and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

Similar documents
Installation and maintenance instructions

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

WOLF GAS CONDENSING BOILERS COMFORTLINE

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

Operating instructions Oil condensing boiler

VIESMANN. Installation instructions VITODENS 200-W. for contractors

Operating instructions

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user

Installation and maintenance instructions

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

Installation and maintenance manual

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

AGS 2 SOLAR PUMP STATION FOR SOLAR DOMESTIC HOT WATER SYSTEMS UK/IE

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

Uni 3000 F Output range 420 to 1850 kw. Oil/gas boiler. Installation and maintenance instructions for the contractor (2014/10) UK

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation, operating and servicing instructions

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

Light oil / kerosene burner

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

INSTALLATION AND MANINTENANCE INSTRUCTIONS

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

WHE 2.24 / WHE 2.24 FF

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

Installation and maintenance instructions

Operating instructions

Operating Instructions

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

AGS 5/5E, AGS 10/10E INSTALLATION AND SERVICING INSTRUCTIONS SOLAR PUMP STATIONS FOR SEALED SOLAR HEATING SYSTEMS AND INDIRECT FED DOMESTIC HOT WATER

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Operating instructions

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Technical documentation. ComfortLine gas condensing boilers CGB-2(K) CGW-2 CGS-2 CSZ-2 NEW

TERMO Combi Cylinder TECHNICAL INFORMATION

Technical information. Remeha P200. Pressurized boiler. Heat output: kw

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

Installation and service instructions for contractors Logano plus SB625. Burner shroud not available in UK and Ireland

VIESMANN VITOLADENS 300-C Oil condensing boilers 12.9 to 28.9 kw

Installation and maintenance instructions

Installation and maintenance instructions

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

Installation, operation and care. Pellmax UB. Burner not included Replaces:

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

TH100 Three in One Instant Hot Water Tap

INSTALLATION AND OPERATION MANUAL

Trumatic E. Trumatic E 2400 (Australia) Operating instructions Page 4 Installation instructions Page 7. To be kept in the vehicle!

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE

Operating instructions

A/23 MFFI - A/27 MFFI

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Parts Available from

Glass and Dishwashers AMX / AUX Series

Propane Heater REMKO PGM 30 REMKO PGM 60

BM Programming Module. For the heating engineer Installation instructions

VIESMANN. Service instructions VITODENS 200-W. for contractors

Installation and maintenance instructions

Manual. Above-counter dispenser for hot drinks OTHG /12

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Operating instructions

/2010 US/CA

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

Installation and maintenance instructions

Transcription:

Technical Guide and Installation Instructions MKS / MUS Steel boiler 70-550 kw The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack. The control unit installation and service instructions included in the control unit pack. Wolf GmbH 84048 Mainburg Postfach 1380 Telephone +49-8751/74-0 Fax +49-8751/741600 Part no. 30 48 034 03/03 TV GB 1

Oil- and gas-fired steel boiler for pressure jet combustion in accordance with EN 303 and EC Directive 90/396/EEC (gas consuming equipment), 73/23/EEC (Low Voltage Directive), 89/336/EEC (EMC Directive), 92/42/EEC (Hot Water Boiler Efficiency) and 93/ 68/EEC (Identification Directive) for heating systems with heating circuit pumps and flow temperatures up to 110 C and 4 bar permissible operating pressure in accordance with DIN 4751 and max. DHW cylinder pressure 10 bar in accordance with DIN 4753. The NO x limits required by the 1st BImSchV 7(2) are maintained. Suitable for heating systems in accordance with DIN 4751 part 1 and 2 with maximum flow temperatures up to 120 C. Oil- and gas-fired steel boilers Type MKS Oil-fired Unit steel boilers with two-stage pressure jet oil burner Type MUS 2

