OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

Similar documents
OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET-1000 (12 VDC)

SET-2000 Oil/Sludge 12 VDC

SET Installation and Operating Instructions. Level switch for one sensor

SET-2000 Hi Level/Oil

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

AND INSTALLATION MANUAL

SolarSET GSM SolarSET GSM with a Beacon

Labkotec automatic warning devices for separators protecting the environment

Operating Instructions

4) Intrinsic Safety Certification

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

DB5 Intrinsically Safe Sounder Type DB-5

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success

Inductive slot sensor

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION

Technical Data. Dimensions

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

INSTRUCTION MANUAL (ATEX)

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

IECEx Certificate of Conformity

E2S Datasheet v10a. The IS-mA1 is suitable for all intrinsically safe signalling applications including fire, security and process control.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Technical Data. Dimensions

INSTRUCTION MANUAL. SIL 2 Load Cell/Strain Gauge Bridge Isolating Converter DIN-Rail Power Bus and Termination Board Model D5264S D5264S

Battery Powered Separator Alarm Type Standalone Unit. Installation, Operation & Maintenance

Installationsmanual GWSL1100/2100, GWML3100

Earth-Rite II PLUS Static Earthing System

OPTIBAR P 1010/2010 C Supplementary instructions

Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS

Labkotec Ice Detector

Technical Data. General specifications. Rated operating distance s n 5 mm

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Universal Tank Alarm Type Installation, Operation & Maintenance

14300 MAINS SEPARATOR ALARM MANUAL

PEPPERL+FUCHS GmbH

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Technical Data. General specifications Switching element function Rated operating distance s n 8 mm

INTRINSICALLY SAFE S314X AND S315X

OMC Ex interface unit. Manual. Version 1.2 August Author: Observator Instruments

IECEx Certificate of Conformity

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Operating Instructions Edition 02/2007

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO

SBEx-4 BISTATE SEPARATOR 1, 2, 3 or 4 channels in rail housing (TS35, 22,5mm width)

User s Manual YTA610 and YTA710 NEPSI Certification

EU DECLARATION OF CONFORMITY

MANUAL Oil Level Sensor

Safety instructions VEGAPULS 64

VERSAFLOW VORTEX Supplementary instructions

Tank Gauging System Special Safety Instruction

Local Control Panels for VG9000H LCP9H Series. Installation, Maintenance and Operating Instructions

E2S Datasheet v10a

Local Control Panels for VG9000H LCP9H Series. Installation, Maintenance and Operating Instructions

LevelSET S GSM Functionalities Instructions for Commissioning and Use

Alarm system For oil-water separator

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

OPTIBAR DP 7060 Supplementary Instructions

PROTECT SRB 200EXi-1A

Snifter ATEX22 VERSION. User Manual. Distributor

INSTRUCTION MANUAL (ATEX / IECEx)

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.

Documentation. Explosion-Protection. for Smoke Detection Panels SDS-4, SDS-8, SDS-12 and Extension Panels SDS-E8, SDS-E12, SDS-E16, SDS-EC16

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

Fixed Gas Detection System/Meridian CERTIFICATION

D SYSTEM CONTROL DWG. APPROVED BY. OrCAD 6 ROSEMOUNT 2410

Operating Manual MS220DA

MANUAL Overflow sensor NVF-104/34-PF

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma,

OPTIWAVE X500 Supplementary Instructions

EUROFLAT SERIES TYPES C... S... M...

Intrinsically Safe Flame Detector Installation Guide

Intrinsically Safe Solutions

FDOOT241-A9-Ex Multisensor fire detector

ATEX Installation Instructions for Micro Motion F-Series Sensors with Certificate DMT 01 ATEX E 158 X

Ex Long & Short stroke LPI POSITION TRANSMITTER MKII For linear position measurement in compressors

OOH740-A9-Ex Multi-sensor fire detector

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

Operating Manual MS220KA and MSR220KA

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

LC2200 Level Controller Installation and Maintenance Instructions

INSTRUCTION MANUAL. Frequency-Pulse Converter, Repeater and Trip Amplifiers Din-Rail Model D1060S D1060S

