ENTROPIE boiler TT100-01

Similar documents
ENTROPIE boiler TT300

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

THW-I NTE. Description THW-I NTE. Industrial Hot Water Boiler THW-I NTE for Oil or Gasfiring. Industrial Hot Water Boiler

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

Homework Chapter2. Homework Chapter3

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

DELTA-TE III. Nozzle-mix line burner

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

INSTALLATION AND OPERATING INSTRUCTIONS

Waste/Multi Oil Boilers from Flexiheat

Easyfire Standalone biomass pellet boiler

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

Multi Energy Boilers. Duo 1 & 2 Triplex 1000 & 3000 Biotriplex. Oil Gas LPG Wood Briquettes Electricity Solar thermal Solar photovoltaics

Controls for Combustion Optimization

INSTALLATION AND OPERATING INSTRUCTIONS. Ariterm 60+

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

Importance of a Draught Regulator

Boiler Technical Specifications (2013)

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Oil and gas solutions. Unicon boiler plants for steam and hot water production

Draft Controls. When to use a Draft Control

Floorstanding Gas Condensing Boilers VITOCROSSAL 100

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

Technical data LA 60TUR+

Solid biofuel solutions

Merloni Elettrodomestici. Technical Fitting Manual OVENS. Language Issue/Edition Page GB /

Installation and maintenance instructions

USERS MANUAL FOR GAS BOILERS

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

ALDRICH COMPANY THREE PASS FIRETUBE BOILER CLASSIC SERIES OPERATING & MAINTENANCE MANUAL

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual

Burner Comparisons. Typical Competitor s Burner

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

C Elba Dual. Cast-iron, floor-standing boiler. High quality Italian product. Life-enhancing heat

Columbia Boiler Company

GB Condensing Gas Boiler

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

Air curtains. 114 MRX condensing gas air curtain. 118 MRA-H gas air curtain. 121 MRA-A ventilation only air curtain

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

ECLIPSE INFORMATION GUIDE

Technical Specification

CHAPTER 10 STEAM AND HOT WATER BOILERS

Installation and operation manual for pellet boiler TANGRA HP 30. Manufactured in accordance with standard: - EN Rev.

Operating manual. Wood pellet boiler. PL M 15 and PL M 25

FIELD OF OPERATION. Multi cyclones Bag filter Flue gas fan Rotary locks Conveying systems Accessories for dust collection plants

INSTALLATION and OPERATION MANUAL DIRECT STEAM KETTLES MOUNTED ON ELECTRIC BOILER BASE CABINET MODELS: EMT-6 EMT-10 EMT-12 EMT-6-6 EMT-10-6 EMT-10-10

Smoke extraction duct of sheet steel

GB Condensing Gas Boiler

Industrial furnaces and associated processing equipment Safety. Part 2: Combustion and fuel handling systems

USER S INFORMATION MANUAL

Single stage operation oil burner

Climate Control System

Installer's Guide. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE YCC-IG EB23D1-12

KDE. PRESSURIZED STAINLESS STEEL CONDENSING BOILER FROM 124 kw TO 2160 kw

LHE OIL LINE HEATER ELECTRIC TYPE

LOW-NOX BURNER RETROFIT CHALLENGE

JÄSPI Solid Fuel Boiler

Light oil - kerosene burner

Steam Fundamentals. (in heating & processing applications)

Multi-fuel oil burners NORTEC WB

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

GB Condensing Gas Boiler

HEADLINE LOREM IPSUM COMPANY EFFICIENCY

COMBUSTION AIR SYSTEM

Technical Concept. Plenum Integrated Filter Fan PIFF 3-AC PIFF 3-EC

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

High Efficiency Oil Fired Hot Water Boiler REPAIR PARTS & OPTIONAL KITS. P/N# , Rev. C [01/09]

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

Module 5: Combustion Technology. Lecture 38: Combustion Burners

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

INSTALLATION AND MANINTENANCE INSTRUCTIONS

NMG NOZZLE MIX GAS BURNERS

Rocket heater GAMERA

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

Math & Physics. Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion.

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

FIELD DRAFT CONTROLS

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

Service Instructions for use by heating contractor VITOROND 200 IMPORTANT. Read and save these instructions for future reference.

