Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Similar documents
Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Purdue e-pubs. Purdue University

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Efficiency of Non-Azeotropic Refrigerant Cycle

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance Analysis of Water-Water Heat Pump System of 100 kw Scale for Cooling Agricultural Facilities

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Sub-Critical Operation of the CO2 Expander/ Compressor

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

System Using Exhaust Heat from Residential GHPs

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

High Efficiency R-134a Compressor for Domestic Refrigerator

Low GWP Refrigerants for Air Conditioning Applications

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Study of R161 Refrigerant for Residential Airconditioning

A study of Transient Performance of A Cascade Heat Pump System

Performance of CO2 Cycles with a Two-Stage Compressor

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

A Study on Cooling Rate with Blade and Sound Fire Extinguisher

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Building Multi Air Conditioner with Higher Efficiency and Fault Detection Function

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Dae-Hyun Jin. 8/2018-Present Assistant Professor of Mechanical Engineering, Taylor University, USA

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

Compressor Capacity Control

Air-Cooled Heat Exchanger Performance for R410A

REDUCTION OF NOISE AND VIBRATION OF FRONT LOADING WASHING MACHINE IN SPIN-CYCLE

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Experimental Study on the Performance of Twisted Capillary Tube

Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

A Study on a Suitability of Sound Fire Extinguisher in Duct Environment

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Low Global Warming Refrigerants For Commercial Refrigeration Systems

R32 Compressor for Air conditioning and Refrigeration applications in China

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Geothermal ORC Systems Using Large Screw Expanders

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building Kyoung Rock Kim Sungkyunkwan University Sang Jin Tae Sungkyunkwan University Keumnam N. Cho Sungkyunkwan University Je Myung Moon Samsung Electronics Co. Jong Yup Kim Samsung Electronics Co. See next page for additional authors Follow this and additional works at: http://docs.lib.purdue.edu/iracc Kim, Kyoung Rock; Tae, Sang Jin; Cho, Keumnam N.; Moon, Je Myung; Kim, Jong Yup; and Kwon, Hyung Jin, "Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air-Conditioning System for Medium Size Building" (2004). International Refrigeration and Air Conditioning Conference. Paper 634. http://docs.lib.purdue.edu/iracc/634 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

Authors Kyoung Rock Kim, Sang Jin Tae, Keumnam N. Cho, Je Myung Moon, Jong Yup Kim, and Hyung Jin Kwon This article is available at Purdue e-pubs: http://docs.lib.purdue.edu/iracc/634

R044, Page 1 EXPERIMENTAL STUDY ON THE PERFORMANCE AND OIL RETURN CHARACTERISTICS OF MULTI-SPLIT AIR- CONDITIONING SYSTEM FOR MEDIUM SIZE BUILDING Kyoung-Rock Kim, Sang-Jin Tae 1, Keumnam Cho 2* Je-Myung Moon, Jong-Yup Kim, Hyung-Jin Kwon 3, 1 Graduate student, School of Mechanical Eng., Sungkyunkwan University, 300 Chunchun-dong, Changan-ku, Suwon, 440-746, South Korea; Phone: +82-31-290-7483; Fax: +82-31-290-5849 E-Mail: kkr7705@skku.edu, sjtae@skku.edu 2* Ph.D, Professor, School of Mechanical Eng., Sungkyunkwan University, 300 Chunchun-dong, Changan-ku, Suwon, 440-746, South Korea; Phone: +82-31-290-7445; Fax: +82-31-290-7923 E-Mail: cho@me.skku.ac.kr 3 Principal engineer, System appliance division, Samsung Electronics Co., LTD, 410 Maetan-3Dong. Paldal-ku, Suwon, 442-742, South Korea; Phone: +82-31-200-6274; Fax: +82-31-200-6392 E-Mail: moonjimy@samsung.co.kr, bulk@samsung.co.kr, kwonhj1@samsung.co.kr *Author for Correspondence ABSTRACT The present study experimentally investigated the effect of tube length and the head on the heating and cooling performance and oil return pattern of multi-split air-conditioning system. The system was installed in a ten-storybuilding with the maximum system tube length of 102m and the maximum head of 45m between indoor and outdoor unit. The maximum vertical head between adjacent indoor units was 13.5m. The system (nominal heating capacity of 28.1kW and cooling capacity of 26.4kW) consisted with one outdoor unit with both one scroll compressor with fixed capacity and the other scroll compressor with variable capacity, and five indoor units. The oil return pattern was observed through the sight glass and recorded by CCD cameras for the cases with and without oil U-traps installed every 10m. The cooling capacities of the system were decreased by 10% and 5% due to long system tube and high head respectively. The heating capacities of the system were decreased by 3% and negligibly small due to long system tube and high head respectively. The adjacent indoor units with the head of 13.5m showed the differences of 3% for the cooling capacity and 5% for the heating capacity comparing with the nominal capacities. The oil levels in the scroll compressors showed the same levels for cases with and without oil U-traps. It means that the oil U-trap is not required for the building with the multi-split air-conditioning system with the tube length of 102m and the vertical head of 45m. 1. INTRODUCTION High efficient air-conditioner is required to meet the demand for thermal comfort and convenience in residential and commercial zone. Multi-split air-conditioning system for building application has to be able to control the indoor unit for separate zone. The system is usually consisted of a number of indoor units and one outdoor unit. It may be installed in the office building residential apartments with very long tube length of approximately 100m and very high vertical head of approximately 50m.