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Technical Data. Dimensions

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

PROFIBUS-PA Display RID 261 PROFIBUS-PA

ExDetector HC-100. Data Sheet. Gas Measuring and Alarm Systems

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

BA334D Intrinsically safe Externally powered pulse input field mounting rate totaliser Issue 13

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Analog Room Pressure Monitor RPC Series

KHA6-GT*-Ex1. Thermocouple trip amplifiers. Composition. Hazardous area. Safe area. Function. 230 V AC 1-channel. Input EEx ia IIC

Transcription:

Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000 Oil Separator Alarm Device with SET/DM3AL sensor Copyright 2012 Labkotec Oy We reserve the right for changes without notice

TABLE OF CONTENTS 1 GENERAL... 3 2 INSTALLATION... 4 2.1 OilSET-1000 control unit... 4 2.2 SET/DM3AL sensor... 5 2.3 Junction box... 5 3 OPERATION AND SETTINGS... 6 3.1 Operation... 6 3.2 Factory settings... 7 4 TROUBLE-SHOOTING... 8 5 REPAIR AND SERVICE... 9 6 SAFETY INSTRUCTIONS... 9 7 TECHNICAL DATA... 10 SYMBOLS Warning / Attention Pay special attention to installations at explosive atmospheres Device is protected by double or reinforced insulation Copyright 2012 Labkotec Oy 2/13 We reserve the right for changes without notice

1 GENERAL OilSET-1000 is an alarm device for monitoring the thickness of the oil layer accumulating in an oil separator. Depending on the order, the delivery consists of OilSET-1000 control unit, SET/DM3AL sensor, junction box and installation supplies. Figure 1. Oil separator alarm system SET/DM3AL sensor is installed into the light liquid storage chamber and gives an alarm when the chamber is filled to a pre-determined degree. The sensor is normally immersed in water. The function is based on the measurement of the electrical conductivity of the surrounding liquid water conducts electricity much better than oil. Oil separator is regarded as potentially explosive (Ex) area. SET/DM3AL sensor can be installed in a zone 0, 1 or 2 potentially explosive area but the control unit must be mounted in a safe area. The LED indicators, push buttons and interfaces of the OilSET-1000 control unit are described in figure 2. Figure 2. OilSET-1000 control unit - features Copyright 2012 Labkotec Oy 3/13 We reserve the right for changes without notice

2 INSTALLATION 2.1 OilSET-1000 control unit OilSET-1000 control unit can be wall-mounted. The mounting holes are located in the base plate of the enclosure, beneath the mounting holes of the front cover. The connectors of the external conductors are isolated by separating plates. The plates must not be removed. The plate covering the connectors must be installed back after executing cable connections. The cover of the enclosure must be tightened so, that the edges touch the base frame. Only then do the push buttons function properly and the enclosure is tight. Before installation, please read the safety instructions in chapter 6! Figure 3. OilSET-1000 alarm device installation. Copyright 2012 Labkotec Oy 4/13 We reserve the right for changes without notice

2.2 SET/DM3AL sensor 2.3 Junction box SET/DM3AL sensor should be installed as described in figure 3. The sensor gives an alarm when the upper electrode is in oil. Please check the correct installation depth also from the instructions of the oil separator. During maintenance procedures (such as servicing the fuel separator systems), the sensor should not be lifted out of the separator tank or installed again until there is water in the tank. If the sensor cable must be extended or there is a need for equipotential grounding, it can be done with the cable junction box. The cabling between the OilSET-1000 control unit and the junction box should be done with a shielded twisted pair instrument cable. LJB2 junction box enables cable extension in potentially explosive atmospheres. The junction box can be installed inside the separator by mounting it to the separator or with a separate mounting hook. In figure 3 the shields and possible excess wires need to be connected to the same point in galvanic contact with metallic frame of the junction box. This point can be connected to equipotential ground thru the ground terminal. Other components of the system that need to be grounded can also be connected to the same ground terminal. The wire used for equipotential grounding must be min. 2.5 mm² mechanically protected or, when not protected, the minimum cross section is 4 mm². Please make sure, that the sensor and cable between OilSET-1000 control unit and the sensor do not exceed the maximum allowed electrical parameters see chapter 7 Technical data. Detailed cabling instructions can also be found in the document SET/DM3AL. Junction box of type LJB2 includes light alloy parts. When installing in explosive atmosphere, make sure, that the junction box is located so, that it can not be mechanically damaged or it will not be exposed to external impacts, friction etc. causing ignition of sparks. Make sure, that the junction box is closed properly. Copyright 2012 Labkotec Oy 5/13 We reserve the right for changes without notice