INSTRUCTIONS FOR INSTALLATION, SETTING AND USE

Presentation On Industrial Boiler Operation And Maintenance

Technical data LA 28TBS

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

Powerful and efficient trolley cleaning and sanitizing. WS 125 trolley washer. Group

Steel Shell Boilers. Max-3 plus kw. Max-3 E & Max-3 condens E kw. CompactGas kw. SR-plus and SR-H plus kw

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Wall-hung boilers. Spare parts catalogue. ecotec plus

Series LV AIRFLO. In-duct firing line burner

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50

Lattner Boiler Company Model HRT Steam Boilers with Forced Draft Burners

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL XP DRUM KIT PATENT PENDING UTILITY 35 USC 111(A)

Heat Exchanger Module for Industrial Applications

NOZZLE MIX COMBINATION BURNER NMC200 SERIES

Transcription:

ENTROPIE boiler TT100-01 1000 16500 kw 140 о С 8,5 bar

Сontents Field application TT100-01 boilers... 36 Diagram of ENTROPIE boiler TT100-01... 36 Technical characteristics of boilers TT100-01... 37 Overall and connecting dimensions of ENTROPIE boilers TT100-01... 37 Dimensions of boilers TT100-01 firebox... 39 Selecting and installation of the burner... 39 hot water boiler Boiler configuration... 40 Boiler accessories... 41 Boiler placement... 42 Transportation... 42

36 ENTROPIE boiler ТТ100-01 Field application TT100-01 boilers ENTROPIE boilers TT100-01 are high-temperature three-pass hot water gas-tube boilers with capacity ranging from 1,0 to 16,5 MW. ENTROPIE boilers TТ100-01 are designed for heating buildings and facilities and for providing engineering processes of various purposes. Under the conditions of transport, storage, installation and operation, the warranty period is 36 months from the date the boiler begins operation, but no more than 42 months from the date of shipment from the manufacturer. General view of ENTROPIE boiler TT100-01 Diagram of ENTROPIE boiler TT100-01 16 17 7 20 14 10 15 21 12 13 4 18 13 Water outlet 9 14 Emergency valve 15 Water guiding element 16 Burner plate 5 17 Sight glass 8 6 1 2 3 19 22 23 11 18 Flue gas removal outlet 1 Flue tube 2 Second pass fire tubes 3 Third pass fire tubes 4 First reversal chamber 5 Torispherical head 6 Second reversal chamber 7 Front door lining 8 Boiler front door 9 Burner 10 Inspection hole 11 Manhole 12 Water inlet 19 Steel load-bearing supports 20 Heat insulation 21 Checkered aluminum coating 22 Drainage pipe 23 Drain nozzle

37 Technical characteristics of boilers TT100-01 Boiler size Rated heat output, kw 1000 2000 2500 3000 3500 4200 5400 6500 8000 10000 12000 15000 16500 Maximum water temperature, C 140 Minimum water temperature at the boiler inlet, C 60 Maximum operating overpressure of water, bar 8,5 Minimum water flow rate, m 3 /h Not regulated Minimum capacity of the first stage of burner, % Not regulated Efficiency*, % 91,8 90,9 90,6 90,8 91,8 93,5 93,5 92,0 92,3 92,5 91,1 92,3 92,0 Rated water flow rate for Δt = 70 C*, m 3 /h 13 25 31 38 44 53 68 81 100 125 150 188 206 Hydraulic resistance of water path at the coolant flow rate for Δt = 70 C, kpa 0,08 0,16 0,36 0,14 0,13 0,18 0,15 0,26 0,23 0,28 0,26 0,25 0,30 Flue gas flow rate, kg/s 0,44 0,90 1,13 1,35 1,56 1,84 2,36 2,88 3,54 4,41 5,37 6,63 7,32 Aerodynamic resistance of gas path for maximum capacity, Pa 260 830 1005 900 1240 1240 1920 1110 1250 1450 1490 1810 2210 Temperature of outgoing flue gas, С 199 217 223 219 199 165 165 196 190 186 211 190 196 Firebox volume, m 3 0,9 1,3 1,5 2,2 2,4 3,3 4,1 5,2 6,6 8,6 10,8 13,8 13,8 Boiler water volume, m 3 1,80 2,80 3,00 4,10 4,60 5,36 6,42 7,40 9,60 12,12 16,00 20,00 20,00 Dry boiler weight (weight tolerance 4,5 %), kg 3013 4912 5361 7374 8028 10175 11595 14329 17486 20442 24648 30432 30432 * when the boiler water temperature 70/140 C and a residual oxygen content of flue gas of 3 %. Overall and connecting dimensions of ENTROPIE boilers TT100-01 L3 i L4 d L5 e b f L6 c The overall and connecting dimensions of boilers with a heat output of 1000 kw provide for one safety pipe (d); in addition, these boilers have no slinging holes (distance В1). Dimensions L3 L6 in accordance with this drawing.

