Influence of the operating time on the behavior of smoke alarms in typical office environments

Similar documents
SupDET 2015 Characterization of Dust and Water Steam Aerosols in False Alarm Scenarios

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

15 th International Conference on Automatic Fire Detection PROCEEDINGS. October 14-16, 2014 Universität Duisburg-Essen Duisburg, Germany

UL268 7 th challenge with single infrared smoke detector

Early Warning Fire Detection Engineering

Research into multi-sensor detector capabilities and false alarm reduction

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

Research on Evaluation of Fire Detection Algorithms

Towards Predicting High Sensitivity Smoke Detector Operational Performance in Building Environments

A Comparison of Aspirated Smoke Detectors

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

Monitoring of Penetration System Performance due to ISO by using Test Panels due to ISO

Procedure for the Approval of New Fire Detection and Alarm Technologies

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

FCP 320/FCH 320 Conventional Automatic Fire Detectors

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

A P P L I C A T I O N S G U I D E. Single-Ended Reflected Beam Smoke Detector

Directories. B.1 Keyword Directory B.2 Tables B.3 Figures B.4 End Notes Fire Safety Guide / Siemens Switzerland Ltd

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Available online at Procedia Engineering 45 (2012 )

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

International Standardization of Oxygen Reduction Systems for Fire Protection

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection

Smoke Detector Testing

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles

Open-area Smoke Imaging Detector. Engineering Specification

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

IQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology

D296/D297. Application Guide. Projected Beam Smoke Detectors

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

FIDAS FINE DUST MONITORING SYSTEMS

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Ex Products Highest level of safety under the most difficult conditions

KEYWORDS: Smart fire detection, fire signatures, nuisance sources, non-fire signatures

THE NEXT GENERATION IN VISIBILITY SENSORS OUTPERFORM BOTH TRADITIONAL TRANSMISSOMETERS AND FORWARD SCATTER SENSORS

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

Recent BRANZFIRE enhancements and validation

Solution F2. Fire Alarm Control Panels one step ahead.

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

The performance of multi-sensors in fire and false alarm tests

Foundations of Fire Safety in Civil Engineering

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

Early Fire Detection and Automatic Extinguishing in Waste-to-Energy Power Plants and Waste Treatment Plants

OFDR-Temperature Sensing using Existing Fiber-Optic Communication Cables An Application for Automatic Fire Detection?

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Battery Performance Alert: A TOOL FOR IMPROVED PATIENT MANAGEMENT FOR DEVICES UNDER BATTERY ADVISORY

Prereq: FOD 131 or Instructor Permission

by Richard W. Bukowski Center for Fire Research Program for Fire Detection and Control Systems National Bureau of Standards Washington,

Cerberus FIT conventional system

Building and Characterizing 14GHz InGaAs Fiber Coupled Photodiodes

S TEM PRODUCT SPECIFICATION

Audit/Twinning Report

Brine Generation Study

FAP-420/FAH-420 Automatic Fire Detectors LSN improved version

Protecting you and your home

LaserFOCUS VLF-250 Engineering Specification

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

COMP201: Software Engineering I. Assignment 1, Part 1 (2017/2018) (100% mark for Assignment 1 is 10% of COMP201 grade)

Fire protection for railway vehicles

Fire protection for rolling stock. Innovative solutions from Siemens Building Technologies. Answers for infrastructure and cities.

Keywords: Fire detection, smoke alarm, nuisance, UL 217, polyurethane foam

The FireBird mission - a scientific mission for Earth observation and hot spot detection

Prerequisite/Co-requisite: Pass the reading and writing portions of COMPASS or other accepted testing instrument.

CCTV, HOW DOES IT WORK?

