TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Similar documents
TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS. David Grassl PE Mechanical Engineer Principal

Best Practices for Condensing Boilers

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: CONDENSING BOILER SYSTEM MYTH BUSTING. David Grassl PE Mechanical Engineer Principal

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

CLEARFIRE HIGH-MASS CONDENSING FIRETUBE BOILER 500 TO 2,000 MBH

The world s standard in efficiency. CBEX FIRETUBE

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

GEOTHERMAL DESIGN GUIDE

CCLEARFIRE CONDENSING FIRETUBE BOILER DESIGNED FOR MAXIMUM HYDRONIC SYSTEM EFFICIENCY 500 TO 3,300 MBTU

HYDRONIC SOLUTIONS. More than just hydronic boilers, we offer the most efficient integrated hydronic solutions on the market.

Medium Mass Boilers. Maxim Power VT

MECHANICAL SCIENCE Module 2 Heat Exchangers

FLX FLEXTUBE. The Widest Range of Hydronic and Steam Watertube Boiler Systems 1,500 to 25,000 MBTU/HR (35-600HP)

CHP-turbine room. CHP can capture almost EXTRACTED STEAM 20 PSI HIGH-PRESSURE STEAM 1250 PSI HEAT EXCHANGER HOT WATER SUPPLY F

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

- Essay Control Functions and Benefits

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

ENERGY RECOVERY SOLUTIONS. Recover wasted energy to increase efficiency and save money immediately.

Cclearfire HIGH EFFICIENCY, COMPACT CONDENSING BOILER 500-3,300 MBTU

THERMAL ICE STORAGE: Application & Design Guide

Efficient Steam System Design

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

clearfire Large capacity condensing boilers 4,000 to 12,000 MBTU/hr

Applications and Piping Strategies for Condensing Boilers - Introduction

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Ohio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m.

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

Infi niti Tankless. Water Heater Series Featuring SRT (Scale Reduction Technology) Built to be the Best

MODEL M5M. High-Efficiency Packaged Watertube Boiler MMBTU

The Book of AERMEC NRL Sequence of Operation

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

BOILER APPLICATION GUIDE for:

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Geothermal Heating and Cooling Using Ground Source Heat Pumps. Prepared by: Steven Forrester, P.E. Principal

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems

Daikin Blueprint: Delivering Hot Water with a Chiller

Energy-Efficiency Measures List

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work

HVAC Water chiller selection and optimisation of operation

Radiant Heating. Systems

Geothermal Heat Pump Systems

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

Challenges and Methods of Estimating a Conceptual HVAC Design

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

Mechanical Vacuum Systems for Secondary Metallurgy Steel Degassing

KE2 EvaporatorEfficiency Theory of Operation

HCLEARFIRE. High-efficiency, modular steam boiler HP

Dehumidifying with Dedicated Outdoor Air

Chilled Water system

Ecoforest. Innovating from the beginning. Foundation of the company. Creation, innovation stars 1968

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

A TRUE GAME CHANGER - The Vortex Heat Recovery Center CONDENSING EFFICIENCIES FOR TRADITIONAL BOILERS & HEATERS

Gas condensing boiler UltraGas

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

Outdoor Reset Control Theory FULL versus PARTIAL reset

Air Conditioning and process cooling Energy Components at a Glance

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

Commercial and Residential Water Source Heat Pumps Boiler/Tower and Geothermal Applications

Heat pump and energy recovery systems

CO2 TRANSCRITICAL BOOSTER SYSTEMS

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

Home Builder Product Selection Guide

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS

Air conditioning and chillers. Customized heat transfer solutions

Refrigeration Systems and Accessories

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

PROFIRE -E SERIES BURNERS

Massachusetts Energy Efficiency Partnership. 5. High Efficiency Systems for Large Boilers

CGAM air-cooled scroll chiller. Highly efficient, yet extremely quiet

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

Get The Edge Over The Competition with The Summit

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

CONTROLLED CHILLED BEAM PUMP MODULE

- Data Brochure Universal Reset Module 422

New standard in compressed air treatment, providing Energy Savings up to 99%

Chapter 11 REFRIGERATION CYCLES

COMcheck Software Version Review Mechanical Compliance Certificate

THE GEOTHERMAL CONCEPT

- Data Brochure Universal Reset Control 364

INDUSTRIAL WATERTUBE BOILERS

Appendix 13. Categories of Cooling and Heating systems

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Residential heating and domestic hot water. Customized heat transfer solutions

