RAGNAR STÅLSKOG AB INSTRUCTION MANUAL HVDC-H HVDC-L VOLTAGE DETECTOR HVDC-H, HVDC-L 15H11

Similar documents
TAG MR VOLTAGE DETECTORS AND ACCESSORIES. Instruction & Operation Manual

HIGH VOLTAGE A.C.(50 or 60Hz) CONTACT CAPACITIVE HIGH VOLTAGE DETECTOR

SAFETY PERSONAL AC VOLTAGE (50 or 60Hz) PROXIMITY DETECTOR

Instruction Manual. Self-Leveling Combination Cross-Line Laser and Five-Beam Laser Dot Model No &

Instruction Manual. Self-Leveling Combination Cross-Line Laser and Five-Beam Laser Dot Model No , &

275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO

HIGH VOLTAGE A.C. PROXIMITY DETECTOR HI-PROX

YELLOW JACKET. H 2 Tracer Gas Leak Detector. Operations Manual. Detects 5% H 2 in 95% Nitrogen Tracer Gas. Model 69341

Programmable Towel Radiator Manual

The Measure of Excellence in Electrical Testing

Visit us at

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

Your Pope Simple Set Automatic Tap Timer

English. Instruction and operation manual S 530. Leak detector for pneumatic systems

Instruction Manual. Self-Leveling Rotary Laser Level Model No &

Model ATD Refrigerant Gas Leak Detector. User Manual. Detects all CFC, HFC, HCFC, HFO Refrigerants including blends

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success

MANUAL Overflow sensor NVF-104/34-PF

Conductive Leakage detectors of the Leckstar range

LD900. User Manual. Refrigerant Gas Leak Detector. Detects all HFO, HFC, HCFC, and CFC Refrigerants including blends. Made in U.S.A.

F AN-ASPIRATED RADIATION SHIELD

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

MANUAL FOR MJK LIQUID SAMPLER 780

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

CLI Refrigerant Gas Leak Detector. User s Guide

Installation and user manual for the BiWire / Conventional Repeater Panel

THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER. Instruction Manual. Model AMB-12H

MANUAL Oil Level Sensor

Product Catalogue. Safety Equipment. Capacitive Voltage Detectors and Voltage Detection Systems

MODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

This instruction manual explains the use of three models listed on the left.

F AN-ASPIRATED RADIATION SHIELD

Insulation fault evaluator EDS460-DG

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

CD100A COMBUSTIBLE GAS DETECTOR

Connection set. Radiator connection set for thermostatic and manual operation Ø 12

SENTINEL A - Fault Passage Indicator

RD99 REFRIGERANT GAS LEAK DETECTOR WARNING!

Model: DC-159. Instruction Manual

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

CONTROL DEVICE SLIDETRONIC HD

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

English. Instruction and operation manual S 530. Leak detector for pneumatic systems

KitchenAid Food Stream Solutions Classic and Integrated Series

1.7. Insulation fault evaluators EDS460/490 EDS461/491

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

InBio X60 Series Access Control Panel User Manual

Hygro and Hygrothermo Transducers (capacitive) for climatic applications

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

SMOKE User Manual. NE v2.0

5, SE GÅNGHESTER,

Hygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring

User Manual - Energenie MiHome etrv

Sensistor XRS9012. Maintenance manual. Hy d r o g e n Leak Det e c t o r

INSTRUCTION MANUAL FOR ELECTRIC RADIANT INFRARED HEATERS

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Leak-Seeker I Refrigerant Leak Detector

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

Interface and EOL Modules 8

Instruction Manual. Self-Leveling Rotary Laser Level Model Nos and

Operating Instructions. Model: LD3 Dual Mode Refrigerant Gas Leak Detector ROBINAIR.COM

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

User Manual. Non-contact Infrared Thermometer.

Notices for installation

HMN-D2 Insert Series

Snifter ATEX22 VERSION. User Manual. Distributor

BAMOSOFT Control. Water hardness monitor INSTRUCTIONS MANUAL DUR. BAMOSOFT Control. Water hardness monitor / M1 01 C

We measure it. testo 316-Ex CH 4 testo 316-1

MANUAL AND INSTALLATION PROCEDURE PRODUCT APPEARANCE

Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

actoolsupply.com User Guide Extech RD300 Air Conditioning AC Refrigerant Leak Detector Refrigerant Leakage Detector Model RD300 actoolsupply.