R044, Page 2 Some experimental and theoretical studies have been carried out on the optimization of the multi-split airconditioning system, reliability of electric expansion valve control and load following characteristics. Kim et al. [1] studied the performance enhancement of the air-conditioner system adopted modulated compressors. Hong et al. [2] studied heating capacity enhancement of the heat pump system with the digital scroll compressor and electric heater at low outdoor air temperature. Han et al. [3] studied numerical simulation for the cooling and heating capacity of multi-split air-conditioner. Choi et al. [4] studied the capacity modulating characteristics of the invert-driven multisplit air-conditioner with two indoor units. Lee et al. [5] studied performance enhancement of a multi-split airconditioner with digital scroll compressor. Kim et al. [6] studied the distribution profile of compressor oil inside two compressors with different load. With the help of the flow visualization technique, oil distribution inside two compressors was visualized as proper level. Kesim et al. [7] studied analytically for the oil entrainment in the vertical pipe. He estimated the minimum refrigerant velocity required to entrain the oil in the vertical tube. Winandy and Cuevas [8] studied the oil return characteristics in a pair of scroll compressors with part load. Most of studies on the multi-split air conditioning system have been done without considering long tube and high vertical head of the system. The effect of the tube length and the vertical head on the cooling and heating performance has to be studied for practical application. The multi-split air conditioning system with long tube and high head may have the trouble with oil recirculation in the system. The oil return characteristics in the multi-split air conditioning system have to be also investigated The present study experimentally investigated the effect of system tube length and the height of head on the heating and cooling performance and oil return pattern of multi-split air-conditioning system. 2. FIELD TEST SYSTEM AND PROCEDURE 2.1 Field test system As shown in Figure 1, the field test system was installed in a ten-story-building to measure the cooling and heating capacity and oil level in the scroll compressor of the multi-split air conditioning system. The multi-split airconditioner consisted of five indoor units and one outdoor unit. The outdoor unit with one fixed scroll compressor and one digital scroll compressor was located at the roof. Compressors were controlled by the PWM (Pulse Width Modulation). Two out of five indoor units (#0, #1 units) as 4-way cassette type were located at the second floor as shown in Fig. 1 and Table 1. Two out of five indoor units (#2, #3 units) as 1-way cassette type were located at the first floor. The other one indoor unit (#4 unit) as 1-way cassette type was located in the basement of the second level. Table 1 shows the specifications of indoor and outdoor units. As shown in Fig. 1, the maximum tube length was 102m between the outdoor unit and the #4 Indoor unit, while the maximum head between the outdoor unit and the #4 indoor unit was 45m. The maximum vertical head between adjacent indoor units was 13.5m. Oil return tests were performed for two different circuits with and without (by-pass) oil U-trap installed every 10m. Thermocouples and humidity sensor were installed at the inlet and the outlet of all indoor units for measuring cooling and heating capacity of the indoor units. Unit name Table 1 : Specifications of indoor and outdoor units Nominal capacity(kw) Cooling Heating Installed floor Tube length * (m) Head * (m) outdoor unit 29.0 31.5 Roof 0 0 #0 indoor unit 7.2 7.6 77 2F #1 indoor unit 7.2 7.6 79 #2 indoor unit 4.0 4.3 61 1F #3 indoor unit 4.0 4.3 59.5-27 -31.5 #4 indoor unit 4.0 4.3 B2F 102-45 * from the outdoor unit