Specification Boiler type MUS 85 100 MKS 85 100 140 190 250 340 420 500 Output range oil/gas (MKS) kw 70-100 85-120 110-160 160-230 200-300 280-380 360-460 420-550 Recommended range (MKS) kw 70-85 85-100 110-140 160-190 200-250 280-340 360-420 420-500 Upper range oil (MUS) kw 70-85 85-100 - - - - - - Set output UNIT burner MUS kw 85 100 - - - - - - Flue gas temperatures 1) from/to C 145-165 145-165 145-165 145-165 145-165 150-170 150-165 155-170 1 st stage flue gas temperature C 120 120 120 120 120 120 120 120 Flue gas mass flow rate 1) Fuel oil EL CO 2 =13% kg/h 127-142 142-168 184-235 269-319 336-420 470-571 605-706 706-840 Flue gas mass flow rate 1) Natural gas E CO 2 =9.5% kg/h 125-151 151-178 196-249 285-338 356-445 498-605 641-748 748-890 Flue gas mass flow rate 1) Natural gas LL CO 2 =9.0% kg/h 129-157 157-185 203-259 296-351 370-462 517-628 665-776 776-924 Flue gas mass flow rate 1) LPG CO 2 =11% kg/h 120-146 146-172 189-240 274-326 343-429 480-583 618-721 721-858 Relative standby loss q B % 0.7 0.7 0.6 0.5 0.5 0.4 0.4 0.3 Total weight MKS kg 406 413 524 730 772 908 975 1035 Total weight MUS kg 426 433 - - - - - - Boiler dim. Width mm 796 796 796 976 976 1036 1036 1036 Height 2) mm 1335 1335 1335 1500 1500 1680 1680 1680 Length MKS mm 1415 1415 1760 1950 1950 2085 2085 2085 Length MUS mm 1825 1825 - - - - - - Flue pipe Ø mm 178 178 195 195 195 250 250 300 Burner aperture MKS mm 130 130 130 245 3) 245 3) 305 3) 305 3) 305 3) Minimum blast tube length MKS mm 170 170 170 215 215 125 125 125 Foundation / plinth Height mm 80/80 80/80 80/80 80/80 80/80 80/- 80/- 80/- Width mm 800/850 800/850 800/850 1000/950 1000/950 1100/- 1100/- 1100/- Length mm 1360/1300 1360/1300 1700/1500 1850/1500 1850/1500 2000/- 2000/- 2000/- Boiler flow (flange) DN 65 65 65 80 80 100 100 100 Safety flow, air-vent valve (male thread) R 1¼" 1¼" 1¼" 1½" 1½" 2" 2" 2" Boiler return (flange) DN 65 65 65 80 80 100 100 100 Filling, draining, safety return (male thread) R 1½" 1½" 1½" 1½" 1½" 1½" 1½" 1½" Boiler water content l 216 213 288 508 494 697 665 635 Boiler gas content l 140 143 206 333 346 428 445 460 Heating surface m 2 3.5 3.8 5.2 8 8.4 10.6 12.5 14.2 Flue gas resistance 1) mbar 0.3 0.4 0.8 1.1 1.4 2.0 2.0 2.0 Heating water resistance (at Dt=20K) 1) mbar 1.2 1.7 3.5 4.5 5.5 9.0 14.0 19.0 Combustion cham. dia. Length mm 808 808 1158 1292 1292 1496 1496 1496 Diameter mm 447 447 447 547 547 588 588 588 Type approval ID 02-226-626 ÖVGW-Reg.-Nr. G2,416 CE designation CE-0085AR0034 Electrical connection 230V / 50Hz / 10A Max. perm. temperature 4) C 120 Max. boiler pressure bar 4 1) At a mean boiler water temperature of 60 C for the upper and lower output of the recommended range. 2) Including control unit 3) Plain burner plate, drill on-site. 4) Adjustable high limit safety cut-out: 120/110/100 C at R31 STAV, R32, R33 and R33/4 (not applicable to installations in Austria). The chimney stack dimensions must be calculated in accordance with DIN 4705, or local regulations. For flue gas temperatures below 160 C, combustion equipment must be connected to highly insulated chimney stacks (heat conductivity resistance class I acc. to DIN 18160 T1) or use suitable, moisture-resistant, type-tested, flue gas systems. 3