Standard ECMA th Edition - December Declared Noise Emission Values of Information Technology and Telecommunications Equipment

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS

Abstract. Introduction

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Battery Performance Alert

Test One: The Uncontrolled Compartment Fire

Availability, Reliability, False Alarm Resistance Best Practice in Fire Alarm Systems. FIRE PROTECTION OF ROLLING STOCK 2 rd March 2017

CONFIRMATION of Product Conformity (QAL1)

Temperature Data Logging

Chapter 17, Initiating Devices

4. The Whitman College Chemical Hygiene Officer is Fred Miller, Manager, Environmental Health and Safety.

Press Presse Press Presse

½ CAUTION ½ DANGER. Getting to know the smoke detector. ARGUS Smoke Detector Single. Accessories. Operating instructions. For your safety A B C D E

Open-area Smoke Imaging Detection (OSID)

A Model of the Population of Fire Detection Equipment Based on the Geometry of the Building Stock

Fire protection for emergency power supply

AEROSOL SPECTROMETERS

VESDA VLP. Engineering Specification

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

VICOTEC450 EXTRACTIVE VISIBILITY MEASURING DEVICES EXTRACTIVE VISIBILITY MEASUREMENT FOR INCREASED SAFETY IN TUNNELS

Gambling with your fire security?

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS

Diagnostics with fieldbus

Australian Standard. Fire detection and alarm systems. Part 6: Carbon monoxide fire detectors using electro-chemical cells

Open-area Smoke Imaging Detection (OSID)

Dated 15-Dec-2000; J. Schilz, subject to change

TESTS OF ADSIL COATING

Transcription:

Wolfgang Krüll, University of Duisburg-Essen Chair of Communication Systems Influence of the operating time on the behavior of smoke alarms kruell@nts.uni-due.de http://nts.uni-duisburg.essen.de

University of Duisburg-Essen, Germany One of the youngest universities in Germany Among the top 10 of the biggest universities in Germany Located in the heart of the Ruhr metropolis Number of students 41.000 Percentage of international students 13 % Number of employees 4700 Number of faculties 11 Humanities, Social Sciences, Educational Sciences, Mathematics, Engineering, Physics, Chemistry, Biology, Medicine, Economics and Business Administration, Mercator School of Management Faculty of Engineering (74 departments) 11.000 students Department of Communication Systems, NTS Organizer of the International Conference on Automatic Fire Detection AUBE '14 1

Heinz Luck Fire Lab, University of Duisburg-Essen, Germany Fire Lab Surface area Flexible room height 34.5 ft * 29.5 ft 9.4 ft 21.5 ft Test scenarios Fire tests in the initial stage of a fire (EN 54) Experiments concerning the distribution of smoke and fire gases under variable conditions Non-standard test scenarios (e.g. Airbus A400M-reproduction) 2

Heinz Luck Fire Lab, University of Duisburg-Essen, Germany Fire Lab Surface area Flexible room height 34.5 ft * 29.5 ft 9.4 ft 21.5 ft Test scenarios Fire tests in the initial stage of a fire (EN 54) Experiments concerning the distribution of smoke and fire gases under variable conditions Non-standard test scenarios (e.g. Airbus A400M-reproduction) Dust, spray and water fog tests Nuisance tests of smoke detectors in high humidity environments 2

Influence of the operating time on the behavior of smoke alarms Motivation Aim of the study Description of the performed tests Measuring results Summary 3

The German standard DIN 14675 Fire-alarm systems - installation and operation Describes the proper setup, operation and maintenance of an automatic fire alarm system having a direct connection to the fire brigade In the framework of maintenance the response behavior of smoke alarms has to be tested or the detectors have to be replaced after 5 resp. 8 years (depending on the detector technology) Reason for the fixed cycles of substitution of smoke alarms are expected long-term changes of the response behavior due to pollution and the aging of components 4

The German standard DIN 14675 Fire-alarm systems - installation and operation No answer how the value of 8 years has been calculated In heavily polluted environments 8 years may be too high An earlier exchange can reduce the number of false alarms In clean environments 8 years may be too short (e.g. office buildings) An exchange of smoke alarms in clean environments at a later date can reduce costs and save resources 5 years?? 8 years The standard does not distinguish between different installation conditions 5