R044, Page 3 2.2 Test procedure Five different operating conditions were shown in Table 2. System performance with full and partial loads was measured. The case operated two indoor units was tested to investigate the effect of the maximum head between two adjacent indoor units of 13.5m on the heating and cooling performance. The case operated one indoor unit was tested to investigated the effect of the maximum length of on the heating and cooling performance and the oil return characteristics under the most severe condition. The oil levels in the compressor were visualized by using CCD camera. Outdoor unit Power meter CCD camera 8th roof Operating Server Data Aqusition Sever 45m 1F Indoor unit #0 Indoor unit #1 2F Indoor unit #2 Indoor unit #3 13.5m Pipe Length 102m B2F Indoor unit #4 Figure 1 : Schematic diagram of the experimental system Experiment Table 2 : Test conditions Indoor Unit #0 #1 #2 #3 #4 operating all indoor units operating 4 indoor units operating 2 indoor units operating 1 indoor unit (without oil U-trap) operating 1 indoor unit (with oil U-trap)

R044, Page 4 3. Results and Discussion 3.1 Effect of the tube length and the head on the heating and cooling performance Figure 2 shows the cooling capacity of the multi-split air-conditioner as the function of tube length when all indoor units were operated. The cooling capacities were obtained as the ratio of the measured cooling capacity to the nominal capacity of indoor unit shown in Table 1. The calorimeter data were compared with the field test data. The calorimeter data were obtained for the multi-split air conditioner with long tube at the standard test ambient air conditions of dry-bulb temperature of 35 and wet-bulb temperature of 27. The calorimeter test conditions had the difference of test temperatures and head with the field test data. The cooling capacity was decreased by 10% as the tube length was longer than 50m. The cooling capacity was decreased by approximately 5% as the head between outdoor and indoor units was as high as 45m. Figure 4 shows the heating capacity of the multi-split air-conditioner as the function of tube length when all indoor units were operated. The heating capacities were also obtained as the ratio of the measured heating capacity to the nominal capacity of indoor unit shown in Table 1. The heating capacity was decreased by approximately 3% as the 120% 100% #0, #1 Indoor unit Cooling capacity 80% 60% 40% #2, #3 Indoor unit #4 Indoor unit 20% Calorimeter data Field test data 0% 0 20 40 60 80 100 120 Tube length (m) Figure 2 : Effect of tube length and head on cooling capacity 120% 100% Heating capacity (%) 80% 60% 40% 20% 0% Calorimeter data Field test data 0 20 40 60 80 100 120 Tube length (m) Figure : 3 Effect of tube length and head on heating capacity

R044, Page 5 tube was as long as 100m. The effects of the head between outdoor and indoor units were negligible. The effects of tube length and the head on the heating capacity were smaller than those on the cooling capacity. Figures 4 and 5 show the effect of head between adjacent indoor units on the cooling and heating capacity. Two indoor units were #2 and #4 indoor units with the vertical head of 13.5m. The cooling capacity of #2 and #4 indoor units showed the difference of 3% for the individual and simultaneous operations. The heating capacity of #2 and #4 indoor units showed the maximum difference of 5% for the individual and simultaneous operations. The heating capacity for simultaneous operation were larger by the maximum of 8% than those for individual operation. 100 % 80 % Cooling Capacity (%) 60 % 40 % 20 % Indoor unit # 2 Indoor unit # 4 Case operated two indoor units Case operated one indoor unit 0 % 0 20 40 60 80 100 Tube length (m) 120 Figure 4 : Effect of head between adjacent indoor units on the cooling capacity 120 % 100 % y (% ) Heat ing capac i t 80 % 60 % 40 % 20 % Indoor unit # 2 Indoor unit # 4 Case operated two indoor units Case operated one indoor unit 0% 0 20 40 60 80 100 Tube length (m) 120 Figure 5 : Effect of head between adjacent indoor units on the heating capacity

