ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42

Similar documents
compact office 24V compact office 24V Lux

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A..

compact office 24V compact office 24V Lux

PresenceLight 180 PresenceLight 360

PresenceLight 180A-KNX.. PresenceLight 360A-KNX.. PresenceLight 180B-KNX.. PresenceLight 360B-KNX..

1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Function description. Channel A light. Motion detector

Motion detector themova P360 KNX UP WH themova P360 KNX UP GR

2. Safety. 1. Product characteristics. 3. Proper use. 4. Operation. Function description. Presence detector

3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Motion detector

2. Safety. 1. Product characteristics. 3. Proper use. 4. Operation. Function description. Presence detector

1. Basic safety information 3 2. Proper use 3

2. Safety. 4. Function

KNX/EIB - Product database - Application description

Product and Applications Description

User Manual 120/240/300 Outdoor Motion Detector

1. Basic safety information 3 2. Proper use 3

FR-A180 FR-A360. Occupancy detector. Use

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions

IP 55 (category II) IP 54 (category II) 4. Connection. 1. Basic safety information. 2. Proper use. 5. Installation. 3. Description.

UP 258E11 OPTISENS OFFICE

1. Basic safety information 3 2. Proper use 3

Detailed operating instructions

PRESENCE DETECTOR. PD-C360i/8 mini KNX PD-C360i/12 mini KNX / 13 7 REMOTE CONTROL PRESENCE DETECTOR

Connections, displays and operating elements C D E G H. Installing the control unit

Detailed operating instructions

0701 CO Light, HVAC, Monitoring, Brightness

II SL. Installation Guide. VOLTEX IMS64-2 Dual output indoor flush mount PIR motion detector IMS64-2

OPERATING INSTRUCTIONS

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

GE Lighting. Lighting Controls. DALI Digital Lighting Controls

LED Compatible Daylight Harvesting and Motion Sensor System

64.7 Ø85. (1) Sensor inset (2) Lens pluggable. (3) Protection cover (covers the high-voltage terminals). (4) Ceiling (drill hole Ø70mm).

luxcontrol lighting control system basicdim basicdim ILD 16DPI 69f Compact control module with ambient light sensor and motion sensor

RE-PR3-E-27 3-Phase Panel Mount 27kW

DIMAX DIMAX D GB F I E NL. Installation and operating instructions Universal dimmer DIMAX 532. Minimum DIMAX 532.

11,9. Ordering data. Max. cable length sensor head 1 basicdim ILD lx 150 lx m 1

DIMAX DIMAX 534 plus D GB F I E nl. Installation and operating instructions Universal dimmer. DIMAX 534 plus

Eco-sensors - PIR. Catalogue number(s): / / Use. 1. Use Technical characteristics (continued)

luxcontrol lighting control system basicdim basicdim ILD Compact control module with ambient light sensor and motion sensor

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

EBMHS (standard & slim-line PSU)

11,1 30. Ordering data

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

SWITCHLITE MRE SLD MAN SWITCHLITE MRE SLD IP55

PIR movement and presence detectors 10 A

Detector switch - Dual Tech

Automatic switch attachment Standard Installation Instructions

Integrated PIR detectors

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

Save energy. ARGUS presence detectors

Motion Sensor. For Outdoor Use. Wall & ceiling mounted. Quick & Easy Installation 2 Channels

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

EBMPIR-MB. Batten mount PIR detectors. Product Guide. Overview. Features

PRODUCT DATA AND INSTALLATION SHEET MWS5-SA STAND ALONE MINIATURE CEILING MOUNTED MICROWAVE PRESENCE DETECTOR

IP65 High Bay Dual Sense Sensor

The Power To Supply... All Your Electrical Products

Push Button Electronic Timer. 31VETR Series. Installation Instructions

Busch-Watchdog presence. Overview and applications of presence detectors.