BS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

OPR Power Series AC to DC POWER SUPPLY SERIES WITH REMOTE MANAGEMENT AND ALARM SYSTEMS. Model Nos. OPR200-24S / OPR200-24R. Manual

OilSET-1000 (12 VDC)

NON-CONTACT VOLTAGE DETECTOR WITH ADJUSTABLE SENSITIVITY AND IR THERMOMETER USER S MANUAL

SET-2000 Hi Level/Oil

Testing Emission Source ITES Operating Manual OM

USER MANUAL 04-0_MOD-KH1204US_H9 Objecto.indb _MOD-KH1204US_H9 Objecto.indb /06/29 15:02: /06/29 15:02:46

Sensor Interface Module Installation/Operation Instructions

USERS MANUAL EasySplicer

Lightning Warning System: LWS MK-II. User's Guide. KOREA EMI Technologies Co.,Ltd , Jangam-ri, Majang-myeon, Icheon-si, Gyeonggi-do, Korea

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex.

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

Operation and maintenance

Alarm system For oil-water separator

TERMO-Blok TERMO-Extra TERMO-Blok PTV

Dehumidifier. Instruction Manual. Model DH-320/A

Installation Guide for inbiox60 Series Access Control Panel

Fire Control Panel FS4000

Transcription:

RAGNAR STÅLSKOG AB INSTRUCTION MANUAL HVDC-H HVDC-L VOLTAGE DETECTOR HVDC-H, HVDC-L 15H11

Attention: Read this instruction manual carefully before using the detector. 1. FUNCTION / USE This device is designed to check absence or presence of nominal voltage by direct contact to the line. 2. SPECIFICATIONS Type: Direct contact DC voltage detector, 20-800 kv (refer to the label indication). Group*: III (indication of voltage present and permanent stand-by). Field of use: Outdoor all weather use (and indoor). Climatic category*: N (-25 C to +55 C, Humidity 20 to 96 %). Category*: L (without probe extension). Permanent stand-by mode. Built in All-check test feature provides checking of all electronic and battery level. Green light indicate that the unit is ready. Polycarbonate shell. Active and passive electrode of aluminium. Sound indication by beeper. Light indication by 1 red and 1 green LED. Dimensions: Ø 90 mm (housing). Universal (sunrise) adapter or RS adapter. Power supply: 4 pcs 1,5 V alkaline battery type LR6. Weight: 0,9 kg. *) Refers to EN-61243-1 (Live working - Voltage detectors - Part 1: Capacitive types to be used for voltages exceeding 1 kv a.c.) 3. OPERATION The HVDC-detector is to be checked, treated and served as a sophisticated measuring instrument and NOT as a tool must be kept clean and dry and avoid shocks and drops. - Before use, clean the detector including the electrodes with a soft cloth and check that scratches and holes are not occurring on the surfaces. - Clean all the part of the device if there is frost or condensation. 3-1 Insulating stick Each unit must be equipped with an insulating stick with the insulating length in accordance with applicable regulations. Can be fitted directly to insulating stick equipped with universal (sunrise) end fitting or RS end fitting (depends of the design of the passive electrode). 340 160 Red LED TEST Button Green LED Beeper 2

3-2 Preparation for field measurements Operator requirements The HVDC-detector operator is to have the knowledge and basic information of: A. The geographical area of the construction lines, and it s specific topography and surroundings. B. The date and time of any currency changes or breaks regarding the appropriate lines. C. Currency and voltage levels of subjects to be tested and the currency and voltage levels in the surrounding area. D. Any special arrangements regarding to the lines to be measured. Equipment requirements to be aware of before testing with HVDC-detector. A. The HVDC-detector has been inspected, clean and dry, with extension rods according to EN 61235/EN 60855. B. The HVDC-detector has been checked and approved by operator according to behaviour described in paragraph 3-3 (Self Test). Topographic requirement under and around lines subject to be measured. A. The area under the lines to be measured MUST be a flat, open space. B. The ground to stand on MUST be free from metal bars and rails. Electrical construction requirements close to the lines subject to be measured. A. The lines to be measured MUST be hanging free for several meters, there MUST NOT be any crossings, junctions or layers of other strange lines, bars or building objects around the spot chosen for the testing positions on the line. B. The lines to be measured MUST hanging separately and suspended from pole to pole. C. The detector MUST be located to the outside of parallel wire pairs when used. 3-3 All-check function (Self Test) This checking has to be done before and after any detection operation - By pushing the test button the red LED flashes and an intermittent signal sounds as long it is depressed. The green light indicates that the unit is ready. - When the test button is released the LED stops flashing and the signal stops. The green light will be lit during approximately 1.5 minutes and serves the purpose to confirm sufficient battery capacity. If 1.5 minutes are not achieved with the green diode (or the red diode constantly continues to flash and the signal sounds), replace the batteries. - If the replacement of the battery has no effect, please contact the company Ragnar Stålskog AB, rs@stalskog.se 3