Aim of the study Determination of long-term changes of the response behavior due to pollution and the aging of components Measurements possibly are able to give essential hints Response threshold value (RTV) EN54 part 7, chap. 5.1.5 Repeatability EN54 part 7, chap. 4.3.1 Directional dependence EN54 part 7, chap. 4.3.2 Reproducibility EN54 part 7, chap. 4.3.3 (in our case as many detectors as possible ) 6

Aim of the study Analysis and documentation of the influence of the environment and the operating life on the response behavior A particular focus of this series of tests was to investigate the behavior of new optical smoke detectors by comparison with optical smoke detectors of different age groups The old detectors were collected from office buildings 4 age groups of old detectors 2-5 years of operating life 6-8 years of operating life 9-12 years of operating life more than 12 years of operating life 7

Quantity structure of the collected and tested detectors New detectors Detectors with 2-5 years of operating life Detectors with 6-8 years of operating life Detectors with 9-12 years of operating life Detectors with more than > 12 years of operating life Detector type 1 10 0 0 22 12 Detector type 2 11 5 13 10 0 Detector type 3 10 4 16 24 10 Detector type 4 10 5 8 11 0 Detector type 5 4 1 2 0 0 45 15 39 67 22 No detectors of this type with an operating life of 2.. 8 years 45 new optical smoke detectors 143 old optical smoke detectors No detectors of this type with an operating life of more than 12 years 8

Lorenz AGW test aerosol generator & EN54 smoke tunnel Response Threshold Value was measured by the MIREX extinction measuring device 9

Principle of the measurement system 10

Requirement for the increase of the aerosol concentration for EN54 tests in the test tunnel (e.g. measurement of the response behaviour and directionality) 0.015 db m -1 min -1 m / t 0.1 db m -1 min -1 Typical slew rate of smoke concentration for EN54 tests 0,06 db m -1 min -1 11

Tests with new detectors Directional Dependence 1 new detector of each detector type 8 measurements of the Response Threshold Value (RTV) after each measurement the detector was turned by 45 Direction with the highest RTV, m max direction with the lowest sensitivity Direction with the lowest RTV, m min direction with the highest sensitivity Repeatability 3 additional measurements at the angle with the highest RTV, m max Reproducibility 9 new detectors of each type at the angle with the highest RTV, m max 12

Measuring results for a new detector, type 1 Angle [deg.] m [db/m] m [db/m] m [db/m] m [db/m] m max / m min < 1.6 Detector 1-6N075 0 0,155 45 0,163 0,164 0,166 0,162 1,022 Repeatability 90 0,155 135 0,152 180 0,152 225 0,148 270 0,147 315 0,149 1,105 Directional dependence Detector 1-6N074 0,173 Detector 1-6N076 0,194 Detector 1-6N077 0,181 Angle with the lowest sensitivity Requirements to pass the EN54 paraffin oil tests Repeatability m max / m min < 1.6 Directional dependence m max / m min < 1.6 Reproducibility m max / m mean 1.33 m mean / m min 1.5 Detector 1-6N078 0,183 0,184 m mean Detector 1-6N079 0,180 0,199 m max Detector 1-6N080 0,186 0,163 m min Detector 1-6N081 0,199 1,081 m max / m mean 1.33 Detector 1-6N082 0,198 1,133 m mean / m min 1.5 Detector 1-6N083 0,185 Reproducibility 13

Directional Dependence of new detectors Detector type 1 Detector type 2 Detector type 3 Detector type 4 Detector type 5 14

Tests with old detectors Directional Dependence 50 % of the old detectors of each detector type 4 measurements of the RTV of each detector after each measurement the detector was turned by 90 Measurements include the angle with the lowest sensitivity (m max ) of a new detector 1 repetition for each measurement Reproducibility & Repeatability 50 % of the old detectors of each detector type 3 measurements of the RTV of each detector at the angle with the lowest sensitivity (m max ) of a new detector 15