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Detector switch - Dual Tech SCS

, ,

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

Push Button Electronic Timer. 31VETR3 Series. Installation Instructions

SCHMIDT LED Measured Value Display MD Instructions for Use

Ceiling PIR HS presence detector. Product Guide. Overview. Features

luxcontrol DALI basicdim DGC Product Manual

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Tri-level Control HF Sensor

IP65 High Bay Dual Sense Sensor

False Ceiling HF Sensors

PPAD-C-230V. Ceiling PIR presence/absence detector. Product Guide. Overview. Features

Product and functional description

LPC3BSP65 & LPC3BDP65

Tri-level Control HF Sensor

Analogue Dimming Microwave Presence/Absence Detector

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

SOLO User Guide. Description. Installation. Programmable Dual Voltage Thermostat 240 V (120 V)

ACS-30-EU-VIA-DU-20-MOD

LPCMPIRM65 & LPCMPIRDSI65

MWS3A-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

1 Safety instructions. 2 Device components. Observer 220. Art.-No.: W 220 WW. Operationsmanual

Product Guide. Ceiling microwave presence detector DALI / DSI. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

C-Bus PIR Occupancy Sensor. Installation Instructions 5751L

KNX Technical Manual Busch-Presence detector KNX / Busch-Watchdog Sky KNX

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

Light Level Detector, Surface Mount 5754PE. Installation Instructions

Product Guide. Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs.

L / -014L / -015L

Sensero-868/915 AC, Sensero-868/915 AC Plus Nr , , ,

Direct Dim Microwave Presence/Absence Detector

360º Surface Mount Ceiling PIR Light Controller

Premium Version Tri-level Dimming Control

Transcription:

Presence detector ECO-IR 360C NT Art. Nr. 202 0 400 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de instrucciones 62 Istruzioni per l uso 82 Gebruikershandleiding 102 Bruksanvisning 122 Bruksanvisning 142 Käyttöohje 162 Betjeningsvejledning 182 1103014509 / 12.09 Theben HTS

English Installation manual Presence detector ECO-IR 360C NT Table of contents 1. Safety.................................................. 43 2. Function and performance characteristics....................... 44 3. Location / Installation....................................... 45 4. Start-up................................................. 48 5. Additional wiring examples.................................. 52 6. Test mode............................................... 54 7. Technical specifications..................................... 55 8. Warranty declaration....................................... 57 9. Troubleshooting........................................... 58 42

GB Thank you for purchasing an Theben HTS presence detector and putting your trust in us. 1. Safety DANGER! Any work on electrical systems must exclusively be carried out by qualified electricians or instructed persons under the direction and supervision of a qualified electrician in accordance with the relevant electrotechnical rules! Any national safety regulations regarding the manipulation of electrical systems must be observed! The voltage supply must be disconnected prior to installation! CAUTION! The device is maintenance-free. The warranty terminates if the device is opened or entered with any kind of object. Designated use The presence detector is solely intended for the purpose contractually specified between the manufacturer and the user. Any other or extended use has to be regarded as not complying with the designated use. The manufacturer is not liable for any resulting damage. 43

2. Function and performance characteristics The presence detector ECO-IR 360C NT detects persons within a room on account of slightest movements. Simultaneously, its light sensor measures the brightness in the room and compares it to the pre-set brightness threshold. ECO-IR 360C NT is used preferably in large rooms and other applications which need a very high detection sensitivity. A mechanical safety lock protects the detector against unauthorised removal. The Switching Contact A «Light» switches on the lighting in case of presence and insufficient brightness, and off in case of absence or sufficient brightness. In addition, the lighting can be switched manually by means of push-buttons. Switching contact Light: relay 230V Real daylight measurement Manual control by push-button or switch Semi or fully automatic operation Suitable for fluorescent lamps and compact energy saving lamps Pulse function for staircase lighting timer QuickSet plus service remote control (optionally) clic user remote control (optionally) The Switching Contact B «Presence» controls heating, ventilation and airconditioning systems. The contact closes in case of presence, a switch-on delay and a switch-off delay can be set with the service remote control Quick- 44