Safety instructions General These installation instructions apply exclusively to WOLF oil- and gas-fired boilers as well as to WOLF Unit steel boilers. Authorised personnel should read these instructions before any installation, commissioning or maintenance work. Adhere to the instructions given in this document. Non-adherence to these installation instructions voids WOLF warranty. Reference symbols Please note: The following symbols and references are used in these installation instructions: Non-observance of these references can put individuals at risk. Non-observance of these references can lead to damage to the oil/gas-fired boiler or the Unit boiler. In addition to the installation instructions, operating instructions and adhesive labels are included or fitted to the boiler. These must also be observed. Observe the enclosed references for heating system installers. Safety instructions Only qualified and trained personnel may install, commission and maintain these boilers. In accordance with VDE 0105 part 1, work on electrical components (e.g. control unit) may only be carried out by qualified electricians. The regulations of VDE/ÖVE and those of your local electricity supplier as well as all other local regulations are apply to electrical installation work. Only operate the boiler within its output range which is stated in the specification supplied by WOLF. Appropriate use of the boiler refers to the exclusive use in hot water heating systems in accordance with DIN 4751. Never remove, bypass or otherwise disable any safety and monitoring equipment. Only operate the boiler in perfect technical condition. Any faults and damage with a potential impact on safety, which might limit the safe use of the equipment, must be remedied immediately by a qualified contractor. Replace faulty components or equipment only with original WOLF spare parts. Standards and regulations The boilers described in these installation instructions are low-temperature boilers according to HeizAnlV and 92/42/EEC (Hot Water Boiler Efficiency). In accordance with the Heating System Order, heating systems above 70 kw may not be operated in single stage mode. Retain the enclosed operating instructions clearly visible in the boiler room. Insert all further documentation in a clear wallet and clip to the boiler side casing. Your boiler and burner should be maintained and cleaned on an annual basis by a heating contractor, to ensure the reliable and economic function of your heating system. We would recommend a maintenance contract. Boilers may only be installed and operated in boiler rooms which are suitable according to the Landes-FeuVo [or local regulations]. 4

Positioning Installation references The boiler should be installed on a level surface which is substantial enough to carry its weight. It is recommended to place the boiler on a foundation or plinth. For dimensions see the specification. During the boiler installation observe all building regulations, the FeuVo and VDI 2050 [in Germany] and local regulations, particularly regarding the size of the boiler room, the fresh air and exhaust air ventilation as well as the chimney stack connection. Please note: Please note: Only install the boiler in boiler rooms which are free from frost and where adequate ventilation is ensured. Drain the boiler, the DHW cylinder and the entire heating system if there is a danger of frost, if the system has been shut down. Position the boiler horizontally or slightly rising towards the back to ensure adequate venting of any trapped air. Boilers should not be installed in areas subject to aggressive vapours or very dusty/ highly humid conditions (workshops, washrooms, hobby rooms etc). The combustion air must be free from halogenated hydrocarbons (e.g. as contained in sprays, solvents and cleaning fluids, paints and adhesives) and high dust concentration. Clearances towards walls and combustible materials must comply with local fire regulations. The above clearances are recommended. Keep the flue pipe connection as short as possible and inclined towards the chimney stack. Thoroughly seal-in the flue pipe. Use flue pipe bends with clean-out covers to facilitate the cleaning of the flue pipe. Repositioning the fixing screws enables the boiler door to be opened in the opposite hand. 5

Casing installation Control unit cable Boiler sensor 2 nd stage 1 st stage Burner cables 1 Thermal insulation: Position (overlapping) around the boiler block and secure with spring clips. 2 Spacers: Secure on the boiler with nuts enclosed. (MKS-85 to 500) Four spacers at the real panel. (MKS-85 to 140) Two bottom spacers per side. (MKS-190 to 500) Three bottom spacers per side and one central top spacer. 3 Thermal insulation: Loosely fitted to the rear boiler wall. 4 Rear panels: Centrally locate both parts and secure with self-tapping screws and with the screws (M8x16) supplied on the rear boiler wall spacers. 5 Thermal insulation: Insert from the top between door and boiler front and locate on the boiler front. 6 Thermal insulation: Fit loosely to the boiler front and secure with spring clips. 7 Thermal insulation: Fit loosely to the boiler front and secure with adhesive strips. 8 Side panels: Push the l.h./r.h. casing over the rear panel and secure with the screws (MUS-85 to 100 / MKS-85 to 140) (M8x16) supplied to the lower two spacers. 8 Side panels: Secure the l.h./r.h. front and rear panels with screws (M6x10) then push over the rear panel (MKS-190 to 500) and secure with the screws (M8x16) supplied on the lower three spacers. 9 Wolf label: Hook into the front panel lid (10). 10 Front panel lid: Locate and click into the panel with fitted control unit. Only complete the fitting of the casing after the control unit has been installed (page 7). 10 Panel lid l.h. rear: Locate on the panel and click into place. 10 Panel lid r.h. rear: Locate on the panel and click into place. 13 Type plate: Affix to the boiler in a clearly visible position. Accompanying documentation: Affix with the clips supplied to the side of the boiler. 6