3-3 Voltage detection operation After performing the test for correct functioning the device is ready for operation. A. The passive electrode of the detector must be laid over the wire or bar to be tested, while it is connected to the appropriate extension rod. (see picture). The active electrode must have sufficient air clearance. If the line is alive, the red LED flashes and an intermittent signal sounds. If the conductor is dead, only the green LED remains lit. B. After each test described above the detector must be carefully lowered to ground and the self test be repeated. C. The Voltage detection operation above has to be repeated three (3) times for each line, and the test position on the line must be changed about one (1) meter from both sides of the first test position of the line. After a period of approximately 1.5 minutes, the device is switched automatically to stand-by mode. For further tests, the test button has to be pushed again and the test for correct functioning has also to be repeated. The detector is ready for operation. 3-4 Product limitation of usability - The detector may NOT operate properly if surface is wet and/or dirty. The HVDC-detector surface MUST be kept dry and free from dirt and pollution s - The detector may NOT operate properly if methods and environments not fulfil the requirements from paragraph 3-2. - The detector may NOT operate properly due to mechanical shocks and/or electrode scratches and/or housing defects. The detector and peripherals MUST be controlled both electrically and mechanically every 6 years by Ragnar Stålskog AB. - The detector may NOT operate properly due to low battery charges. The detector batteries MUST be replaced with new batteries according to paragraph 4.1 - The detector may NOT operate properly under a voltage range different from the voltage range described for each detector. The HVDC-detector MUST not be used under other voltage ranges other than those described for each HVDC-detector in it s technical data sheet. 4

4-1 Battery replacement This operation must be carried out in a clean area. - Remove the passive electrode/rod connector. - Unscrew the active top electrode. - Push the electronic unit backwards out of the housing. - Replace batteries 4 x LR6 á 1,5 V Alkaline (twice a year is recommended). Important! Checking the polarity indicated by the sign + engraved on the battery holder. - Take care of the quality and position of the O-ring seal. Lubricate the seal with silicone grease. Top electrode Housing Passive electrode - Screw the top electrode holding firmly inside piece in position. Important! Never change the top electrode between different HVDC-tester (each top O-ring seal electrode is individual adapted to each tester). O-ring seal - Do not over tighten the top electrode. - Attach the passive electrode. - Check the device with the all check function. 4-2 Cleaning Cleaning of the polycarbonate shell with silicone impregnated cloth, excluding any solvent. 4-3 Special care - HVDC-H and HVDC-L are safety devices, they must be keep clean stored in a clean and dry area. Avoid shocks and drops. - When opening the unit (only for battery replacement) take special care of the cleanness of the inside: no dust, dirt or moisture, and check the quality of the seals. Any attempt to disassemble the unit or to have access to the circuit board is prohibited and shall release manufacturer from his guarantee duty. 5

5. MAINTENANCE 5-1 Storage Before each storage the HVDC-detector MUST be visually inspected for any damages and cleaned dry. Storage location: inside a building or truck, and NOT exposed for sunshine or high frequency radiation. Storage air conditions: a temperature between + 5 C to + 40 C and NOT exposed to water, moistness, pollution or dust. Do NOT store HVDC-detector for a longer time with batteries kept inside the HVDC-indicator. The batteries of the HVDC-indicator must be replaced EVERY six (6) months regardless of use or storage. The battery holder MUST be visually inspected for leakage from the batteries and/or incoming moistness 5-1 Routine maintenance At least every 6 years detector must be checked by the manufacturer*, a check which includes control of the Threshold voltage*. **) Threshold voltage is a voltage level, set by the manufacturer of the device, where the Voltage Detector shall start to indicate voltage present. The threshold value is fixed at a voltage level of approx. 0,10 x U nmax with regard to the rated voltage range of the detector. *) RAGNAR STÅLSKOG AB Instrumentvägen 6 SE-194 52 Upplands Väsby, SWEDEN Tel: +46 (0)8 594 211 80 Fax: +46 (0)8 590 882 91 www.stalskog.se, rs@stalskog.se 6

7

RAGNAR STÅLSKOG AB INSTRUMENTVÄGEN 6 - BOX 701 - SE-194 27 UPPLANDS VÄSBY, SWEDEN TFN: +46 (0)8 594 211 80 FAX: +46 (0)8 590 882 91 www.stalskog.se, rs@stalskog.se