Set plus. The contact can also be used for room surveillance purposes. Using reduced sensitivity, it only responds on very distinct movements. Switching contact Presence: potential-free relay Adjustable switch-on delay and switch-off delay Surveillance function GB 3. Location / Installation 3.1 Presence detection The ideal mounting height is 2.0-3.5m. The sensitivity of the detector decreases with increasing mounting height. In order to ensure proper detection of persons, the ECO-IR 360C NT requires an unobstructed view of the persons. Office equipment, plants, suspended lamps etc. may affect the presence detection (shading). H. mont. Personnes assises Personnes marchant 2,0m 4,5m x 4,5m 6,0m x 6,0m ± 0,5m 2,5m 6,0m x 6,0m 8,0m x 8,0m ± 0,5m 3,0m 7,0m x 7,0m 9,0m x 9,0m ± 0,5m 3,5m 8,0m x 8,0m 10m x 10m ± 1,0m 4,0m --- 11m x 11m ± 1,0m 45

Detection range (mounting height 3,0m) o seated persons walking persons 46

3.2 Light measurement The ECO-IR 360C NT is designed for use with fluorescent lamps. It ist particularly suitable for switching electronic ballasts. Incandescent or halogen lamps may interfere with the operation of the detector. With indirect lighting, ensure that the light from these lamps is not directed at the detector, as this would affect the daylight measurement. GB 3.3 Connection The presence detector ECO-IR 360C NT must be flush mounted into a concealed housing. A suitable frame for surface mounting is also available. 3.4 Coding Before use, the ECO-IR 360C NT has to be configured as «Master» or «Slave» with the enclosed code keys. 47

3.5 Single Unit Operation For single unit operation, the ECO-IR DUAL- C NT is configured as a «Master» and thus is able to control light and with the presence output e.g. a HVAC application. To get a «Master», the correspon-ding code key has to be inserted into the power module ECO-IR 540C. Stuck the corresponding sticker «Master» onto the power module. 4. Start-up The detectors are supplied ready for operation with a factory setting of standard values. QuickSet plus service remote control for starting-up is optionally available, which allows to set all potentiometer values and the switch off delay time/surveillance function from a distance. 4.1 Settings for switching contact A «Light» Potentiometer Brightness threshold LUX Scale Transfer zones (no working area) approx. 2 Working areas (office, conference room) approx. 4 Activities requiring good visibility (laboratory, drawing, etc.) > 5 Deactivation of brightness measurement «on» 48 Presence (e.g. HVAC)

Depending on the installation location, natural light intensity, furniture, reflection characteristics of the room and the furniture it may be necessary to correct the settings by 1-2 steps on the scale. GB For ease of setting up, we recommend the service remote control QuickSet plus. Switch-off delay time Transfer areas approx. 5min. Working areas approx. 10min. In the range between 2-15min the switch-off delay varies according to its self-learning behavior. The set values <2min or >15min remain fixed. «Pulse»: staircase lighting timer control (0.5s on / 10s off ) DIP switch Fully / Semi-automatic mode «auto»: Fully automatic mode. The lighting is switched on automatically. «man»: Semi-automatic mode. The lighting must be switched on manually by push button or switch. 49

Push-button function: room / corridor «room»: Manual switching on/off possible. «corridor»: Detector is used as staircase lighting timer. No manual switching-off possible. Push-button/Switch control Optional push-button or switch operation. Multiple push-buttons on one control input possible. Use illuminated push-buttons with PEN conductor connection only. 4.2 Settings for switching output B «Presence» Switch-off delay time for presence The pre-set values remain unchanged (no self-learning effect). Switch-on delay time for presence Switch-off delay time and room surveillance function can only be set with the service remote control QuickSet plus. In case of presence, the contact does not close before the set switch-on delay has elapsed. 0 = Contact closes immediately in case of presence. Room surveillance : the contact closes only in case of distinct movements (effective protection against false alarms). 50