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Removal of Non-condensable Gases and Air Is Critical In A Steam System

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone

Transcription:

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal

Similar to traditional boiler systems, condensing boiler systems have many designs they can operate within as they are built to handle a range of hot water temperatures. The best application for condensing boilers, though, is one that utilizes a lowtemperature, hot water design because it facilitates condensing that yields efficiency gains. In addition, most condensing boilers in these types of applications warrant only a simple piping configuration that avoids mixing valves, which is beneficial because mixing valves ultimately raises the hot-water- return temperature back to the boiler above the condensing point. This paper will discuss how incorporating condensing boilers into non-traditional systems and designs can lead to better system efficiency. WATER SOURCE S In the push toward energy efficiency, water-source, heat-pump systems should be considered as energy can be transferred from zone-to-zone to be reused instead of expending new energy to heat or cool the zone. This form of energy recovery is highly efficient and also provides the ability to independently control each zone based on heating or cooling demand. Each zone consists of a heat pump, which is a self-contained heating and cooling unit, that utilizes the vapor compression cycle with a refrigerant-to-air heat exchanger and a refrigerant-to-water heat exchanger. This creates two heat-exchange coils that operate as either the condenser or evaporator, and each coil is dependent upon the heat-pump mode of operation. The heat pump also has a compressor, expansion valve, and a reversing valve that allows the refrigerant flow in the heat pump to change directions based on the mode of operation. In this system, the refrigerant-to-water coil uses a water source that is distributed throughout the building to either pull heat from the loop or reject heat to the loop for space heating or cooling purposes as shown in Figure 1. Figure 1: Typical heat pump operation using a water loop for heat addition or heat rejection. WATER OUT WATER IN COOL AIR TO DISTRIBUTION SYSTEM WATER OUT WATER IN WARM AIR TO DISTRIBUTION SYSTEM REFRIGERANT TO AIR REFRIGERANT TO AIR EXPANSION VALVE EXPANSION VALVE REFRIGERANT TO AIR REFRIGERANT TO AIR 4-WAY REVERSING VALVE FAN 4-WAY REVERSING VALVE FAN SYSTEM LOOP COMPRESSOR SYSTEM LOOP COMPRESSOR WATER SOURCE COOLING CYCLE WATER SOURCE HEATING CYCLE By operating in this configuration, the heat-pump system provides continuous heat recovery throughout the building and assumes the building has the need for simultaneous heating and cooling. The intent of the water loop is to maintain the temperature within a range of approximately 60 F to 90 F for the heat pumps to be able to utilize the loop based on the individual space needs. A heat source is added to increase the amount of heat to the loop to maintain the loop temperature: (1) when the loop temperature drops below the predetermined temperature during periods of high-heating demand at design load, (2) when the spaces needing heat exceed the amount of heat available from the cooling units, or (3) during morning warm-up. Similarly, the system typically utilizes a closed-circuit cooling tower to reject heat from the building during periods of high cooling demand as shown in Figure 2. 2

Figure 2: Water source heat pump system piping configuration. BOILER COOLING TOWER SYSTEM PUMPS BOILER PUMP COOLING TOWER PUMP SYSTEM LOOP The methods of pumping and piping can be debated, but regardless of the method used, a boiler is typically added to increase heat to the system. Since the water temperature in the heat-pump loop is medium-grade, the need for a high water temperature from a standard, non-condensing boiler is unnecessary and wasteful as it overheats the loop temperature. The system also has a strong need for modulation due to the wide variation in load that matches well with a condensing boiler, which can provide high turndown at the desired water temperature. Similarly, a condensing boiler does not require mixing valves to maintain the hot water temperature above the condensing temperature of the fl ue gases as required for noncondensing boilers, making them a good fi t with less complexity. A comparison of the piping requirements for a condensing and non-condensing boiler in a water-source, heat-pump system can be viewed in Figure 3. Figure 3: Piping configuration for condensing vs. non-condensing boilers in a heat pump system. TO SYSTEM CONDENSING BOILER SCHEMATIC TO SYSTEM NON-CONDENSING BOILER SCHEMATIC MAIN SYSTEM PUMPS MAIN SYSTEM PUMPS BALANCE VALVE BYPASS PIPING COMMON PIPE COMMON PIPE BOILER PUMP BOILER PUMP FROM SYSTEM FROM SYSTEM 3