Control unit installation High limit safety cut-out Please note: Ensure, during the control unit installationthat the sensor capillaries are not kinked or twisted and have only been pulled out of the boiler casing as far as necessary. Do not route on-site cables for outside temperature and flow temperature sensors together with mains power cables. Electrical wiring in accordance with the wiring diagram enclosed. Ensure that cables which are not required are secured against contact. Observe the respective installation and operating instructions for R32, R33 and R33/4 control units. R31-STAV control unit 1 st stage Burner cable 2 nd stage Boiler sensor Mains supply cable Heating circuit pump cable Loading pump cable DHW cylinder cable Control unit Guide the cable through the casing lid cut-out, and secure the control unit housing on the casing lid with the self-tapping screws supplied. Guide the burner cables through the boiler front cut-out. Push the boiler sensors in any order into the boiler sensor well. Guide the mains supply cable, and the heating circuit pump cable through the boiler back cut-out. Guide the loading pump cable (for DHW cylinder connection accessories) through the boiler back cut-out. Guide the DHW cylinder cable (for DHW cylinder connection accessories) through the boiler back cut-out. Adjusting the boiler thermostat If necessary, the boiler thermostat can be adjusted from 80 C to 90 C. To do this, turn the boiler thermostat clockwise to its end-stop (80 C); pull out the rotary selector approx. 3 mm and continue to turn clockwise to its end-stop (90 C). Please note: The boiler thermostat must not be set to 90 C if the high limit safety cut-out has been adjusted to 100 C. Changing the setting of the high limit safety cut-out (STB) for R31-STAV The high limit safety cut-out (STB) is factory-set to 120 C. Change the setting of the STB, if required. Such changes are irreversible. Disconnect the control unit from its power supply. Remove the control unit lid with a screwdriver. Unscrew the plastic cap and locking nut. Remove the high limit safety cut-out. Adjust the setscrew in accordance with the scale. Install in reverse order. Control accessories Please note: Installation and electrical wiring according to the wiring diagram supplied with the control accessories. If Wolf boilers are equipped with control units not supplied by Wolf or if technical modifications are carried out on Wolf control units, Wolf will not be liable for any consequential losses which may occur. 7

Installation / maintenance Connections Venting Safety flow Boiler flow Boiler return Flue pipe connection Draining, filling Pipework Central heating boiler Connect the heating flow and return to the respective boiler fittings. For connections, see above. Install a check valve behind the boiler circuit pump(s) to prevent incorrect circulation. Install a safety equipment assembly. Please note: The pipework between the boiler and the safety valve must not be able to be shut off. Connect underfloor heating via a four-way mixer. Provide system separation by means of a heat exchanger, when using pipes which are not impermeable to oxygen. Filling the heating system The boiler and central heating system may only be filled, if a type-tested safety valve (opening pressure max. 3 bar) has been installed at the "ventilation connection of the boiler. Install a filling/drain valve to fill the central heating system at the "drain, filling connection, and connect a water hose. Observe the pressure gauge in the safety equipment assembly when filling the system with water. Check the safety valve function. Ventilate the boiler (automatic air-vent valve). Draining the heating system Shut down the heating system and let it cool down. Open the drain valve on the boiler. Open the radiator bleed valves. 8

Minimum return temperatures / return temperature raising facility Minimum return temperatures To prevent falling below the dewpoint, the following measures for raising the return temperature are required in order to maintain the minimum temperatures t Rmin listed in the table. System Fuel Oil Gas Control unit R31, R32 R31, R32 R33, R33/4 R33, R33/4 Radiator central heating t Kmin C 38 50 less than 20l/kW t Rmin C 30 40 Design 80/60 Return temp. raising 1-3 2/3 acc. to sys. example Low-temp. central heating t Kmin C 38 50 with less than 20l/kW; t Rmin C 30 40 Design temperature Return temp. raising 1-3 2/3 55/45 and above acc. to sys. example Systems with more than t Kmin C 38 50 20l/kW underfloor/ t Rmin C 30 40 low-temp. central heating Design temperature Return temp. raising 2/3 2/3 under 55/45 acc. to sys. example t Kmin = min. boiler temperature t Rmin = min. return temperature Please note: A weather-compensated control unit is equipped with soft boiler start, which prevents condensate being formed during the start-up phase. Sizing shunt pump The flow rate of shunt pump V is calculated according to the following formula: V Q N c p ρ W Q N x 3600 V = in m 3 /h c p x t x ρ W = Shunt pump volume flow in m³/h = Rated boiler output in kw = Specific energy 4.2 kws/kgk = Specific weight of water 1000 kg/m³ t = Temperature differential between the flow temperature and bypass temperature (recommended design temperature differential 30k) The shunt pump head results from the boiler pressure loss at the selected volume flow, the pipework pressure loss as well as all individual boiler circuit pressure losses. System example A return temperature limit stat T switches the shunt pump ON, when the permissible return temperature is no longer maintained. A return temperature limit stat T1 switches the shunt pump ON, when the minimum return temperature is no longer maintained. If the return temperature falls further, the return temperature limit stat T2 signals to the control unit R, which throttles the heat transfer via one or several mixers M in the heating circuit. A return temperature limit stat T regulates a distribution valve M, so that if the permissible return temperature is no longer maintained, the heating circuit flow will be partially or fully closed. After the boiler has been heated up, the distribution valve M will open as wide as the permissible return temperature requires. The distribution valve M, can also be installed as mixer into the return. 9