38 ENTROPIE boiler ТТ100-01 В1 В2 L2 L3 L4 d i e b f c L5 L6 L7 L8 a l g В3 C L1 H4 H5 j k H3 H2 H1 H L Overall and connecting dimensions Rated heat output, kw 1000 2000 2500 3000 3500 4200 5400 6500 8000 10000 12000 15000 16500 Flue gas outlet, DN a 300 500 500 500 500 650 650 800 800 900 1000 1000 1000 Water inlet, DN b 125 150 150 200 200 200 250 250 300 300 350 400 400 Water outlet, DN c 125 150 150 200 200 200 250 250 300 300 350 400 400 Safety valve, DN d 50 65 65 65 65 80 80 100 100 125 125 125 125 Temperature sensor (inlet) e G 1/2-B Temperature sensor (outlet) f G 1/2-B Flue gas temperature sensor g G 1/2-B Inspection hole, mm i 252x190 Boiler water drainage, mm j 40 50 Condensate removal k G 1-B Draft and heat gauge l G 1/2-B Length, mm L 2747 3323 3573 4064 4370 4819 4991 5352 5648 6289 6805 7401 7401 Width, mm B 1540 1740 1740 1944 1940 2100 2200 2360 2500 2680 2860 3060 3060 Height, mm H 1768 2043 2043 2228 2228 2430 2420 2574 2710 2862 3074 3276 3276 Length of supporting frame, mm L1 2240 2460 2710 3120 3520 3687 3869 4200 4500 5135 5470 6135 6135 Cover width, mm L2 225 275 275 325 325 325 323 327 325 327 329 329 329 Distance, mm L3 333 133 133 133 128 276 276 448 608 481 414 574 574 Distance, mm L4 300 250 250 300 300 300 300 470 500 500 500 600 600 Distance, mm L5 300 400 400 400 400 700 700 470 490 500 440 850 850 Distance, mm L6 430 900 1150 1250 1650 1400 1400 1500 1500 1850 2000 1700 1700 Distance, mm L7 400 550 550 600 600 700 800 900 1000 1400 1600 2000 2000 Distance, mm L8 745 803 803 952 955 1010 1178 1134 1213 1217 1506 1332 1332 Distance, mm В1-1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 Distance, mm B2 490 500 500 500 500 500 670 738 960 660 762 760 760 Width of supporting frame, mm B3 910 1152 1152 1152 1152 1528 1540 1580 1800 1800 1820 1940 1940 Distance, mm H1 1360 1555 1555 1760 1760 1857 1888 1970 2070 2130 2364 2514 2514 Distance, mm H2 910 1085 1085 1170 1170 1257 1238 1314 1370 1450 1564 1664 1664 Distance, mm H3 560 610 610 620 620 657 638 614 620 700 614 614 614 Distance, mm H4 239 315 315 301 301 323 245 237 213 290 227 230 230 Distance, mm H5 107 181 181 166 166 163 109 120 92 91 105 105 105 Note. The boilers with heat output of 1000 kw and 1500 kw have no slinging holes (distance B1). Dimensions L3 L6 in accordance with the diagram on page 36.

39 Dimensions of boiler TT100-01 firebox 1 Burner flame head 1 2 d D2 2 Rigid heat insulation of front door 3 Elastic heat-insulating material 3 s s1 L1 L2 Burner installation Boiler size 1000 2000 2500 3000 3500 4200 5400 6500 8000 10000 12000 15000 16500 Diameter of installation hole, d, mm 310 380 380 450 450 480 450 500 590 590 730 730 730 Thickness of cover, taking into account the adapter plate, s, mm 247 297 297 347 347 347 345 349 347 349 347 347 347 Installation size of burner, s1, mm 20 60 Firebox diameter, D2, mm 600 780 780 900 900 1000 1100 1180 1280 1380 1500 1600 1600 Flue tube length, L1, mm 1905 2355 2605 2905 3305 3650 3805 4105 4470 5105 5405 6105 6105 Firebox length, L2, mm 2139 2628 2878 3223 3623 3975 4156 4503 4888 5538 5891 6614 6614 Selection and installation of the burner The aerodynamic characteristics of the burners and their placement shall ensure that the flame fills the firebox uniformly without affecting the firebox material and prevent any areas becoming stagnant or poorly ventilated within the firebox volume. Burners to be used with ENTROPIE boilers TT100-01 shall have a forced air supply with a regulated air excess factor. Starting up burners, combustion chamber blowing, operation, and shutdown should be performed automatically. ENTROPIE boilers TT100-01 are operated with excess pressure in the firebox. In selecting burners, it is necessary to take into account the following factors: length and diameter of the firebox, aerodynamic drag of the boiler. Hot water ENTROPIE boilers TT100-01 can be operated with rotary fan combined burners designed for combustion of gas and liquid fuel.