GEOTHERMAL S Geothermal heat pumps operate in the same manner as water-source heat pumps with a ground, geothermal well, or a body of water such as a lake or pond acting as the heat sink/source for the system in lieu of a boiler and/or cooling tower. For this type of system, the fi rst cost of a geothermal well fi eld may be cost prohibitive due to the capacity required to satisfy the entire load. In this instance, adding a condensing boiler can be a viable option as a peak shaving device when the capacity of the geothermal fi eld is limited and does not handle the entire load, allowing the remaining portion of the load to be handled by the boiler. HYBRID (CONDENSING & NON-CONDENSING) SYSTEMS A hybrid system is a system that consists of both condensing and non-condensing boilers in the same system. Due to the more robust construction of a condensing boiler as well as the materials necessary to protect it from the acidic condensate, a condensing boiler is more expensive compared to a similar-sized non-condensing boiler. If the cost for a fully condensing boiler plant exceeds the budget, the best approach is a hybrid system that can use the advantages of each system to its benefi t based on the hot water return temperature. Hybrid applications also work well in retrofi t applications, where a legacy, non-condensing boiler is maintained for design-load days, while a more effi cient condensing boiler is utilized whenever possible. In addition, a hybrid solution is an excellent one for a boiler plant that requires #2 fuel oil back-up because condensing boilers are best suited for operating on natural gas or propane while non-condensing boilers can be operated as dual-fuel. In a hybrid system, condensing boilers should be positioned upstream of non-condensing boilers, as shown in Figure 4. This allows the condensing boilers access to the lowest hot water return temperature, enabling them to operate in the condensing mode for maximum effi ciency. If additional heat is needed above the capacity of the condensing boilers, the non-condensing boiler can provide it, given that it has a higher hot water return temperature to prevent the boiler from condensing and subsequent damage. Also, this confi guration is very benefi cial during low loads as the condensing boiler can be used as the fi rst boiler to operate based on hot water reset conditions or when lower hot water supply temperatures can provide the required capacity for the system. Figure 4: Typical piping configuration for a hybrid system with the condensing boilers upstream of the non-condensing boiler. OUTSIDE AIR CONDENSING HEADER CONDENSING HYDRONIC NON-CONDENSING HYDRONIC PUMP SUPPLY WATER RETURN WATER SYSTEM PUMPS RETURN WATER IN CONTROL COMMUNICATION RETURN WATER SUPPLY WATER SUPPLY WATER OUT 4