R044, Page 6 3.2 Oil return characteristics in the scroll compressors Multi-split air conditioning system utilized oil U-traps installed every 10m prior to the present study. If the U- traps are not needed for the multi-split system applied for the building with the height of approximately 50m, construction cost can be reduced due to space saving. The oil levels in the scroll compressor of the outdoor unit were visualized by a couple of CCD camera as shown in Fig. 6. The oil level of 70mm is the middle of the sight glass as shown in Fig. 6. The oil return characteristics may be the worst case among the field test cases shown in Table 2 when only #4 indoor unit is operating. Figure 7 showed the oil levels with and without oil U-traps as the function of time when only #4 indoor unit was operated. The oil levels were ranged from 68 to 83 mm for both heating and cooling modes. No changes were observed for both with and without U-traps. It means that the U-trap is not needed for the multi-split air conditioner under the test conditions. Figure 8 showed the comparison of cooling and heating capacities for the cases with and without U-traps. The differences of cooling and heating capacities were negligible. Figure 6 : Visualization of oil level in the scroll compressor Oil level for cooling mode 90 85 80 75 70 65 60 by-pas U-trap Oil level for heating mode 90 85 80 75 70 65 60 0 5 10 15 20 Time (Hour) Figure 7 : Oil levels with and without oil U-traps

R044, Page 7 Cooling or heating capacity (kw) 4.5 4 3.5 3 2.5 2 1.5 1 0.5 0 U-trap by-pass U-trap by-pass Cooling mode Heating mode Operation mode Figure 8 : Comparison of cooling and heating capacities for the cases with and without U-traps 4. CONCLUSIONS 1. The cooling capacities of the multi-split air conditioning system were decreased by approximately 10% due to the tube length of 102m and 5% due to the maximum head of 45m between outdoor and indoor units comparing with the nominal cooling capacities. 2. The heating capacities were decreased by approximately 3% due to the tube length of 102m and negligibly small due to the maximum head of 45m comparing with the nominal heating capacities. The effects of tube length and the head on the heating capacity were smaller than those on the cooling capacity. 3. The adjacent indoor units with the head of 13.5m showed the differences of 3% for the cooling capacity and 5% for the heating capacity. 4. The oil levels in the scroll of compressors showed the same levels for the cases with and without U-traps. It means that the U-trap is not required for the building with the multi-split air conditioner with the tube length of 102m and the vertical head of 45m. REFERENCES [1] Kim, C. M., Hwang, Y. J., Ryu, Y. H. and Cho, K. S., 2001, The experimental study on the comparison in performance of the system used modulated compressors, Proceeding of the SAREK, pp. 1114-1120. (in Korean) [2] Hong, J. T., Jang, G. S., Kim, D. Y., Kim, J. Y., Moon, J. M., Youn, B., Shim, S. C., 2001, An experinmental study on the heating capacity improvement at low temperature condition of system air-conditioner using the digital scroll compressor, Proceeding of the SAREK, pp. 680-685. (in Korean) [3] Han, D. Y., Kwon, H. J., Ha, S. C., 1999 Design and performance prediction of the multi-type heat pump system, Proceeding of the SAREK, pp. 515-520. (in Korean) [4] Choi, J. M., Kim, Y. C., 2003, Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves, Energy, Vol. 28, pp 141-155 [5] Lee, Y. S., Jun, Y. H., Kim, D. H., Chang, K. S., Youn, B., Moon, J. M., Hong, J. T., Oh, M. D., 2002, An Experimental Study on the cooling and heating characteristics of system air-conditioner using the digital scroll compressor, Proceeding of the SAREK, pp.575-580. (in Korean) [6] Kim, C. M., Hwang, Y. J., Jung, B. Y., 2003, The experimental study on uniform distrubution of oil at the air conditioning system using two compressors, Proceeding of the SAREK, Vol.15, No.2, pp.103-108. (in Korean)

R044, Page 8 [7] Kesim S. C., Albayrak K., Ileri A., 2000, Oil entrainment in vertical refrigerant piping, International Journal of Refrigeration, Vol 23, pp. 626-631. [8] Winandy E. L., Cuevas C. B. 2003, Analysis of the oil return in a pair of scroll compressors working in parallel at part load, Applied Thermal Engineering, Vol23, pp. 623-636. ACKNOWLEDGEMENTS This research was supported by the Smart Future Appliance Research Center (SFARC), (funded by the Samsung Electronics Co.) at Sungkyunkwan University in the year of 2003.