40 ENTROPIE boiler ТТ100-01 The burner model shall pass industrial tests and meet the requirements of DIN EN 267, 676. To order a hot water ENTROPIE boiler TT100-01 complete with burner, it is necessary to indicate the gas pressure in case of using gas as the main or reserve fuel. When ordering a burner, check that its connecting dimensions and flame head dimensions comply with the technical requirements for the boiler and this technical data sheet. An additional extension and/ or intermediate flange shall be ordered when the burner is fitted with a long flame head. Manufacture of a special door for installation of a burner with individual characteristics is possible. The burner gas line shall contain a compensator. It will relieve mechanical loads on the gas pipeline during boiler maintenance and operation. The burner flame head is equipped according to the manufacturer's requirements. The burner flame head shall be inserted in the firebox, taking into account the dimensions s1. The space between the burner flame head and rigid heat insulation of the boiler front door should be sealed with an elastic heat-insulating material attached to the boiler (this should be installed around the perimeter of the burner hole on the front door). Boiler configuration Several options of boiler delivery sets are available depending on the equipment: full delivery set, partial delivery set, or delivery without parts. The full delivery set includes a boiler with burner equipment, set of parts and components installed according to the information specified in the questionnaire. Due to factory installation, the optimal and reliable operation of all boiler units is guaranteed. Elastic material is supplied as part of the boiler delivery set for sealing the annular gap between the burner flame head and rigid thermal insulation of the front door. On request the boiler can be supplied with the partial delivery set equipment (boiler fitted with a burner and relief valves) or without parts. In the latter case, the customer will independently equip the boiler with burners, safety devices, and automatic controls.

41 Boiler accessories On additional request the manufacturer can deliver the following accessories for boilers: Plate for burner Flange for burner Collecting channel of the safety group for connecting sensors and monitoring devices Pressure limiters for minimum and maximum pressure Safety valves Temperature sensors Three-way valve Boil-off protection sensor Other accessories for boiler installation and maintenance

42 ENTROPIE boiler ТТ100-01 Boiler placement The distance from the boiler front to the wall of the boiler room shall leave enough space for boiler maintenance and repair, and no less than 3 m. During operation, for boilers running on gaseous or liquid fuel, the distance from the protruding parts of the burner devices to the boiler room wall shall be at least 1 m. The width of passageways between the boiler and the boiler room wall shall be at least 1 m. passageway, and there shall be a minimum distance of 70 mm between them. The width of the passageway between the boiler and the rear wall of the boiler room shall be wide enough for carrying out maintenance, repair, and installation of the connecting element of flue tube. In this case, the width of the passageway shall be at least 1 m. In case the boiler is installed near walls or columns, the insulation of the boilers shall not be in close contact with the boiler room wall if there is no Deviations from the recommended distances are allowed but only within the distances specified in the local regulatory documents. Transportation Subject to the approval of the customer and relevant authorities, the boiler can be transported by any mode of transport. During boiler transportation, the open flange and fitting connections, cable insertions shall be plugged, all temporary openings shall be closed. During transportation and storage it is necessary to take precautions in order to protect the boiler against mechanical damages. Special slinging devices, namely, eye bolts, are provided for the process of loading, unloading, and placing the boiler (units, boiler elements) in its permanent location. Boiler slinging with the use of other elements is not allowed. Operation of hoisting devices shall prevent any sliding (dragging) of any part, unit and vehicles along the surfaces of storage areas. Slinging and lifting from other parts of the boiler is not allowed! The boiler shall be loaded on a vehicle using cranes with the corresponding lifting capacity, equipped with beams and lifting devices. The boiler shall be secured to vehicles in accordance with the corresponding specifications for cargo handling and securing for each mode of transport.

43 L d B B1 CoM L1 1 1 20 30 о 50 70 о Boiler transportation diagram 2 H 2 1 50 70 о 80 110 L2 2 1 1 B2 2 80 110 60 Center of mass Means of fastening 1 Tilt protection 2 Diagonal fastening Diagram for boiler slinging Description Numerical value Rated heat output, kw 1000 2000 2500 3000 3500 4200 5400 6500 8000 10000 12000 15000 16500 Length, L, mm 2868 3443 3693 4184 4485 4944 5146 5503 5790 6440 6962 7550 7550 Width, B, mm 1540 1740 1740 1944 1940 2100 2200 2360 2500 2680 2860 3060 3060 Height, H, mm 1768 2043 2043 2228 2228 2430 2420 2574 2710 2862 3074 3276 3276 Distance, B1, mm - 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 Distance, B2, mm 245 250 250 250 250 250 335 369 480 330 381 380 380 Diameter of transportation hole, d, mm - 28 28 28 28 28 28 28 28 28 28 28 28 Center of mass, L1, mm 1011 1226 1364 1506 1706 1872 2023 2137 2266 2674 2833 3191 3191 Distance, L2, mm 1100 1530 1780 1525 2370 2300 2300 2645 3400 3325 3955 4355 4355 Weight, m, kg 3013 4912 5361 7374 8028 10175 11595 14329 17486 20442 24648 30432 30432