4.3 Behaviour on switching on Whenever the sensor module is plugged onto the power module or the unit is energised, the detector goes through tree phases which are indicated by an LED. Fast blinking (4x per second) means the code key is not recongnized. 1. Start-up phase (30sec) LED flashes every second, both contacts are closed (light and presence on) In case of absence, both contacts open after 30sec. 2. Service phase (10min) The «Light» contact reacts instantaneously on brightness in order to check the brightness threshold. If the brightness is insufficient the lighting is switched on (LED on),and if the brightness is sufficient the lighting is switched off (LED off). During the service phase, switching of the lighting occurs fully automatically (no semi-automatic mode). The service phase terminates earlier by actuating the push-button or the remote control. 3. Operation GB The detector is ready for operation (LED off). 51

5. Additional wiring examples 5.1 Master-Slave parallel circuit operation Two or more detectors are required for the desired room size. The coding of the detector (Master or Slave) is set by means of a code key on the power modules. Stuck the corresponding sticker («Master», «Slave») onto the power modules. Only the master switches the lighting. All other detectors serve as slaves. Presence detection is done by all detectors together. Daylight measurement done by the Master only. Set the potentiometer and DIP switches on all detectors. Note: the settings of the potentiometer LUX is effective only with the master. Max. 10 detectors can be connected in parallel. Use the same phase for all detectors. L N lightning Push-button/ Switch L N P L N P ECO-IR 540C ECO-IR 540C Maste r Slave SA A B1 B2 SA A B1 B2 Presence (e.g. HVAC) 52

5.2 Parallel circuit operation with external staircase lighting timer The coding of all detectors as «Master» is set by means of a code key on the power modules. Stuck the corresponding sticker («Master») onto the power modules. Directly connect the switching contacts of multiple detectors in parallel. Set the switch-off delay on all detectors to «pulse» Max. 10 detectors can be connected in parallel. Use the same phase for all detectors. External staircase lighting timer e.g. Theben ELPA 1 GB L N L N ELPA 1 out in L N P ECO-IR 540C Master S A B1 B2 L N P ECO-IR 540C Master S A B1 B2 53

6. Test mode The test mode serves to check the presence detection and the wiring (Master-Slave parallel circuit operation). 6.1 Setting the test mode with DIP-Switch Set DIP switch to «Test» (on all detectors in parallel circuit operation). 1. Start-up phase (30sec) Both contacts are closed for 30sec. (LED 20s «on», 10s «off» ) The blinking pattern of the LED indicates which coding has been set in the detector: 2 pulses = Master; 5 pulses = Slave Fast blinking (4x per second): the code key is not recongnized! 2. Test mode In case of movement (LED on), both contacts close In case of absence (LED off), both contacts open after 10sec. NOTE: no brightness measurement, detector always in fully automatic mode The detector remains permanently in the test mode 6.2 Setting the test mode with QuickSet plus While setting the test mode with QuickSet plus, the detector jumps the start-up phase and changes directly into the test mode. Test mode ceases automatically after 10 minutes. The detector performs a reset (see section 4.3). 54

7. Technical specifications Sensor module Detection range: horizontal vertical ECO-IR 360C NT 360 120 Recomm. mounting height (Mh) 2,0m - 3,5m Maximum range 8 x 8m (Mh. 2,5m) 10 x 10m (Mh. 3,5m) True daylight measurement Light measurement deactivated Switch off delay for light Short pulse Switch off delay for presence Switch on delay for presence; room surveillance; only available with service remote control Power module Mains voltage Relay output A for light approx. 10-1500Lux on 10s - 20min. 0.5s on / 10s off 10s - 120min. 0s - 10min. ECO-IR 540C 230V± 10%, 50 Hz with initial current limitation Nominal voltage 230V ± 10% Max. switching capacity 1400VA / 6AX~µ Max. number of electronic ballasts *) A relay or contactor must be connected in case of more powerful devices 16x (1x 58W); 8x (2x58W) 24x (1x36W);12x (2x36W) 24x (less than 36W) GB 55

