contact output 1 O2 lean contact output 2 Fire alarm output (default). You can set other functions with the Fire Expert lean contact output 2 configuration tool. Max 30 Vdc/1.0 A N lean contact output 2 N PO1 24 V - Power supply out (-) Power supply 1. 24 V power supply for external devices. 24 V + Power supply out (+) Short-circuit protection, max. 500 ma Page 9 of 14 2017.

Terminal onnector symbol Function Description PO2 24 V - Power supply out (-) Power supply 2. 24 V power supply for external devices. 24 V + Power supply out (+) Short-circuit protection, max. 500 ma MO1 - Monitored output line 1 - Fire alarm device line as default (monitored). You can set other functions + Monitored output line 1 + with the Fire Expert configuration tool. MO2 - Monitored output line 2 - Max 500 ma each. + Monitored output line 2 + MO3 - Monitored output line 3 - + Monitored output line 3 + MO4 - Monitored output line 4 - Fault warning device line as default (monitored). You can set other functions + Monitored output line 4 + with the Fire Expert configuration tool. Max 500 ma each. Figure 8. lean contact outputs on the OA circuit board 1. 16 clean contact outputs Table 8. Terminals on the OA circuit board Terminal onnector symbol Function Description O1 O2 N lean contact output N Fire alarm output. You can set other functions with the Fire Expert lean contact output lean contact output O3 O4 N lean contact output N Fire door output. You can set other lean contact output functions with the Fire Expert lean contact output Page 10 of 14 2017.

Terminal onnector symbol Function Description O5 O6 N lean contact output N Pre-alarm output. You can set other lean contact output functions with the Fire Expert lean contact output O7 O8 N lean contact output N Technical alarm output. You can set other functions with the Fire Expert lean contact output lean contact output O9 O10 O11 O12 O13 O14 O15 O16 N lean contact output N Fault warning output. You can set other functions with the Fire Expert lean contact output configuration tool. Max 30 VDdc1.0 A. lean contact output N lean contact output N Maintenance warning output. You can lean contact output set other functions with the Fire Expert lean contact output N lean contact output N Disablement output. You can set other functions with the Fire Expert lean contact output lean contact output N lean contact output N Access level 2 output. You can set other lean contact output functions with the Fire Expert lean contact output Page 11 of 14 2017.

Security annex Purpose of network connectivity The Esmi Sense FDP Fire detection panel supports centralized configuration management and remote monitoring and operation using the EcoStruxure Fire Expert online solution. In order to enable the remote management capabilities, the panel needs to have access to an Internet connection, and has to be registered in the EcoStruxure Fire Expert service during commissioning, as described in the EcoStruxure Fire Expert User manual. Technical requirements for the Internet connection When using the customer s own network connection instead of the bundled mobile data solution, the connectivity must meet the following criteria: A DHP service must be available for the panel, providing an IP configuration that is able to look up and contact the EcoStruxure Fire Expert service at the address gatewayfdp.esmifire.com The client must be able to connect Fire Expert directly. The service is listening to TP port 443. All connections are outbound and initiated by the FDP, no inbound port openings are required. Page 12 of 14 2017.

Only the connector Ethernet onnection to EcoStruxure Fire Expert and maintenance must be used for Internet connectivity. Refer to the product installation documentation to identify the correct physical connector in the unit. Security principles The panel uses its internet connection only for contacting the management services provided by EcoStruxure Fire Expert over secured connections. The panel will not contact any third-party systems or accept any incoming connections. onnections between FDP and EcoStruxure Fire Expert are encrypted and use certificates for endpoint authentication. The management interface uses only the external Ethernet interface and has been isolated from fire detection core features, which operate independently of any online features. Unavailability of the Internet connectivity or malicious traffic in the external network do not affect the core functionality of the panel.. WARNING ertain hardware configurations have additional Ethernet ports for inter-panel connectivity. These interfaces are reserved for this purpose only. Do not connect these ports to any LAN set up for another purpose and never connect any unsupported devices to the FDP dedicated network. Although the panel s interfaces have been secured against malicious traffic, the load caused by unsupported devices could affect the core features. The panel does not provide remote shell access and does not have any default OS level accounts. The network interface has been hardened and firmware distributions include security patches available at release time. Schneider Electric will provide fixes to vulnerabilities discovered in components used, but installation of fixes requires that changes are approved by owner. In order to ensure the security of the panel, the person responsible for managing the panel must acknowledge and deploy the fixes in a timely manner. If the responsibility of installing security patches has not been assigned, the manufacturer cannot assure the security of the connection and it is not safe to connect the panel to the Internet. Security of the EcoStruxure Fire Expert cloud services EcoStruxure Fire Expert is a multitenant SaaS service built on the Microsoft Azure cloud platform and relies on security solutions provided by the platform. For more information on the technology, refer to Microsoft Azure security documentation. The access control model of the service is based on the ownership of data and role-based permissions. Each customer has access to only their own data. Transfer of customer data over the Internet uses only secure connections. Page 13 of 14 2017.

0402 P.O. Box 415 FI-02601 Espoo, Finland For models: FDP221, FDP252, FDP292 Declaration of performance: 0402-PR-S0154-17, 0402-PR-S0155-17 European standard EN 54-2:1997/A:1999/A1:2006 EN 54-4:1997/A:1999/A1:2002/A2:2006 ontrol and indicating equipment for fire detection and fire alarm systems for buildings FDP221, FDP252, FDP292 Provided options: 7.8; 7.9.1; 7.10.3; 7.11; 7.12.2; 7.13; 8.3; 8.4; 8.9; 9.5; 10 Related documents: D01778 Esmi Sense FDP Fire detection panel with SL loop controller data sheet, D01779 Esmi Sense FDP Fire detection panel with AL2 loop controller data sheet, O1884 Esmi Sense FDP Fire detection panel User manual, O1885 Esmi Sense FDP Fire detection panel Installation and commissioning manual, O1889 Esmi Sense FDP Fire detection panel Maintenance manual 2018 Schneider Electronic Fire & Security Oy. Unauthorized copying and lending are prohibited. Tel: +358 10 446 511 Page 14 of 14 2017.