Total number of measurements depending on the operating life New detectors Detectors with 2-5 years of operating life Detectors with 6-8 years of operating life Detectors with 9-12 years of operating life Detectors with more than > 12 years of operating life Number of tests Detector type 1 21 - - 132 68 221 Detector type 2 21 24 80 60-185 Detector type 3 20 24 92 144 60 340 Detector type 4 20 24 48 68-160 Detector type 5 14 8 16 - - 38 Total number of measurements depending on the operating life 96 80 236 272 128 944 A total of 944 measurements of new and old detectors were collected The directionality and RTV tests were done repeatedly with identical configuration The scattering result values were averaged 16

Number of tests Measurement of response value of detector type 1, angle 45 m max m mean m min 1 line = 1 measurement 10 detectors 22 detectors 12 detectors Detector age 17

Number of tests Measurement of response value of detector type 1 Angle with the lowest sensitivity of a new detector type 1 is 45 1 of 12 detectors is more sensitive 2 of 38 measurements 10 det. 22 det. 12 det. Higher sensitivity = more false alarms 97 % of the old detectors type 1 Detector age have passed the test for new detectors Detector type 1 EN54 new detector 2-5 years 6-8 years 9-12 years > 12 years m min 0.162 - - 0.150 0.093 m max 0.199 - - 0.216 0.155 m mean 0.179 - - 0.188 0.154 m max / m mean 1.33 1.11 - - 1.15 1.29 m mean / m min 1.5 1.11 - - 1.25 1.66 18

Number of tests Measurement of response value of detector type 2, angle 90 11 detectors 5 detectors 13 detectors 10 detectors Detector age 19

Number of tests Measurement of response value of detector type 3, angle 135 10 4 16 24 10 detectors Detector age 20

Number of tests Measurement of response value of detector type 3, angle 135 Angle with the lowest sensitivity of a new detector type 3 is 135 1 of 16 detectors is less sensitive 4 of 50 measurements A lower sensitivity increases 10 4 16 24 10 detectors the probability that a possible fire Detector age will be detected too late 98 % of the old detectors type 3 have passed the test for new detectors Detector type 3 EN54 new detector 2-5 years 6-8 years 9-12 years > 12 years m min 0.155 0.143 0.162 0.152 0.182 m max 0.191 0.190 0.269 0.239 0.233 m mean 0.172 0.168 0.187 0.184 0.204 m max / m mean 1.33 1.11 1.13 1.43 1.30 1.14 m mean / m min 1.5 1.11 1.17 1.16 1.21 1.12 21

Number of tests Measurement of response value of detector type 4, angle 270 6 10 detectors detectors 8 detectors 11 detectors Detector age 22

Summary Key aspect of the study was the verification of the behavior of new and old optical smoke detectors with respect to the defined EN54 requirements A total of 944 measurements of 45 new and 143 old optical smoke detectors were collected and analyzed The old detectors were collected from office buildings (relatively clean areas) 23

Summary Directional Dependence No conspicuous features The EN 54 requirement m max / m min < 1.6 was met by all tested detectors even after more than 12 years of operating life However, it can be observed that the angle with the lowest sensitivity of detector type 4 has changed from 270 to 90 Detector with 9-12 years operating life compared with a new detector 24

Summary Reproducibility and aging effects The production spread of new smoke alarms has to be within the limits m max / m mean 1.33 and m mean / m min 1.5 To show possible indications of e.g. aging of the detectors these values were calculated for each of the 4 age groups 25

Summary Reproducibility and aging effects The production spread of new smoke alarms has to be within the limits m max / m mean 1.33 and m mean / m min 1.5 To show possible indications of e.g. aging of the detectors these values were calculated for each of the 4 age groups Only minor changes with two exceptions A general trend to lower or higher RTV as a function of the operating age could not be determined A minor age-dependent variation may be determined depending on the detector type 25

Summary Reproducibility and aging effects 2 detector types may be more sensitive with advancing age Detector type 1 changes of m mean 14 % (age > 12 years) Detector type 4 changes of m mean 15 % (9-12 years old) Higher sensitivity more false alarms no problem the detector will be exchanged 26