Relay output B for presence potential-free Maximum voltage 220V DC / 250VAC Maximum switching capacity 100W / 460VA Recommended minimum load 10V / 100mA Depth Diameter Mounting plate 35mm 55mm 70 x 70mm Terminals without screws max. 1.5mm2 Size of concealed housing 1 (NIS,PMI) (for flush-mounting) Ambient temperature 0-50 C Degree of protection IP 40 Article numbers ECO-IR 360C NT 202 0 400 Surface frame for ECO-IR 360 907 0 512 QuickSet plus service remote control 907 0 532 clic user remote control 907 0 515 *) Use of T5-FL: When using T5-FL lamps with a comparable wattage, the same number of electronic ballasts may be connected to the detector s switching contact as for the T8- FL. When using the 80W-FL, the number should be halved in comparison to the 58W-FL. CE Declaration of Conformity This device complies with the protection regulations of the EMC directives 2004/108/EC and of the Low Voltage directive 2006/95/EC. 56

8. Warranty declaration Theben HTS presence detectors are manufactured and quality-tested with the utmost care using state-of-the-art technologies. Theben HTS therefore guarantees perfect function, provided the detectors are used as intended. However, should a defect occur, Theben HTS offers the following warranty within the scope of its General Terms and Conditions of Business: GB Please bear in mind the following points: The warranty period is 24 months, commencing from the manufacturing date. The warranty becomes null and void if you or third parties undertake alterations to the units. If the presence detector is connected to a software-controlled system, the warranty for this connection is only valid provided the stated interface specification is adhered to. We undertake to repair or replace as quickly as possible all supplied components which have become defective or unusable as a result of demonstrably bad material, faulty design or defective workmanship up to the expiry of the warranty period. Returns In the event of a warranty claim please send the unit together with the delivery note and a brief description of the fault to the dealer concerned. Industrial property rights The concept including hardware and software of these units is protected by copyright. 57

9. Troubleshooting Fault Lighting does not switch on or switches off in case of presence and darkness With persons present, the lighting is on although the brightness is sufficient Lighting does not switch off or switches on spontaneously in case of absence Light keeps switching on and off ( blinking ) Push-button does not work Lighting cannot be switched off with the push-button Error blinking (4x per sec.) Cause Lux value setting is too low; Detector is in semi-automatic mode; Lighting was switched off manually; Person is outside the detection range; Detection is disturbed by obstacle(s); Set switch-off delay setting is too short. Lux value setting is too high; The lighting has been switched on manually with clic recently (wait for 30 min); Detector is in test mode. Wait until the switch-off delay time has elapsed (self-learning effect); Disturbing heat sources within the detection range (heaters, incandescent lamp/ halogen lamp, moving objects (e.g. curtains due to open windows); Load (el. starter devices, relay) has no interference suppression. Incandescent lamps or halogen lamps controlled via ECO-IR, deactivate Lux measurement, swap incandescent lamps with PL lamps. Direct shining of FL lamps on the sensor is too high. Check detector arrangement in relation to lamps. Device is still in start-up phase or an illuminated pushbutton without PEN conductor connection is used; Push-button is not connected to the master. DIP-switch in corridor position. Code key missing or not recognized. Failure during self test; Device not working. 58

4 Dimensions ECO-IR 360C NT 87 4 GB 46,3 21,3 66,5 35,5 37,5 22 48 95 11 70 56 R30 84,5 56 70 Subject to change without prior notice. Errors and omissions excepted. 59

Theben AG Hohenbergstrasse 32, DE-72401 Haigerloch Tel. +49 (0) 74 74 692-0 Fax +49 (0) 74 74 692-150 Hotline Tel. +49 (0) 74 74 692-369 Fax +49 (0) 74 74 692-207 hotline@theben.de Switzerland Theben HTS AG Im Langhag 11, CH - 8307 Effretikon Tel. +41 (0)52 355 17 00 Fax +41 (0)52 355 17 01 www.theben-hts.ch Please find the contact addresses for additional countries on www.theben.de 60