Fill water / burner connection Fill water Water guidelines for heating systems in accordance with VDI 2035 at operating temperatures up to 100 C: Group Total of rated boiler output Q Filling and top-up water Heating water kw *) for exceptions see VDI 2035 (+) may be required, see VDI 2035 Total alkaline earths in mol/m³ ph value Diamide Na 2 SO 3 Excess in mg/kg 0 Q 100 -*) - - - 1 100 < Q 350 1 to 3 8 to 9.5 - - 2 350 < Q 1000 1 to 2 8 to 9.5 2 to 5(+) 5 to 20(+) Water guidelines for heating systems in accordance with VdTÜV guidelines at operating temperatures above 100 C: Filling and top-up water Circulating water Residual hardness p value ph value Diamide Na 2 SO 3 mval/kg mval/kg Excess in mg/kg <0.03 0.5-1.5 8.5-10.0 0.5-25 10-40 Burner connection Observe the TRD 411 (oil combustion) and TRD 412 (gas combustion) guidelines. The gas installation and operation of heating systems must comply with the DVGW Code of Practice "Gas" and the technical connection conditions of your gas supply company and/all local regulations. Burner size MKS-85-140 Acc. to EN 226 adjustable to burner size connection MKS-190 - Burner plate in acc. with blast tube dia. MKS-500 cut-out and tap thread. Match the door insulation to the blast tube diameter of the burner. The blast tube must protrude into the combustion chamber at least 25 mm beyond the door installation. Use fixing screws for the burner flange, which cannot the inserted into the boiler door more than 15 mm. Connect the ventilation fitting at the sight glass with the burner fitting. After the control unit installation, plug the burner cable into the burner. Ensure that the combustion output matches the rated boiler output. Observe the details provided by the burner supplier. Minimum boiler output To prevent the system falling below the dewpoint, the following minimum boiler output for two-stage burners are required for the first stage: MKS MUS Type 85 100 140 190 250 340 420 500 85 100 Output range kw 70-100 85-120 110-160 160-230 200-300 280-380 360-460 420-550 70-85 85-100 Min. boiler output burner stage 1 kw 51 60 84 114 150 204 252 300 51 60 10

Electrical connection Electrical connection Connect the heating circuit pump(s), the return shunt pump and the DHW cylinder loading pump(s) on-site via contactors, if: - three-phase pumps (400 V) are connected. - burner and pump draw more than 2 A each. - the total control unit power consumption is exceeded. Mains power connection 230V 50 Hz 10 A Heating circuit pump(s) / return shunt pump connection To the control unit To the control unit 3 x 1.5 2 Return limit thermostat 3 x 1.0 2 ye/gn PE br L1 bl N bl N ye/gn PE br L1 PE L1 N Heating system emergency stop switch (on site) Heating circuit pump on-site Return shunt pump Burner two-stage without socket part To the control unit To the control unit 7 x 1.0 2 4 x 1.0 2 Burner with socket part Burner plug plug into the control unit Burner plug on the control unit blk ye/gn blu br w gr r 2 3 4 1 7 x 1.0 2 4 x 1.0 2 blk ye/gn bl br w gr r Burner connection Remove the burner plug from the control unit, connect the black to the brown core and connect the white core to the burner phase. Burner socket part Burner socket part 1 st stage 2 nd stage Connection for on-site safety equipment To the control unit blk y blk y To the burner y blk y blk Terminals for low water indicator Control unit junction box Terminals for safety pressure switch Terminals for remote pressure monitoring 11