3 OPERATION AND SETTINGS Functionality test 3.1 Operation Normal mode no alarms Oil alarm The OilSET-1000 alarm device is initialized at the factory. The operation of the alarm device should be checked always after the installation. 1. Immerse the sensor into water. The device should be in normal mode. 2. Lift the sensor up in air or oil. An Oil alarm should be generated (see chapter 3.1 for more detailed description). 3. Immerse the sensor back into water. The alarm should go off after a delay of 5 sec. Clean up the sensor if necessary before placing it back into the oil separator. A more detailed description of the operation is provided in chapter 3.1. If the operation is not as described here, check the factory settings (chapter 3.2.) or contact a representative of the manufacturer. The operation of a factory-initialized OilSET-1000 is described in this chapter. SET/DM3AL sensor is totally immersed in water. Mains LED indicator is on. Other LED indicators are off. Relays 1 and 2 are energized. SET/DM3AL sensor is immersed in oil. (The sensor gives an alarm when the upper electrode is in oil.) Mains LED indicator is on. Oil Alarm LED indicator is on. Buzzer on after 5 sec delay. Relays de-energize after 5 sec delay. (Note. The same alarm takes place when SET/DM3AL sensor is in the air.) After removal of an alarm, the Oil Alarm LED indicator and buzzer will be off, and relays will be energized after a fixed delay of 5 sec. Fault alarm Reset of an alarm Sensor cable break, short circuit or a broken sensor, i.e. too low or too high sensor signal current. Mains LED indicator is on. Sensor circuit Fault LED indicator is on after 5 sec delay. Buzzer is on after 5 sec delay. The relays de-energize after 5 sec delay. When pressing the Reset push button. Buzzer will go off. Relay 1 energizes. Relay 2 will stay de-energized until the actual alarm or fault is off. TEST FUNCTION Test function provides an artificial alarm, which can be used to test the function of the OilSET-1000 alarm device and the function of other equipment, which are connected to OilSET-1000 via its relays. Attention! Before pressing the Test button, make sure that the change of relay status does not cause hazards elsewhere! Copyright 2012 Labkotec Oy 6/13 We reserve the right for changes without notice

Normal situation Alarm on Fault alarm on 3.2 Factory settings When pressing the Test push button: Oil Alarm and Fault LED indicators are immediately on. Buzzer is immediately on. Relays de-energize after 2 sec of continuous pressing. When the Test push button is released: LED indicators and buzzer go immediately off. Relays energize immediately. When pressing the Test push button: Fault LED indicator is immediately on. Oil Alarm LED indicator remains on. Buzzer remains on. If it has been reset earlier, it will return to be on. If relay 1 was already reset, it will de-energize again after 2 sec. of continuous pressing. Test will not affect relay 2, because it is already in alarm status. When the Test push button is released: The device returns without delay to the preceding status. When pressing the Test push button: The device does not react to the test at all. If the operation of OilSET-1000 is not as described in the previous chapter, check that the device settings are as in figure 4. Change the settings according to the following instructions if needed. The following tasks must only be executed by a person with proper education and knowledge of Ex-i devices. We recommend, that when altering the settings the mains voltage is off or the device is initialized before the installation is executed. Figure 4. Factory settings The settings are made with switches (MODE and DELAY) and potentiometer (SENSITIVITY) located in the upper printed circuit board, and the jumper located in the lower board (figure 4). In figure 4, the switches and the potentiometer are as set in the factory. Switch S2 is used to set the operational delay of the control unit. When the switch is in low position, relays operate and buzzer is on after 5 seconds after the level has reached the trigger level, and if the level still remains on the same side of the trigger level. When the switch is in high position, the delay is 30 seconds. Delays are operational in both directions (energizing, de-energizing). Alarm LED follows the sensor current value and trigger level without delay. Fault alarm takes place after a fixed delay of 5 sec. Copyright 2012 Labkotec Oy 7/13 We reserve the right for changes without notice