HEAT RECOVERY CHILLER SYSTEMS Heat-recovery chiller systems, or high-lift chiller applications, also can be used with condensing boilers as the systems complement one another, similar to a hybrid system. In this application, the intent of the heat-recovery chiller is to provide hot water at a temperature high enough to heat the building, whereas a condensing boiler requires a low hot water return temperature to promote condensing. Utilizing both systems provides redundancy in operation when there is not the ability to run the heat-recovery chiller, which requires a constant cooling load to function properly. This configuration also provides fuel flexibility, enabling the system to operate with either the heat-recovery chiller or condensing boiler based on fuel price for the lowest operating cost. IN-FLOOR HYDRONIC RADIANT HEATING & SNOW-MELT SYSTEMS In-floor hydronic radiant heating is a relatively cost-effective way to provide heat that can be concealed architecturally within a space. In-floor heating requires a low hot-water-supply temperature in the range of 100 F to 120 F, an excellent condition for condensing boilers. Although hot water return temperatures naturally will be low, the temperatures will remain low by keeping the tubing spaced closely together, reducing the floor resistance, installing the tubing near the top of the slab, and providing insulation below the tubing. In addition to boiler-efficiency improvements, in-floor heating embeds the tubing within the slab, which conceals it from any damage. It also eliminates finned heat exchangers or enclosures that can corrode, become physically damaged, or need to be replaced over time. Snow-melt systems are similar to in-floor hydronic radiant systems in that hot water supply and return temperatures are very similar, but the tubing is used in exterior applications, and glycol often is used to prevent freezing within the piping system. Depending on the building s heating system, a plate-and-frame heat exchanger can be used to separate the snow-melt system loop from the main building heating system loop, or a dedicated boiler to the snow-melt system can be provided. DOMESTIC WATER HEATING The process for a domestic water heater is identical to the process for heating hot water in that fuel is burned and the combustion gases are removed through the exhaust flue, so a majority of the energy exits through the stack. In a condensing domestic water heater, a secondary heat exchanger exists within the water heater that allows the combustion gases to come in contact with the domestic cold water entering the water heater. This secondary heat exchanger creates additional surface area and removes the latent energy from the flue gases as they condense to heat the domestic water prior to discharging the exhaust to the atmosphere. Another method to create domestic hot water involves operating hydronic hot water boilers to heat domestic water in a storage tank with either a shell-and-tube or plate-and-frame heat exchanger. Because domestic hot water supply temperatures typically are around 120 F, this enables condensing on a regular basis. This is also a good application for a dual-return condensing boiler, which is discussed later in this paper. POOL HEATING Pool heating is similar to domestic water heating in that pool heat requires only low-grade heat to maintain the pool water temperature below 90 F, as shown in Figure 5. Return water temperatures leaving the heat exchanger can be near or at the temperature of the pool, meaning the return water temperature back to the boiler is ideal for condensing. Again, the low water temperature is a perfect application to utilize condensing equipment to recover the energy that would otherwise be wasted in the flue gases. Hot water for pool heating can be provided either with a condensing, domestic water heater or a condensing boiler with heat exchangers. Similarly, pool heating is a good application for a dual-return condensing boiler. Figure 5: Basic schematic of a heat exchanger being used for pool heating, snowmelt, or other process load. VSD SYSTEM PUMP M TO SYSTEM FROM SYSTEM TO POOL HEATER, SNOWMELT, PROCESS LOAD, ETC. 5

SERIES CIRCUIT WITH LOAD PUMPS Another unique system that is advantageous for condensing boilers is a series circuit with load pumps as shown in Figure 6. This system is a modifi ed primary-secondary system with pumped coils and common piping at each coil. In this confi guration, the coils do not have control valves, but are instead controlled based on the coil pump or injection pump in the secondary loop. Figure 6: Series circuit with load pumps. WHITE PAPER #3 FIGURE 5 COIL 1 COIL 2 SYSTEM PUMP COIL 3 COIL PUMP (TYP.) COIL 5 COIL 4 This confi guration requires the designer to size each coil slightly differently as the water temperature decreases the further away the coil is from the hot water production source, so the hot water supply to each coil is slightly lower than the previous coil. The benefi t of this arrangement is the cascading approach that enables an increased system T. For example, the coils at the end of the loop with the lowest hot water supply temperatures can be loads that require low-grade heat, as previously described, to further drive the hot-waterreturn temperature to the boiler as low as possible, which promotes additional condensing with increased effi ciency. DUAL RETURN Some boilers today are equipped with a dual-return capability that allows hot water return from two sources within the building, as shown in Figure 7. The intent of the dual return is to maximize the effi ciency of the boiler that might otherwise be lost due to mixing the hot water return from all sources in the system as some coils or building functions may have a high load and design T while other coils or functions may have a low load and small T. With a dualreturn system, if there are applications that utilize low hot water temperatures, similar to any of the systems mentioned earlier, this loop can be kept separate from the higher hot water return temperature loop back to the boiler. Then, the two return loops are piped to the boiler separately with the lower temperature hot water return loop piped into the boiler where it will come in contact Figure 7: Dual return system schematic wtih two temperature zones and domestic hot water. Load 1 Load 2 180 F 120 F 150 F 80 F with the cooler temperature fl ue gases, and the warmer hot water return loop is piped to the connection that comes in contact with the hotter fl ue gases to extend the condensing conditions. This dual- return approach promotes site-specifi c customization to optimize operation and condensing within the boiler that would otherwise be lost due to the system piping confi guration. Although this approach may use additional piping, the design strategy maximizes the condensing zone prior to blending the lower and higher return water temperatures within the boiler. In order to effectively use this piping setup, it is critical to keep the water loops separated and ensure that at least 10% of the fl ow be provided to the low-temperature connection. Depending on the boiler type and 180 F 150 F 80 F 10-30% of Total Load Make-Up Water Domestic Hot Water 6