Safety equipment Safety equipment acc. to DIN 4751 part 1 Scope: Open and sealed, physically protected heat generator systems with flow temperatures up to 100 C. Fresh air ventilation/ exhaustion Thermometer Safety valve Expansion vessel Test line Heat consumer Cap valve Shut-off valve Boiler fill and drain valve Safety valve Expansion vessels of sealed heating systems are provided with a standpipe as safety equipment in accordance with DIN 4750 or a safety valve in accordance with TRD 721. Expansion vessels Install an expansion vessel compliant with DIN 4807 T2 for each boiler system at its highest point. Thermometer A thermometer with sensor well is fitted to the flow of each boiler. Water level indicator Each boiler is equipped with a water level indicator which is visible from the boiler control position, which enables the static pressure of the heating system to be checked that any time. Mark the lowest permissible water level on the water level indicator. Please note: The pipework between the boiler, the expansion vessel and the safety valve must not be able to be shut off. A valve which has been protected against unauthorised closure, e.g. a cap valve, would also be acceptable. The system diagram only indicates the safety requirements but is not a recommendation for specific types of heating network control. 12

Safety equipment Safety equipment acc. to DIN 4751 part 2 Scope: Sealed, thermostatically protected heat generator systems with flow temperatures up to 120 C. Thermometer Heat. circ. pump Safety valve Open flash trap Low water indicator Maximum pressure limiter Pressure gauge Heat consumer External pressure monitoring Fresh air ventilation/ exhaustion Cap valve Expansion vessel Drain valve Minimum pressure switch Boiler fill and drain valve Safety valve Every boiler must be protected against exceeding the permissible operating pressure by a diaphragm safety valve or other spring-biased safety valves. Safety valves must comply with TRD 721. A maximum of three safety valves may be applied to each heat generator. A flash trap must be installed immediately next to each safety valve for boilers with a rated output in excess of 350 kw. The installation of flash traps is not required for hot water heating systems, if each heat generator is equipped with one or an additional STB and one or an additional pressure switch. Sizes and internal diameters of diaphragm safety valves, dimensions of supply lines and blow-off lines. Diaphragm safety valve Blow-off output in kw 50 100 200 350 600 Size, internal diameter, DN 15 20 25 32 40 Fitting thread for supply line G ½" G ¾" G 1" G 1¼" G 1½" Fitting thread for blow-off line G ¾" G 1" G 1¼" G 1½ G 2" Expansion vessels The water and gas chamber of pressure expansion valves must be calculated in accordance with DIN 4807 part 2. If the permissible operating pressure is lower than the highest working pressure of the pressure dwell valve, protect the expansion vessel by suitable type-tested safety valves against excessive pressures. Size open expansion vessels for a minimum pressure of 2 bar. Arrange all expansion vessels with shut-off facilities towards the heating system. Ensure that the shut-off equipment is sufficiently protected against unintentional closure (e.g. cap valve protected with a wire and seal). Low water indicator Equip each boiler with a type-tested low-water indicator. A low-water indicator is not required for boilers up to 350 kw, since excessive heating at low water conditions is prevented. This was verified as part of the type testing of the STB installed in the control unit. 13

Safety equipment Thermometer Install a temperature indicator and a facility for checking the flow temperature into the boiler flow line, so that the actual heating water flow temperature can be recorded. The permissible flow temperature must be permanently marked on the display scale. Pressure gauge The boiler must be equipped with a pressure gauge with immediate connection to the water chamber or in immediate proximity of the flow, as well as a suitable connection for the pressure testing device according to DIN 16263 or DIN 16271. The response pressure of the boiler safety valve and the minimum system pressure must be permanently marked on the display scale. Equip every boiler, which is protected above 3 bar or which has a rated output higher than 350 kw, with a maximum pressure switch (type-tested according to VdTÜV Code of Practice Issue 100/l). External pressure monitoring Monitor the operating pressure of hot water heat generator systems with a minimum pressure switch, type-tested in accordance with the VdTÜV Code of Practice Issue 100/I, in order to prevent water evaporating inside the heating system as a result of insufficient external pressure. Please note: Install a check valve downstream of the boiler circuit pump to prevent incorrect circulation. The pipework between the boiler, the safety valve and the low-water indicator must not be able to be shut off. The system diagram only indicate the safety requirements, but is not a recommendation for specific types of heating network control. 14