4 TROUBLE-SHOOTING Problem: Possible reason: To do: MAINS LED indicator is off Supply voltage is too low or the fuse is blown. Transformer or MAINS LED indicator is faulty. 1. Check if the two pole mains switch is off. 2. Check the fuse. 3. Measure the voltage between poles N and L1. It should be 230 VAC + 10 %. Problem: Possible reason: To do: No alarm when sensor in oil or air, or the alarm will not go off The SENSITIVITY setting is wrong in the control unit (see figure 4), or sensor is dirty. 1. Clean-up the sensor and immerse it into oil. If it s not possible lift it up in the air. 2. Turn the SENSITIVITY potentiometer to its fully anticlockwise position and the slowly clockwise until the sensor gives an alarm and after that ¼ turn more. 3. Immerse the sensor into water and wait until the alarm goes off. If the alarm does not go off, turn the potentiometer slowly clockwise until the alarm goes off. 4. Lift the sensor up in the air or oil. The sensor should give an alarm again. Problem: Possible reason: To do: FAULT LED indicator is on Current in sensor circuit too low (cable break) or too high (cable in short circuit). The sensor might also be broken. 1. Make sure, that the sensor cable has been connected correctly to the OilSET- 1000 control unit. See sensor specific instructions. 2. Measure the voltage separately between the poles 10 and 11. The voltages should be between 10,3.11,8 V. 3. If the voltage is correct, measure the sensor current. Do as follows: 3.1 Disconnect sensor s [+] wire from sensor connector (pole 10). 3.2 Measure short circuit current between [+] and [-] poles. 3.3 Connect ma-meter as in figure 5. Make a comparison to the values in Table 1. 3.4 Connect the wire back to the connector. If the problem can not be solved with the above instructions, please contact Labkotec Oy s local distributor or Labkotec Oy s service. Attention! If the sensor is located in an explosive atmosphere, the multimeter must be Exi-approved! Figure 5. Sensor current measurement Shortcircuit Sensor in the air Sensor in oil (εr. 2) Sensor in the water Factory setting for alarm point (see Fig. 7.) SET/DM3AL, channel 1 Poles 10 [+] ja 11 [-] 20 ma 24 ma 9 11 ma 9 11 ma 3-4 ma Table 1. Sensor currents approx. 6.5 ma Copyright 2012 Labkotec Oy 8/13 We reserve the right for changes without notice

5 REPAIR AND SERVICE The sensor should be cleaned and the operation should also be tested when emptying the oil storage chamber or at least once every six months. The easiest way to check the operation is to lift the sensor up in the air and to put it back to the separator. The operation is described in chapter 3. For cleaning, a mild detergent (e.g. washing-up liquid) and a scrubbing brush can be used. The mains fuse (marked 125 mat) can be changed to another glass tube fuse 5 x 20 mm / 125 mat complying IEC/EN 60127-2/3. Any other repair and service works on the device may be carried out only by a person who has received training in Ex-i devices and is authorized by the manufacturer. In case of queries, please contact Labkotec Oy s service: labkotec.service@labkotec.fi. Environment-Agency Pollution Prevention Guidelines (PPG3): Any electrical device used within a separator or used to monitor sensors placed within a separator must be intrinsically safe and certified to a suitable explosion protection standard. The location of the monitoring device, such as the alarm or 'separator management system' control panel, must be located within a safe area and conform to the requirements of BS EN 60079-10. For this reason it is important to always use qualified technicians who are familiar with the installation, calibration and servicing of intrinsically safe equipment. Regular maintenance and testing of equipment is essential. 6 SAFETY INSTRUCTIONS OilSET-1000 control unit must not be installed in potentially explosive atmosphere. Sensors connected to it may be installed in zone 0, 1 or 2 potentially explosive atmospheres. In case of installations in explosive atmospheres the national requirements and relevant standards as IEC/EN 60079-25 and/or IEC/EN 60079-14 must be taken into account. Warning! If the cabling is voltage-tested, the sensor must be disconnected. If electrostatic discharges can cause hazards in the operating environment, the device must be connected into equipotential ground according to requirements with regards to explosive atmospheres. Equipotential grounding is made by connecting all conductive parts into same potential e.g. at the cable junction box. Equipotential ground must be earthed. The device does not include a mains switch. A two pole mains switch (250 VAC 1 A), which isolates both lines (L1, N) must be installed in the main power supply lines in the vicinity of the unit. This switch facilitates maintenance and service operations and it has to be marked to identify the unit. When executing service, inspection and repair in explosive atmosphere, the rules in standards IEC/EN 60079-17 and IEC/EN 60079-19 about instructions of Ex-devices must be obeyed. Copyright 2012 Labkotec Oy 9/13 We reserve the right for changes without notice