Summary Reproducibility and aging effects 2 detector types may be more sensitive with advancing age Detector type 1 changes of m mean 14 % (age > 12 years) Detector type 4 changes of m mean 15 % (9-12 years old) Higher sensitivity more false alarms no problem the detector will be exchanged Detector type 3 trend to lower sensitivity changes of m mean 9 % (age < 12 years) changes of m mean 19 % (age > 12 years) Detector type 2 no trend to higher or lower sensitivity Detector type 5 no trend to higher or lower sensitivity 26

Summary It can be shown that the age limit of 8 years (DIN 14675) is not an insurmountable problem. It should be stressed that the study should not be valued as absolute proof. The performed investigations show first important details for a possible review of the defined age limit. The study represents only a very small sample of detectors. A scientifically sound statement requires a significantly larger number of smoke alarms from different manufacturers and different areas of application. 27

Outlook Sensitivity test after??? years at regular intervals during operation, e.g. with trutest? trutest provides a linear increase of the aerosol concentration. The light obscuration is measured in %/ft. The result is not comparable with EN54 smoke tunnel tests due? to a different areosol. In new installations the RTV of each smoke alarm has to be measured. 28

Outlook Sensitivity test after??? years at regular intervals during operation, e.g. with trutest? trutest provides a linear increase of the aerosol concentration. The light obscuration is measured in %/ft. The result is not comparable with EN54 smoke tunnel tests due to a different areosol. In new installations the RTV of each smoke alarm has to be measured. Cost-benefit analysis: What is more expensive, the replacement after 5 resp. 8 years or further re-testing? Discussing the matter with the standardization bodies? Extension to 8 + X years? Define X No hard deadline for replacement, but a risk analysis? Companies with an own fire service make a decision by themselves? The predicted life time? Current smoke alarms are equipped with a 10 year battery. The behavior of multisensor detectors (e.g. with a CO-sensor)? The behavior of detectors with integrated pollution compensation??? Measurements with a larger number of smoke alarms from different manufacturers and different areas of application. 28

Thank you for your attention! http://nts.uni-due.de

Publications Wolfgang Krüll, Thorsten Schultze, Robert Tobera & Ingolf Willms Characterization of Dust and Water Steam Aerosols in False Alarm Scenarios - Design of a Test Method for Fire Detectors in Dusty and in Highly Foggy Environments SupDET 2015, Orlando, Florida, U.S.A., March 2015 W. Krüll, T. Schultze, R. Tobera & I. Willms Apparatus for the test of fire detectors in dusty environments 15th International Conference on Automatic Fire Detection, AUBE '14, Duisburg, Germany, October 2014 R. Tobera, W. Krüll, T. Schultze & I. Willms Apparatus for the test of fire detectors in high foggy environments 15th International Conference on Automatic Fire Detection, AUBE '14, Duisburg, Germany, October 2014 W. Krüll, T. Schultze, R. Tobera & I. Willms Characterization of dust aerosols in false alarm scenarios 15th International Conference on Automatic Fire Detection, AUBE '14, Duisburg, Germany, October 2014 W. Krüll, T. Schultze, R. Tobera & I. Willms Analysis of dust properties to solve the complex problem of non-fire sensitivity testing of optical smoke detectors 9th Asia-Oceania Symposium on Fire Science and Technology, AOSFST, Hefei, China, October 2012. W. Krüll, T. Schultze, I. Willms & A. Freiling Developments in Non-Fire Sensitivity Testing of Optical Smoke Detectors - Proposal for a New Test Method 10th International Symposium on Fire Science, University of Maryland, College Park, Maryland USA, June 2011 W. Krüll, T. Schultze, I. Willms & A. Freiling Development of a test installation to determine false alarm susceptibility of smoke detectors International s+s report, number 1, 4/2011, page 10 15, VdS, Cologne, Germany, 2011 W. Krüll, T. Schultze, I. Willms & A. Freiling Test Apparatus for the Evaluation of the Behaviour of Smoke Detectors in non-fire Situations 2010 International Symposium on Safety Science and Technology, 2010 ISSST, Hangzhou, China, October 2010 I. Willms & W. Kruell Developments in Non-Fire Sensitivity Testing EUSAS Conference on "Fire Detection: State of the Art and Future Development", Zug, Switzerland, June 2010 29