pumping arrangement, check valves are potentially required on both return connections to prevent the reversal of flow to the other return loop. If pumping away from the boiler, check valves are likely not required. BUFFER TANKS As the design paradigm has shifted from non-condensing boilers to condensing boilers, another notable change in boiler design involves boiler mass or the water volume within the boiler, which was defined and discussed in the first white paper. Older boiler systems had a large system mass or volumes of water so the system could ride out rapid temperature changes within the system. Today, a majority of boilers are shifting to low mass with very little water volume in the boiler, which results in ( ) MANUFACTURER S RECOMMENDED MINIMUM MINIMUM MINIMUM BOILER BOILER SYSTEM CYCLE TIME OUTPUT LOAD MINUTES BTU/HR. BTU/HR. = DIFFERENTIAL WITHIN TANK boiler cycling, poor temperature control, and less-consistent system operation. The use of a buffer tank reduces the concern of boiler cycling during low loads (or no loads) and enables the system to ride out these potential temperature fluctuations. A buffer tank is nothing more than a tank within the piping configuration that adds mass back into the system. The buffer tank is full of water and helps store the excess energy in the system and prevent boiler cycling to provide better temperature control. Since boilers have a minimum run time and off time prior to restart, the tank acts as a buffer until the boiler can be turned back on again. To properly size a buffer tank, some system characteristics are important, including the boiler performance capabilities with the desired firing rates, and allowable temperature drop in the system to limit boiler cycling based on the manufacturer s requirements. If no guidelines are provided, it is recommended to limit cycling to less than five times per hour. Additionally, the minimum boiler output at the lowest turndown should be compared to the minimum heating load in the system. With these parameters, a buffer tank should be selected above the calculated tank volume, as defined in the equation below, to provide sufficient system mass. F X 500 TOTAL BUFFER TANK SIZE GALLONS Buffer tanks can be used in both variable-primary-flow systems and primary-secondary systems as the intent is to increase system volume. In a variable-primary-flow system, the tank can be located anywhere in the system, but is typically located near the boiler. In a primary-secondary system, the tank can act as the common pipe providing hydraulic separation between the primary and secondary loops, while also providing a location where air can be removed. This can eliminate the need for an air separator as the tank provides low velocities allowing air entrained in the system to be removed as shown in Figure 8. By effectively separating the distribution system flow from the boiler loop, a more constant delivery temperature can be achieved along with longer boiler operational cycles, which leads to reduced boiler cycling and increased system efficiency. The calculation for a buffer tank is something that should always be checked during the system design, but there may be some systems where a buffer tank is not required. For example, in a system with a high mass boiler, it is possible that the boiler itself may have enough mass, acting as the buffer tank, and negate the need for an additional tank in the system distribution piping. Figure 8: Buffer tank location for a primary-secondary system. PUMP SYSTEM LOAD BUFFER TANK PUMP SECONDARY PRIMARY This paper covered a variety of system applications that demonstrate the benefits of using a condensing boiler in the system design. In all designs with condensing boilers, the main goal is to maintain the minimum hot water return temperature to the boiler allowable by the system to operate in the condensing mode, thereby increasing energy efficiency and reducing costs. The next paper will detail additional advantages and disadvantages of condensing boiler applications. 7

Providing energy-efficient, environmentally friendly boiler room solutions Cleaver-Brooks is one of only a few boiler room solution providers in the world to operate a dedicated research and development facility. Having pioneered several industry-leading technologies, we remain just as committed today to introducing technology and products that enable a more energy-efficient and environmentally friendly generation of steam and hot water. We distribute our products through the Cleaver-Brooks Representatives Association, or CBRA, an alliance of independently owned and operated companies that provide boiler room products and service. CBRA companies can be counted on to provide Cleaver-Brooks products and parts, engineering support, customer training, technical service and system maintenance. To find a CBRA representative near you, please visit cleaverbrooks.com/reps. Boiler system icons are copyrights of Cleaver-Brooks, Inc. Packaged Boiler Systems 221 Law Street Thomasville, GA 31792 USA 800-250-5883 info@cleaverbrooks.com cleaverbrooks.com Printed in the USA 2017 Cleaver-Brooks, Inc CB-XXXX 1/17