7 TECHNICAL DATA OilSET-1000 control unit Dimensions 175 mm x 125 mm x 75 mm (L x H x D) Enclosure IP 65, material polycarbonate Ambient temperature -25 ºC +50 ºC Supply voltage Power consumption Sensors Max. resistance of the current loop between the control unit and a sensor Relay outputs 230 VAC ± 10 %, 50/60 Hz Fuse 5 x 20 mm 125 mat (IEC/EN 60127-2/3) The device is not equipped with a mains switch 2 VA One SET sensor (SET/DM3AL) 75 Ω. Two potential-free relay outputs 250 V, 5 A, 100 VA Operational delay 5 sec or 30 sec. Relays de-energize at trigger point. Operation mode selectable for increasing or decreasing level. Electrical safety IEC/EN 61010-1, Class II, CAT II / III Insulation level Sensor / Mains supply voltage EMC Ex-classification Emission Immunity 375V (IEC/EN 60079-11) IEC/EN 61000-6-3 IEC/EN 61000-6-2 II (1) G [Ex ia] IIC SET/DM3AL sensor Principle of operation Signal Supply voltage Material IP-classification Measurement of conductivity Analog 3 ma / 10 ma 8 V 16 V (DC) PVC (black); AISI 316, NBR, PA IP68 Temperature Operation: 0 ºC +60 ºC Safety: -30 ºC +60 ºC Cable Shielded oil-proof cable 2 x 0.75 mm 2. Standard length 5 m. Other lengths optional. The max. length of the fixed cable is 15 m. Can be extended with a shielded cable. The recommended maximum cable loop resistance is 75 Ω. EMC Ex-classification Emission Immunity Special conditions (X) ATEX IECEx IEC/EN 61000-6-3 IEC/EN 61000-6-2 II 1 G Ex ia IIA T5 Ga (Ta -30 ºC +60 ºC) The risk of electrostatic charge must be observed! VTT 09 ATEX 026X IECEx VTT 10.0001X Electrical parameters Ui = 16 V Ii = 80 ma Pi= 400 mw Ci = 3500 pf Li = 85 μh Manufacturing year: Please see the serial number on the type plate x xxx x xxxxx xx YY x where YY = manufacturing year (e.g. 12 = 2012) Special conditions (X) ATEX IECEx (Ta = -25 C +50 C) VTT 04 ATEX 031X IECEx VTT 10.0003X Electrical parameters Characteristic curve of the output voltage is trapezoidal See table 2. U o = 14,7 V P o = 297 mw I o = 55 ma R = 404 Ω Manufacturing year: Please see the serial number on the type plate xxx x xxxxx xx YY x where YY = manufacturing year (e.g. 12 = 2012) Due to non-linear characteristics of the sensor voltage, the interaction of both, capacitance and inductance, must be taken into account. The table below indicates the connecting values in explosion groups IIC and IIB. In explosion group IIA the values of the group IIB can be applied. Max. permissible value Combined Co and Lo Co Lo Co Lo II C 608nF 10 mh 568nF 458 nf 388 nf 328 nf 258 nf 0,15 mh 0,5 mh 1,0 mh 2,0 mh 5,0 mh II B 3,84μF 30 mh 3,5 µf 3,1 µf 2,4 µf 1,9 µf 1,6 µf 0,15 mh 0,5 mh 1,0 mh 2,0 mh 5,0 mh L o /R o = 116,5 µh/ω (IIC) and 466 µh/ω (IIB) Table 2. OilSET-1000 electrical parameters Figure 6. Dimensional drawing of SET/DM3AL sensor Copyright 2012 Labkotec Oy 10/13 We reserve the right for changes without notice