Approximate sizing of chimney cross-sections Approximate calculation: Circular cross-sections Required chimney diameter in cm Rated output in kw Effective chimney height in m Square cross-sections Required chimney size in cm x cm Rated output in kw Effective chimney height in m Please note: We recommend that you let your chimney manufacturer design the chimney. 15

Part numbers 1 Thermal insulation 2 Spacers 3 Thermal insulation 4 Back panels 5 Thermal insulation 6 Thermal insulation 7 Thermal insulation 8 Side panels 9 Wolf label 10 Front panel lid 11 Left-hand rear panel lid 12 Right-hand rear panel lid 13 Type plate Steel boiler MKS / MUS 70 up to 550 kw Part no. 85 100 140 190 250 340 420 500 Packing cord for boiler door, 3200 mm long 16 41 401 X X X X X X X X Gasket for clean-out aperture 39 03 000 X X X X X X X X Flat seal/flue gas collector box to approx. 3 rd quarter of 98 16 08 015 X X X - - - - - Flat seal/flue gas collector box to approx. 3 rd quarter of 98 16 08 016 - - - X X - - Flat pack./flue gas collector box to approx. 3 rd quarter of 98 16 08 017 - - - - - X X X Sight glass flat packing 39 01 040 X X X X X X X X Cleaning brush 24 40 240 X X - - - - - - Cleaning brush 24 40 241 - - X - - - - - Cleaning brush 24 40 242 - - - X X - - - Cleaning brush 24 40 243 - - - - - X X X Sight glass 24 00 125 X X X X X X X X Sensor well (up to model M 2850) 45 00 150 X X X X X X X X Sensor well (from model M 2851) 24 25 070 X X X X X X X X Turbulators 89 00 150 X X - - - - - - Turbulators 89 00 151 - - X - - - - - Turbulators 89 00 152 - - - X X - - - Turbulators 89 00 153 - - - - - X X X Jamb brick 16 10 415 X X X - - - - - Jamb brick 16 10 416 - - - X X - - - Jamb brick 16 10 417 - - - - - X X X Casing and insulation from approx. 3 rd quarter of 98 89 00 557 X X - - - - - - Casing and insulation from approx. 3 rd quarter of 98 89 00 561 - - X - - - - - Casing and insulation from approx. 3 rd quarter of 98 89 00 562 - - - X X - - - Casing and insulation from approx. 3 rd quarter of 98 89 00 570 - - - - - X X X MKS 16

Troubleshooting Fault Cause Remedy Burner does not start No voltage present Check fuse, electrical connections, position of ctrl.unit, or enters fault state ON/OFF switch and heat. system emerg. stop switch Oil tank empty / Fill oil tank / Gas supply line shut off Open gas supply line Burner fault High limit safety cut-out has switched OFF Oil filter clogged Press the reset button at the boiler control unit (see burner installation instructions) Press the reset button on the control unit. Replace oil filter Heating circuit System in summer mode Check summer/winter switch position pump does not start Heating circuit pump locked up Turn the pump shaft with a screwdriver Heating circuit pump faulty Replace the heating circuit pump Cylinder loading pump DHW cylinder thermostat faulty Check the DHW cyl. thermostat and replace, if nec. does not run DHW loading pump locked up Turn the pump shaft with a screwdriver Cylinder loading pump faulty Replace the DHW loading pump The heating system operates, Maximum boiler temperature Raise maximum boiler temperature. but room temp. too low set too low 17

18 Notes

Notes 19

Declaration of Conformity in accordance with the 97/23/EC Pressure Device Directive Appendix VII Product designation: Applied conformity assessment procedure: Steel boiler type MKS, MUS Module B + C1 Name and address TÜV Süddeutschland Bau und Betrieb GmbH of the named body: Westendstraße 199 80686 Munich ID of the named body: CE 0036 Applied standards TRD 702 and specifications: DIN EN 297 and 656 We, Wolf GmbH, Industriestraße 1, 84048 Mainburg, hereby declare that the above boiler complies with the appropriate regulations laid down in the 97/23/EC Directive, when the safety temperature has been set to > 110 C. This declaration loses its validity, if the product is modified without our express permission. Observe the safety instructions in the documentation and the operating instructions. Mainburg, 11.06.2002 pp. Steppe 20